... ... @@ -128,7 +128,6 @@
128 128  == Updating Firmware ==
129 129  
130 130  {{error}}
131 -(((
132 132  Per Crestron's Zūm Wired firmware v4.01.06 release notes, devices running firmware v3.09.05 or earlier "are not supported for upgrade via the Zum App / Hub / or Toolbox" and users should contact Crestron True Blue Support for upgrade paths when required.
133 133  
134 134  Zūm Wired JBOXs operating as the Primary controller in App mode with firmware versions 4.x.x and above are limited in the number of secondary devices that can be supported on the Zūm Link bus:
... ... @@ -136,8 +136,8 @@
136 136  * ZUMNET-JBOX-DALI : 7 maximum secondary devices
137 137  * ZUMNET-JBOX-~*~** : 14 maximum secondary devices
138 138  * ZUMLINK-JBOX-~*~** : 14 maximum secondary devices
138 +
139 139  These limitations do not apply to JBOXs operating in CNET mode //or// running firmware versions 3.x.x
140 -)))
141 141  {{/error}}
142 142  
143 143  It is best practice to upgrade all Zūm Wired devices to the latest version, or at the very least update all devices to the same firmware version across the job. The recommended process for updating Zūm Wired firmware is:
... ... @@ -227,12 +227,10 @@
227 227  
228 228  === Zūm Mode Auto Switch ===
229 229  
230 -{{error}}
231 -ZUMNET-JBOXs on firmware 4.x.x and above that exceed the maximum allowable ZUMLINK device count must not have Auto Switch enabled. Doing so will result in unintended behavior, including improper app mode functionality and excessive rebooting once reconnected to the processor.
229 +{{error}}ZUMNET-JBOXs on firmware 4.x.x and above that exceed the maximum allowable ZUMLINK device count must not have Auto Switch enabled. Doing so will result in unintended behavior, including improper app mode functionality and excessive rebooting once reconnected to the processor.
232 232  {{/error}}
233 233  
234 -{{warning}}
235 -With Auto Switch enabled, ZUMNET-JBOXs may overwrite the ShowRunnerCLC™ scenes upon reconnecting to the processor: disable auto switch or set scenes both in the App and in ShowRunnerCLC™ to avoid this issue
232 +{{warning}}With Auto Switch enabled, ZUMNET-JBOXs may overwrite the ShowRunnerCLC™ scenes upon reconnecting to the processor: disable auto switch or set scenes both in the App and in ShowRunnerCLC™ to avoid this issue
236 236  {{/warning}}
237 237  
238 238  Zūm Mode Auto Switch is a feature introduced by Crestron in November of 2022 with .puf firmware v1.04.05 (device firmware 1.004.00005). This feature is intended to address concerns that arose from projects using custom programs with ZUMNET-JBOX-* devices in CNET Mode. Previously, if a device in CNET Mode lost connection to the processor, then it would be impossible to maintain any sort of control over the lighting. With Zūm Mode Auto Switch enabled, a ZUMNET-JBOX running in CNET Mode will automatically switch to App Mode and process local logic in the event that it loses connection to the processor.