Wiki source code of Zūm Net Device Setup

Version 10.3 by Alexander Mott on 2022/06/17 16:47

Show last authors
1 === Zūm Net Devices in SHOWRUNNER™ ===
2
3 Zūm Net devices are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the local Zūm Link devices in each room to the overall lighting network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]], and Zūm Net is an Ethernet protocol, this means that Zūm Net devices can be thought of as single-net DIN-CENCN-2s. As of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with SHOWRUNNER™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.
4
5 Much like DIN-CENCN-2s in SHOWRUNNER™ installations, ZUMNET-JBOXs identify themselves to the processor via their IP-ID, so the specific IP address of any given ZUMNET-JBOX does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. If hosted devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet which will list all the Zūm Net and Zūm Link devices and their associated IP-IDs. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
6
7 === Identification and IP Configuration ===
8
9 Configuring ZUMNET-JBOXs must be done over Ethernet, and is easiest to do once all ZUMNET-JBOXs have been installed, powered up, and connected to the lighting network. (It is not necessary for all Zūm Link devices to be installed in order to configure ZUMNET-JBOXs.)
10
11 Since there is no option to configure ZUMNET-JBOXs via USB, a DHCP server is required. There are three options for DHCP servers:
12
13 * Using a processor with a Control Subnet (only available on certain processors)
14 * Using the built-in [[SHOWRUNNER™ DHCP Server>>doc:SHOWRUNNER™ User Guide & Wiki.Troubleshooting.DHCP Server.WebHome]] (available on all processors running SHOWRUNNER™ v3.009 or newer)
15 * Using third party DHCP server software on your computer
16
17 Most devices (DIN-CENCN-2, TSW, ZUMNET-JBOXs) rely only on IP-ID to identify themselves to the processor, but some devices (such as GLPACs, DMX controllers, and other processors) have IP addresses that are explicitly defined in the configuration file. The DHCP server should be configured to assign IP addresses that are visible to the processor, but excluded from assigning these explicitly defined IP addresses if possible.
18
19 Configuring ZUMNET-JBOXs can be broken up into two separate processes:
20
21 1. Identifying which DHCP assigned IP address corresponds to each ZUMNET-JBOX
22 1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP address and IP-ID
23
24 ==== Identifying ZUMNET-JBOXs ====
25
26 Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID.
27
28 There are three primary ways of identifying ZUMNET-JBOXs:
29
30 1. Identifying by hostname
31 1. Identifying by serial number or MAC address
32 1. Identifying through Toolbox
33
34 Each of these methods involves generating a Device Summary using the Device Discovery Tool in Toolbox. The Device Summary is a file which lists all devices that are discoverable on the network along with useful information such as their hostname, IP address, and MAC address.
35
36 To generate a Device Summary in Toolbox:
37
38 * Connect to the lighting network and open Device Discovery Tool in Toolbox
39 * The Device Discovery tool will automatically report how many Ethernet devices have been discovered
40 * Verify that the expected number of Ethernet devices have been discovered, including any TSWs, GLPACs, DIN-CENCN-2s, etc.
41 ** Note that only Crestron devices will appear in Device Discovery; non-Crestron devices (such as Pharos or Enttec DMX controllers) will not appear in Device Discovery Tool
42 ** If no devices are discovered, verify that your computer is connected to the network and your IP address is compatible with the network
43 ** If some devices are missing, there may be an issue with your DHCP server settings or the network wiring
44 * Click the "Export..." button below the list of discovered devices
45 ** If this button says "Address Book", then Toolbox needs to be updated
46 * Click the Write Device Summary button and save the DeviceSummary.txt to your computer
47 * The DeviceSummary.txt provides the IP address, MAC address, and serial number for each device on the network
48 * Cross reference the DeviceSummary.txt with the serial numbers/MAC addresses provided by the installer in order to determine which ZUMNET-JBOX has been assigned each IP address
49 * Update the SRTakeoff.xlsx with the device serial number, MAC address, and automatically assigned IP address for all ZUMNET-JBOXs
50
51 ===== Identifying by Hostname =====
52
53 Oftentimes,
54
55 If the electrical contractor has provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is relatively easy to identify which ZUMNET-JBOX should get which IP-ID:
56
57 * Connect to the lighting network and open Device Discovery Tool in Toolbox
58 * The Device Discovery tool will automatically report how many Ethernet devices have been discovered
59 ** Verify that the correct number of Ethernet devices have been discovered, including any TSWs, GLPACs, DIN-CENCN-2s, etc.
60 ** Note that only Crestron devices will appear in Device Discovery; non-Crestron devices (such as Pharos or Enttec DMX controllers) will not appear in Device Discovery Tool
61 * Click the "Export..." button below the list of discovered devices
62 ** If this button says "Address Book", then Toolbox needs to be updated
63 * Click the Write Device Summary button and save the DeviceSummary.txt to your computer
64 * The DeviceSummary.txt provides the IP address, MAC address, and serial number for each device on the network
65 * Cross reference the DeviceSummary.txt with the serial numbers/MAC addresses provided by the installer in order to determine which ZUMNET-JBOX has been assigned each IP address
66 * Update the SRTakeoff.xlsx with the device serial number, MAC address, and automatically assigned IP address for all ZUMNET-JBOXs
67
68 If the electrical contractor has not provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is necessary to connect to each ZUMNET-JBOX individually and identify them through Toolbox. Putting a device into identify will stop any programs running on a processor, and taking a device out of identify mode will restart the program. This starting/stopping of the program can be time consuming when a large number of devices are being identified, so it may be a good idea to run the ##stopprog -p:01## command on the processor prior to identifying devices. Once all the devices are identified, run the ##progreset## command to resume the program.
69
70 * Connect to the lighting network and open Device Discovery Tool in Toolbox
71 * Note the IP addresses for all of the installed ZUMNET-JBOXs
72 * Connect to the first ZUMNET-JBOX using Network Device Tree View
73 * Locate the "ZUMNET-JBOX-xx-xx-LOCAL" device in the list of connected devices
74 ** The model will vary between 0-10V and DALI JBOXs
75 ** The ID should be "03" regardless of model
76 * Right click the device and press "Identify This Device..." from the context menu
77 * The device will blink any attached fixtures and make an alarm sound
78 * Walk around the jobsite until the room/controlled fixtures are located
79 * Update the SRTakeoff.xlsx with the device serial number, MAC address, and automatically assigned IP address
80 * Repeat all steps for each ZUMNET-JBOXs until all of the ZUMNET-JBOXs have been identified
81
82 ==== Assigning Permanent Static IP Addresses and IP-IDs ====
83
84 Once you have identified which IP address has been assigned to each ZUMNET-JBOX, you can begin configuring them with permanent static IP addresses and the correct IP-ID:
85
86 * Open Text Console in Toolbox and connect to the first ZUMNET-JBOX
87 * Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.80**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%))
88 ** Disable DHCP: ##dhcp off##
89 ** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.80**(%%)##
90 ** Set IP subnet mask: ##ipm 0 (% style="color:darkgoldenrod" %)**255.255.255.0**(%%)##
91 ** Set default gateway: ##defr 0 **10.0.0.1**##
92 ** Update IP table: ##addm (% style="color:olive" %)**30**(%%) (% style="color:orange" %)**10.0.0.10**(%%)##
93 ** Set hostname: ##host (% style="color:purple" %)**ZNET-JBOX-RM-201**(%%)##
94 ** Reboot the ZUMNET-JBOX: ##reboot##
95 * Repeat for all ZUMNET-JBOXs on the job
96
97 === Zūm Net Specific Configuration ===
98
99 Zūm Net devices have a two additional settings not present for other devices: Zūm/Cresnet mode and Master/Slave mode.
100
101 ==== Zūm/Cresnet Mode ====
102
103 ZUMNET-JBOXs should ship in "Zūm Mode" by default, also known as "App Mode" because this is the setting required to be able to configure Zūm Wired rooms using the Crestron Zūm Mobile App.
104
105 If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the App and all internal logic will be disabled. Generally, Cresnet mode is only required if non Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads).
106
107 The commands to view or change the Zūm/Cresnet mode are:
108
109 * View current mode: ##zwmode##
110 * Make Zūm/App mode: ##zwmode zum##
111 * Make Cresnet mode: ##zwmode cnet##
112
113 A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it.
114
115 ==== Master/Slave Mode ====
116
117 ZUMNET-JBOXs should ship in "Master" mode by default, and generally this is how they should be configured.
118
119 "Slave" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX. There are two scenarios in which a ZUMNET-JBOX will need to be configured in "Slave" mode:
120
121 1. It is connected to another ZUMNET-JBOX via the Zūm Link bus
122 1. It is being used as a Cresnet device, connected to a processor or DIN-CENCN-2 using a Cresnet/Zūm Link adapter
123
124 The commands to view or change the Master/Slave mode are:
125
126 * View current mode: ##zwms##
127 * Make "master": ##zwms master##
128 * Make "slave": ##zwms slave##
129
130 A reboot is required if the mode is to be changed.
131
132 === Changing IP-IDs ===
133
134 If ZUMNET-JBOXs must be assigned different IP-IDs than indicated in the SRTakeoff.xlsx, or if Zūm Link devices are moved between ZUMNET-JBOXs, then the configuration file must be updated. Every Zūm Link device in the configuration has a ##"DeviceHostId"## associated with it, which corresponds to the IP-ID of the ZUMNET-JBOX hosting it.
135
136 If a Zūm Link device is moved from one ZUMNET-JBOX to another, then this ##"DeviceHostId"## must be updated with the IP-ID of the new device.
137
138 If a ZUMNET-JBOX is assigned a different IP-ID, then it's own ##"DeviceHostId"## as well as the ##"DeviceHostId"## for all hosted Zūm Link devices must be changed to the new IP-ID. In addition to changing these ##"DeviceHostId"##, the ##"IpId"## for the associated entry in ##"IpDevices"## must be updated. ##"IpDevices"## are located towards the beginning of the configuration file. Note that while the ##"DeviceHostId"## is in hexadecimal, the ##"IpId"## is a decimal integer. This means that a ZUMNET-JBOX with ##"DeviceHostId": "31"## would be associated with an entry in ##"IpDevices"## with ##"IpId": 49##
139
140 Below are two snippets from a configuration file comparing a ZUMNET-JBOX-16A-LV lighting controller and it's associated entry in ##"IpDevices"##:
141
142 [[image:1655247008527-737.png]]
143
144 [[image:1655246948921-246.png]]