... ... @@ -128,15 +128,27 @@
128 128  == Updating Firmware ==
129 129  
130 130  {{error}}
131 +(((
131 131  Per Crestron's Zūm Wired firmware v4.01.06 release notes, devices running firmware v3.09.05 or earlier "are not supported for upgrade via the Zum App / Hub / or Toolbox" and users should contact Crestron True Blue Support for upgrade paths when required.
133 +)))
132 132  
135 +(((
133 133  Zūm Wired JBOXs operating as the Primary controller in App mode with firmware versions 4.x.x and above are limited in the number of secondary devices that can be supported on the Zūm Link bus:
137 +)))
134 134  
135 -* ZUMNET-JBOX-DALI : 7 maximum secondary devices
136 -* ZUMNET-JBOX-~*~** : 14 maximum secondary devices
137 -* ZUMLINK-JBOX-~*~** : 14 maximum secondary devices
139 +* (((
140 +ZUMNET-JBOX-DALI : 7 maximum secondary devices
141 +)))
142 +* (((
143 +ZUMNET-JBOX-~*~** : 14 maximum secondary devices
144 +)))
145 +* (((
146 +ZUMLINK-JBOX-~*~** : 14 maximum secondary devices
147 +)))
138 138  
149 +(((
139 139  These limitations do not apply to JBOXs operating in CNET mode //or// running firmware versions 3.x.x
151 +)))
140 140  {{/error}}
141 141  
142 142  It is best practice to upgrade all Zūm Wired devices to the latest version, or at the very least update all devices to the same firmware version across the job. The recommended process for updating Zūm Wired firmware is:
... ... @@ -185,9 +185,9 @@
185 185  
186 186  == Zūm/Cresnet Mode ==
187 187  
188 -{{warning}}
200 +{{error}}
189 189  ZUMNET-JBOXs on firmware 4.x.x and above that exceed the maximum allowable ZUMLINK device count must be kept in CNET mode and not be allowed into Zūm Mode.
190 -{{/warning}}
202 +{{/error}}
191 191  
192 192  Zūm Mode (also known as App Mode) is the default setting for ZUMNET-JBOXs shipping on newer firmware, and allows them to be configured from the Crestron Zūm App as long as a ZUMLINK-KP is connected to the JBOX. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled.
193 193  
... ... @@ -229,6 +229,7 @@
229 229  {{error}}
230 230  ZUMNET-JBOXs on firmware 4.x.x and above that exceed the maximum allowable ZUMLINK device count must not have Auto Switch enabled. Doing so will result in unintended behavior, including improper app mode functionality and excessive rebooting once reconnected to the processor.
231 231  {{/error}}
244 +
232 232  {{warning}}
233 233  With Auto Switch enabled, ZUMNET-JBOXs may overwrite the ShowRunnerCLC™ scenes upon reconnecting to the processor: disable auto switch or set scenes both in the App and in ShowRunnerCLC™ to avoid this issue
234 234  {{/warning}}