CEN-GWEXER Setup
CEN-GWEXERs are a two-way radiofrequency (RF) transceivers that allow Crestron infinetEX and Extended Range wireless devices to communicate with the control processor over Ethernet. They are for Crestron wireless systems what DIN-CENCN-2s are for wired Cresnet systems.
For SHOWRUNNER™ installations, the IP address of the CEN-GWEXER does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. Instead, CEN-GWEXERs are identified to the processor via their IP-ID. Note that which infinetEX devices are landed at which CEN-GWEXER matters, and if devices are moved between CEN-GWEXERs then the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet with an IP Table tab that lists all the CEN-GWEXER IP-IDs in the program. If no takeoff is provided, then the processor's IP table can be checked by running the ipt -t command from the processor after the configuration is loaded. DIN-CENCN-2's will typically have IP-IDs in the "Cx" range.
IP Configuration
Typically, each CEN-GWEXER will need to be initially configured via USB (micro USB), unless their MAC addresses are already known and the lighting network has a DHCP server (either by running DHCP server software on your computer, or if the processor has a control subnet or is running the ShowRunner™ DHCP Server).
CEN-GWEXERs for the first time, it may be necessary to manually change the connection type from "Auto" to "SSL/TLS". It is also necessary to manually edit the CEN-GWEXER's address book entry so that the connection protocol is "SSL/TLS" when a CEN-GWEXER is added to the address book using Device Discovery tool export.
Whether connected to the CEN-GWEXER via USB or Ethernet, the process to configure the static IP addresses is the same:
- Open Text Console in Toolbox and connect to the CEN-GWEXER
- Note that you may need to manually select "SSL" connection type, as "Auto" might not always redirect
- Run the following commands to configure the CEN-GWEXER's static IP settings (example is for a 10.0.0.0/24 subnet, with a static IP address of 10.0.0.12, an IP-ID of C1, and a target processor IP address of 10.0.0.10, and a device hostname of GWEXER-L1)
- Set IP address: ipa 0 10.0.0.12
- Set IP subnet mask: ipm 0 255.255.255.0
- Set default gateway: defr 0 10.0.0.1
- Disable DHCP: dhcp off
- Update IP table: addm C1 10.0.0.10
- Set hostname: host GWEXER-L1
- Reboot the CEN-GWEXER: reboot
- Repeat for all CEN-GWEXERs on the job
SSL Setup
Crestron devices that support SSL require the use of a secure connection between the processor and the device. In order to establish this secure connection, the processor must have authentication enabled and there must be a user on the processor with "Connects" group permissions.
Configure the Connects user on the processor:
- Ensure the processor has its IP configured and authentication enabled
- Verify the processor has authentication enabled by running the command: auth without any parameters
- Create a user by running the following commands, replacing the "username" and "password" with your desired credentials
- adduser -N:username -P:password
- addusertogroup -N:username -G:Connects
- Verify that the user has been created by running the command: listusers
- This process only needs to be performed once per processor on the jobsite
Configure the CS authentication on the CEN-GWEXER:
- Run the following command, replacing the "username" and "password" with the credentials of the Connects user from the previous step
- setcsauth -N:username -P:password
- Repeat this process for every CEN-GWEXER on the jobsite
RF Channel
Lorem
//"RFCHAnnel [#]" set rf channel for gwexer
Acquiring Devices
//1-2-3-hold on 4 until all lights blink, then release
top light will blink slowly a few times and then hold solid or start blinking rapidly
if rapid blinking, cancel acquire and make sure that rf gateway is in acquire mode and device is in range then repeat to put device into acquire mode
Text Console
//"acquire start" and "acquire stop"
//"rep" to show acquired devices
Gateway Configuration Tool
//Connect > functions > gateway configuration for better acquiring tool
Moving/Removing Devices (Unacquiring Devices)
When a wireless Crestron device is acquired to a new gateway using the typical acquiring process described above, it will automatically forget the previously connected gateway. The gateway itself, however, must manually "forget" the previously connected device before a newly acquired and addressed device will function correctly. This is necessary whether the originally connected device is moved or if the originally corrected device has failed and is being replaced.
To unacquire a device from a gateway, it is necessary to run the below commands, replacing "[TSID]" with either the 4-byte hexadecimal TSID of a single device or "all" to forget all previously acquired devices. Devices do not need to be online in order to be acquired (e.g., a failed device can still be unacquired using this method). While only one of these commands needs to be run per device, it is not documented which command (ending in "0" or "1") is required for each model, so it is generally advisable to run both commands for each device to be unacquired:
- unacquirebytsid [TSID] 0
- unacquirebytsid [TSID] 1
Once all of the necessary TSIDs have been unacquired, use the reboot command to reboot the gateway and complete the unacquire process.