... ... @@ -1,7 +1,8 @@
1 -{{warning}}
1 +(% class="box warningmessage" %)
2 +(((
2 2  This article is for configuring Zūm Net devices using Crestron Toolbox. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
3 3  For details on using the Zūm Discovery feature to automatically build a ShowRunnerCLC™ configuration based on the Zūm App settings, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.Zūm Discovery.WebHome]].
4 -{{/warning}}
5 +)))
5 5  
6 6  {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
7 7  {{toc/}}
... ... @@ -127,29 +127,18 @@
127 127  
128 128  == Updating Firmware ==
129 129  
130 -{{error}}
131 +(% class="box errormessage" %)
131 131  (((
132 132  Per Crestron's Zūm Wired firmware v4.01.06 release notes, devices running firmware v3.09.05 or earlier "are not supported for upgrade via the Zum App / Hub / or Toolbox" and users should contact Crestron True Blue Support for upgrade paths when required.
133 -)))
134 134  
135 -(((
136 136  Zūm Wired JBOXs operating as the Primary controller in App mode with firmware versions 4.x.x and above are limited in the number of secondary devices that can be supported on the Zūm Link bus:
137 -)))
138 138  
139 -* (((
140 -ZUMNET-JBOX-DALI : 7 maximum secondary devices
141 -)))
142 -* (((
143 -ZUMNET-JBOX-~*~** : 14 maximum secondary devices
144 -)))
145 -* (((
146 -ZUMLINK-JBOX-~*~** : 14 maximum secondary devices
147 -)))
137 +* ZUMNET-JBOX-DALI : 7 maximum secondary devices
138 +* ZUMNET-JBOX-~*~** : 14 maximum secondary devices
139 +* ZUMLINK-JBOX-~*~** : 14 maximum secondary devices
148 148  
149 -(((
150 150  These limitations do not apply to JBOXs operating in CNET mode //or// running firmware versions 3.x.x
151 151  )))
152 -{{/error}}
153 153  
154 154  It is best practice to upgrade all Zūm Wired devices to the latest version, or at the very least update all devices to the same firmware version across the job. The recommended process for updating Zūm Wired firmware is:
155 155  
... ... @@ -171,10 +171,11 @@
171 171  
172 172  == Primary/Secondary Mode ==
173 173  
174 -{{warning}}
164 +(% class="box warningmessage" %)
165 +(((
175 175  Zūm Wired firmware v1.03.27 (device firmware v1.002.00026) updates the terminology from "master"/"slave" to "primary"/"secondary", and changes the ##zwms## command to ##zwps##
176 176  Devices running this newer firmware will not accept commands using "master"/"slave" as arguments.
177 -{{/warning}}
168 +)))
178 178  
179 179  ZUMNET-JBOXs can be in either "Primary" or "Secondary" mode. In most situations, "Primary" is the desired mode of operations, as "Secondary" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX and prevents it from discovering devices on the Zūm Link bus or performing any logic. There are two scenarios in which a ZUMNET-JBOX should be configured in "Secondary" mode:
180 180  
... ... @@ -197,10 +197,6 @@
197 197  
198 198  == Zūm/Cresnet Mode ==
199 199  
200 -{{error}}
201 -ZUMNET-JBOXs on firmware 4.x.x and above that exceed the maximum allowable ZUMLINK device count must be kept in CNET mode and not be allowed into Zūm Mode.
202 -{{/error}}
203 -
204 204  Zūm Mode (also known as App Mode) is the default setting for ZUMNET-JBOXs shipping on newer firmware, and allows them to be configured from the Crestron Zūm App as long as a ZUMLINK-KP is connected to the JBOX. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled.
205 205  
206 206  Generally, ZUMNET-JBOXs do not need to be in Cresnet mode to work with ShowRunnerCLC™ except in specific cases:
... ... @@ -238,10 +238,6 @@
238 238  
239 239  === Zūm Mode Auto Switch ===
240 240  
241 -{{error}}
242 -ZUMNET-JBOXs on firmware 4.x.x and above that exceed the maximum allowable ZUMLINK device count must not have Auto Switch enabled. Doing so will result in unintended behavior, including improper app mode functionality and excessive rebooting once reconnected to the processor.
243 -{{/error}}
244 -
245 245  {{warning}}
246 246  With Auto Switch enabled, ZUMNET-JBOXs may overwrite the ShowRunnerCLC™ scenes upon reconnecting to the processor: disable auto switch or set scenes both in the App and in ShowRunnerCLC™ to avoid this issue
247 247  {{/warning}}