... ... @@ -21,10 +21,20 @@
21 21  1. Identifying which DHCP assigned IP address corresponds to each ZUMNET-JBOX
22 22  1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP address and IP-ID
23 23  
24 -==== Identifying Zūm Net Devices ====
24 +==== Identifying ZUMNET-JBOXs ====
25 25  
26 26  Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID.
27 27  
28 +There are three primary ways of identifying ZUMNET-JBOXs:
29 +
30 +1. Identifying by hostname
31 +1. Identifying by serial number or MAC address
32 +1. Identifying through Toolbox
33 +
34 +===== Identifying by Hostname =====
35 +
36 +Oftentimes,
37 +
28 28  If the electrical contractor has provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is relatively easy to identify which ZUMNET-JBOX should get which IP-ID:
29 29  
30 30  * Connect to the lighting network and open Device Discovery Tool in Toolbox
... ... @@ -69,12 +69,39 @@
69 69  
70 70  === Zūm Net Specific Configuration ===
71 71  
72 -Zūm Net devices have
82 +Zūm Net devices have a two additional settings not present for other devices: Zūm/Cresnet mode and Master/Slave mode.
73 73  
74 -App vs Cresnet mode
84 +==== Zūm/Cresnet Mode ====
75 75  
76 -Master vs Slave
86 +ZUMNET-JBOXs should ship in "Zūm Mode" by default, also known as "App Mode" because this is the setting required to be able to configure Zūm Wired rooms using the Crestron Zūm Mobile App.
77 77  
88 +If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the App and all internal logic will be disabled. Generally, Cresnet mode is only required if non Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads).
89 +
90 +The commands to view or change the Zūm/Cresnet mode are:
91 +
92 +* View current mode: ##zwmode##
93 +* Make Zūm/App mode: ##zwmode zum##
94 +* Make Cresnet mode: ##zwmode cnet##
95 +
96 +A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it.
97 +
98 +==== Master/Slave Mode ====
99 +
100 +ZUMNET-JBOXs should ship in "Master" mode by default, and generally this is how they should be configured.
101 +
102 +"Slave" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX. There are two scenarios in which a ZUMNET-JBOX will need to be configured in "Slave" mode:
103 +
104 +1. It is connected to another ZUMNET-JBOX via the Zūm Link bus
105 +1. It is being used as a Cresnet device, connected to a processor or DIN-CENCN-2 using a Cresnet/Zūm Link adapter
106 +
107 +The commands to view or change the Master/Slave mode are:
108 +
109 +* View current mode: ##zwms##
110 +* Make "master": ##zwms master##
111 +* Make "slave": ##zwms slave##
112 +
113 +A reboot is required if the mode is to be changed.
114 +
78 78  === Changing IP-IDs ===
79 79  
80 80  If ZUMNET-JBOXs must be assigned different IP-IDs than indicated in the SRTakeoff.xlsx, or if Zūm Link devices are moved between ZUMNET-JBOXs, then the configuration file must be updated. Every Zūm Link device in the configuration has a ##"DeviceHostId"## associated with it, which corresponds to the IP-ID of the ZUMNET-JBOX hosting it.