Wiki source code of Crestron Zūm Wireless

Version 3.28 by Mark Kohlmann on 2020/04/14 21:12

Hide last authors
Mark Kohlmann 1.1 1 Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
2
3 ==== Integration Options ====
4
5 * SHOWRUNNER™ Total Control - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB.
6 * SHOWRUNNER™ + AVBRIDGE + Serial Port - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
7 * SHOWRUNNER™ + ZUM-FLOOR-HUB - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
8
9 ==== Feature Matrix ====
10
Mark Kohlmann 3.24 11 |=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ + AVBRIDGE + Serial Port|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
Mark Kohlmann 1.2 12 |(% colspan="6" %)**Hardware Requirements**
Mark Kohlmann 1.1 13 |Requires JBOX and ZUMMESH-NETBRIDGE|Y|N|Y|Y|Y
14 |Requires ZUMMESH-GATEWAY|Y|N|Y|Y|N/A
15 |Requires RS-232 Serial Port per Room|N|Y|N|N|N/A
Mark Kohlmann 1.2 16 |Physical Presence in Room to Change Scenes|N|N|Y, via Zūm Setup App|Y, via Zūm Setup App|Y
17 |(% colspan="6" %)**User Interfaces**
18 |Web Browser|(((
19 Crestron SmartGraphics XPanel
20 HTML5 UI Under Development (Q4 2020)
21 )))|Crestron SmartGraphics XPanel
22 HTML5 UI Under Development (Q4 2020)|SHOWRUNNER™ - Crestron SmartGraphics XPanel
23 ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
Mark Kohlmann 3.1 24 |iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
Mark Kohlmann 1.2 25 |Touchscreens (Crestron TSW series)|Y|Y|Y, Limited Features for Zūm Rooms|N|N
26 |(% colspan="6" %)**Features**
27 |Scene Recall|Y|Y|Y|Y|Y
28 |Override Fade Time for Scene Recall~*~*|Y|N|N|N|N
29 |Scene Save|Y|Y|N|N|Y
30 |Load Control|Y|Y|N|N|Y
31 |Demand Response|Y|N|Y, separate triggers for SHOWRUNNER™ and ZUM-FLOOR-HUB required|Y|N
32 |Enable/Disable Occupancy|Y|Y|Y, from Floor Hub|Y|Y
33 |Override Occupancy Logic|Y|Y|N|N|N
Mark Kohlmann 2.1 34 |Plug Load On/Off|Y|Y|Y|Y|By Hardware
Mark Kohlmann 3.24 35 |Integration with Non-Zūm Crestron Hardware|Y|Y|N|N|N
36 |Custom Zūm Keypad Programming|N|Y, Zūm AV Keypad Only|N|N|Y, within the limits of the hardware
Mark Kohlmann 3.20 37 |New Feature Release Cycle|Aggressive|Aggressive|SHOWRUNNER™: Aggressive
38 Floor Hub: 6-12 months|6-12 months|6-12 months
Mark Kohlmann 3.24 39 |Room Organization|(((
40 Under Development:
41 Building/Floor/Sub-Group/Area
42 Categorization to Filter by Different Types
43 )))|See SHOWRUNNER™ Total Control|SHOWRUNNER™: See SHOWRUNNER™ Total Control
44 Floor Hub: Category/Room|Category/Room|(((
45 N/A
46 )))
Mark Kohlmann 2.1 47 |(% colspan="6" %)**Calendar/Scheduling**
Mark Kohlmann 3.1 48 |Logic Type|Event Driven
49 Profile Support (Under Development)|Event Driven
50 Profile Support (Under Development)|SHOWRUNNER™: Event Driven
51 Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
52 |Astronomical Clock|Y|Y|Y|Y|N/A
53 |Holidays|Pattern|Pattern|SHOWRUNNER™: Pattern
54 Floor Hub: Hard Coded|Hard Coded|N/A
55 |Custom Patterns|Y, Advanced Scheduler License|Y, Advanced Scheduler License|SHOWRUNNER™: Y, Advanced Scheduler License
56 Floor Hub: N|N|N/A
Mark Kohlmann 3.11 57 |(% colspan="6" %)**Integrations**
Mark Kohlmann 3.20 58 |A/V Integration: API|Y|Y|SHOWRUNNER™: Y
59 Floor Hub: Limited|Limited|N/A
60 |A/V Integration: Crestron EISC|Y|Y|SHOWRUNNER™: Y
61 Floor Hub: N|N|N/A
62 |A/V Integration: RS-232|Y|Y|(((
63 SHOWRUNNER™: Y
64 Floor Hub: AVBRIDGE per Area
65 )))|AVBRIDGE per Area|N/A
Mark Kohlmann 3.11 66 |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
67 SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
68 Floor Hub: Y
Mark Kohlmann 3.13 69 )))|Y|N/A
Mark Kohlmann 3.20 70 |BACNET Features|(((
71 Per Area Status:
72 Active Scene
73 Occupied
74 Occupancy Enabled
75 Individual Load Level
76 Photocell Level (per Photocell)
77
78 System:
79 Demand Response Enabled
80 System Wide Override (Panic/Emergency)
81 )))|See list for SHOWRUNNER™ Total Control|(((
82 SHOWRUNNER™: See list for SHOWRUNNER™ Total Control
83 Floor Hub: See list for ZUM-FLOOR-HUB
84 )))|(((
85 Per Room Status:
86 Online
87 On
88 Occupied
89 Daylighting Active
90 Device Battery is Low
91 Plug Loads Enabled
92 Occupancy Sensor Enabled
93 Current Daylight Level
94 Active Scene
95 \\System:
96 Demand Response Enabled
97 )))|N/A
Mark Kohlmann 3.13 98 |BACNET Settings Scope|Per Area|Per Area|(((
99 SHOWRUNNER™: Per Area
100 Floor Hub: Global
101 )))|Global|N/A
Mark Kohlmann 3.20 102 |Crestron Fusion|Y|Y|(((
103 SHOWRUNNER™: Y
104 Floor Hub: N
105 )))|N|N/A
Mark Kohlmann 3.24 106 |Export to Zūm Floor Hub|Y, Licensed|Y, Licensed|SHOWRUNNER™: Y, Licensed|N/A|N/A
Mark Kohlmann 3.11 107
Mark Kohlmann 1.2 108 ##* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.##
Mark Kohlmann 3.24 109 ##~*~* Fade time is automatically applied if scene is set longer than 1 second.  Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).##