Changes for page Zūm Net Device Setup
Last modified by Alexander Mott on 2025/06/04 21:12
From version 52.1
edited by Alexander Mott
on 2024/10/22 19:55
on 2024/10/22 19:55
Change comment:
There is no comment for this version
To version 53.1
edited by Alexander Mott
on 2025/06/04 21:12
on 2025/06/04 21:12
Change comment:
There is no comment for this version
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -225,6 +225,10 @@ 225 225 226 226 === Zūm Mode Auto Switch === 227 227 228 +{{warning}} 229 +With Auto Switch enabled, ZUMNET-JBOXs may overwrite the ShowRunnerCLC™ scenes upon reconnecting to the processor: disable auto switch or set scenes both in the App and in ShowRunnerCLC™ to avoid this issue 230 +{{/warning}} 231 + 228 228 Zūm Mode Auto Switch is a feature introduced by Crestron in November of 2022 with .puf firmware v1.04.05 (device firmware 1.004.00005). This feature is intended to address concerns that arose from projects using custom programs with ZUMNET-JBOX-* devices in CNET Mode. Previously, if a device in CNET Mode lost connection to the processor, then it would be impossible to maintain any sort of control over the lighting. With Zūm Mode Auto Switch enabled, a ZUMNET-JBOX running in CNET Mode will automatically switch to App Mode and process local logic in the event that it loses connection to the processor. 229 229 230 230 Note that on 0-10V and switched JBOXs, the connected loads will flash once when rebooting. On ZUMNET-DALI-JBOX models, the JBOX will reboot once when switching to App mode and twice when switching back to CNET mode (once to switch to CNET, and a second time to switch to Legacy DALI mode)