1 -=== Zūm Net Devices in SHOWRUNNER™ ===
1 +=== ZUMNET-JBOXs in SHOWRUNNER™ ===
2 2  
3 -Zūm Net devices are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the local Zūm Link devices in each room to the overall lighting network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]], and Zūm Net is an Ethernet protocol, this means that Zūm Net devices can be thought of as single-net DIN-CENCN-2s. As of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with SHOWRUNNER™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.
3 +ZUMNET-JBOXs are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the Zūm Link network in each room to the Zūm Net network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]] and Zūm Net is an Ethernet protocol, this means that ZUMNET-JBOXs can be thought of as single-net DIN-CENCN-2s.
4 4  
5 -Much like DIN-CENCN-2s in SHOWRUNNER™ installations, ZUMNET-JBOXs identify themselves to the processor via their IP-ID, so the specific IP address of any giveZUMNET-JBOX does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. If hosted devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet which will list all the Zūm Net and Zūm Link devices and their associated IP-IDs. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
5 +Much like DIN-CENCN-2s in SHOWRUNNER™ installations, the IP address of the ZUMNET-JBOX also does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. Instead, ZUMNET-JBOXs are identified to the processor via their IP-ID. If devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, then the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet with an IP Table tab that lists all the ZUMNET-JBOX IP-IDs in the program. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
6 6  
7 7  === Identification and IP Configuration ===
8 8  
... ... @@ -19,11 +19,11 @@
19 19  Configuring ZUMNET-JBOXs can be broken up into two separate processes:
20 20  
21 21  1. Identifying which DHCP assigned IP address corresponds to each ZUMNET-JBOX
22 -1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP address and IP-ID
22 +1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP and the correct IP-ID
23 23  
24 -==== Identifying Zūm Net Devices ====
24 +==== Identifying ZUMNET-JBOXs ====
25 25  
26 -Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID.
26 +Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID.
27 27  
28 28  If the electrical contractor has provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is relatively easy to identify which ZUMNET-JBOX should get which IP-ID:
29 29  
... ... @@ -33,12 +33,12 @@
33 33  ** Note that only Crestron devices will appear in Device Discovery; non-Crestron devices (such as Pharos or Enttec DMX controllers) will not appear in Device Discovery Tool
34 34  * Click the "Export..." button below the list of discovered devices
35 35  ** If this button says "Address Book", then Toolbox needs to be updated
36 -* Click the Write Device Summary button and save the DeviceSummary.txt to your computer
36 +* Click the Write Device Summary and save the DeviceSummary.txt to your computer
37 37  * The DeviceSummary.txt provides the IP address, MAC address, and serial number for each device on the network
38 38  * Cross reference the DeviceSummary.txt with the serial numbers/MAC addresses provided by the installer in order to determine which ZUMNET-JBOX has been assigned each IP address
39 39  * Update the SRTakeoff.xlsx with the device serial number, MAC address, and automatically assigned IP address for all ZUMNET-JBOXs
40 40  
41 -If the electrical contractor has not provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is necessary to connect to each ZUMNET-JBOX individually and identify them through Toolbox. Putting a device into identify will stop any programs running on a processor, and taking a device out of identify mode will restart the program. This starting/stopping of the program can be time consuming when a large number of devices are being identified, so it may be a good idea to run the ##stopprog -p:01## command on the processor prior to identifying devices. Once all the devices are identified, run the ##progreset## command to resume the program.
41 +If the electrical contractor has not provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is necessary to connect to each ZUMNET-JBOX individually and identify them individually:
42 42  
43 43  * Connect to the lighting network and open Device Discovery Tool in Toolbox
44 44  * Note the IP addresses for all of the installed ZUMNET-JBOXs
... ... @@ -58,7 +58,7 @@
58 58  
59 59  * Open Text Console in Toolbox and connect to the first ZUMNET-JBOX
60 60  * Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.20**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%))
61 -** Disable DHCP: ##dhcp off##
61 +** Disable DHCP: ##dhcp 0 off##
62 62  ** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.20**(%%)##
63 63  ** Set IP subnet mask: ##ipm 0 (% style="color:darkgoldenrod" %)**255.255.255.0**(%%)##
64 64  ** Set default gateway: ##defr 0 **10.0.0.1**##
... ... @@ -67,10 +67,8 @@
67 67  ** Reboot the ZUMNET-JBOX: ##reboot##
68 68  * Repeat for all ZUMNET-JBOXs on the job
69 69  
70 -=== Zūm Net Specific Configuration ===
70 +=== ZUMNET-JBOX Specific Configuration ===
71 71  
72 -Zūm Net devices have
73 -
74 74  App vs Cresnet mode
75 75  
76 76  Master vs Slave
1655410981707-782.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,1 +1,0 @@
1 -5.6 KB
Content
1655410997733-287.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,1 +1,0 @@
1 -2.6 KB
Content