Changes for page Zūm Net Device Setup
Last modified by Alexander Mott on 2025/06/04 21:12
From version 51.1
edited by Alexander Mott
on 2024/10/15 14:39
on 2024/10/15 14:39
Change comment:
There is no comment for this version
To version 53.1
edited by Alexander Mott
on 2025/06/04 21:12
on 2025/06/04 21:12
Change comment:
There is no comment for this version
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -130,7 +130,15 @@ 130 130 131 131 (% class="box errormessage" %) 132 132 ((( 133 -Per Crestron's Zūm Wired firmware v4.01.06.02 release notes, devices running firmware v3.09.05 or earlier "are not supported for upgrade via the Zum App / Hub / or Toolbox" and users should contact Crestron True Blue Support for upgrade paths when required. 133 +Per Crestron's Zūm Wired firmware v4.01.06 release notes, devices running firmware v3.09.05 or earlier "are not supported for upgrade via the Zum App / Hub / or Toolbox" and users should contact Crestron True Blue Support for upgrade paths when required. 134 + 135 +Zūm Wired JBOXs operating as the Primary controller in App mode with firmware versions 4.x.x and above are limited in the number of secondary devices that can be supported on the Zūm Link bus: 136 + 137 +* ZUMNET-JBOX-DALI : 7 maximum secondary devices 138 +* ZUMNET-JBOX-~*~** : 14 maximum secondary devices 139 +* ZUMLINK-JBOX-~*~** : 14 maximum secondary devices 140 + 141 +These limitations do not apply to JBOXs operating in CNET mode //or// running firmware versions 3.x.x 134 134 ))) 135 135 136 136 It is best practice to upgrade all Zūm Wired devices to the latest version, or at the very least update all devices to the same firmware version across the job. The recommended process for updating Zūm Wired firmware is: ... ... @@ -217,6 +217,10 @@ 217 217 218 218 === Zūm Mode Auto Switch === 219 219 228 +{{warning}} 229 +With Auto Switch enabled, ZUMNET-JBOXs may overwrite the ShowRunnerCLC™ scenes upon reconnecting to the processor: disable auto switch or set scenes both in the App and in ShowRunnerCLC™ to avoid this issue 230 +{{/warning}} 231 + 220 220 Zūm Mode Auto Switch is a feature introduced by Crestron in November of 2022 with .puf firmware v1.04.05 (device firmware 1.004.00005). This feature is intended to address concerns that arose from projects using custom programs with ZUMNET-JBOX-* devices in CNET Mode. Previously, if a device in CNET Mode lost connection to the processor, then it would be impossible to maintain any sort of control over the lighting. With Zūm Mode Auto Switch enabled, a ZUMNET-JBOX running in CNET Mode will automatically switch to App Mode and process local logic in the event that it loses connection to the processor. 221 221 222 222 Note that on 0-10V and switched JBOXs, the connected loads will flash once when rebooting. On ZUMNET-DALI-JBOX models, the JBOX will reboot once when switching to App mode and twice when switching back to CNET mode (once to switch to CNET, and a second time to switch to Legacy DALI mode)