... ... @@ -1,7 +1,7 @@
1 1  (% class="box warningmessage" %)
2 2  (((
3 -This article is for configuring Zūm Net devices using Crestron Toolbox. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
4 -For details on using the Zūm Discovery feature to automatically build a ShowRunnerCLC™ configuration based on the Zūm App settings, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.Zūm Discovery.WebHome]].
3 +This article is for configuring Zūm Net devices using Crestron Toolbox. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
4 +For details on using the Zūm Discovery feature to automatically build a ShowRunnerCLC™ configuration based on the Zūm App settings, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.Zūm Discovery.WebHome]].
5 5  )))
6 6  
7 7  {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
... ... @@ -77,7 +77,7 @@
77 77  
78 78  If all hostnames have been set, then it becomes very easy to know which DHCP assigned IP address is associated with each room using the Device Summary. Generate a Device Summary with the new hostnames and proceed to IP configuration.
79 79  
80 -Full instructions on configuring Zūm Wired using the Crestron Zūm App, can be found [[here>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
80 +Full instructions on configuring Zūm Wired using the Crestron Zūm App, can be found [[here>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
81 81  
82 82  === Identifying by Serial Number or MAC Address ===
83 83  
... ... @@ -155,24 +155,8 @@
155 155  
156 156  == Zūm/Cresnet Mode ==
157 157  
158 -Zūm Mode (also known as App Mode) is the default setting for ZUMNET-JBOXs shipping on newer firmware, and allows them to be configured from the Crestron Zūm App as long as a ZUMLINK-KP is connected to the JBOX. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled.
158 +Zūm Mode (also known as App Mode) is the default setting for new ZUMNET-JBOXs, and allows them to be configured from the Crestron Zūm App. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled. Generally, Cresnet mode is only required if non-Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads) or if certain ShowRunnerCLC™ features are required (such as changing the dimming response curve).
159 159  
160 -Generally, ZUMNET-JBOXs do not need to be in Cresnet mode to work with ShowRunnerCLC™ except in specific cases:
161 -
162 -* ZUMNET-JBOX-DALI controllers are being used in legacy mode
163 -* Site-specific security requirements do not allow for wireless connectivity to the lighting controls
164 -* Certain ShowRunnerCLC™ features are required (such as changing the dimming response curve)
165 -* On older versions of firmware, Cresnet mode was required if non-Zūm Link devices were connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads)
166 -** This is no longer the case on recent firmware, and ZUMNET-JBOXs with Cresnet hardware connected to them can be left in Zūm/App mode, though the Cresnet hardware will not be able to function without the control processor
167 -
168 -When a ZUMNET-JBOX is in Zūm Mode and configured to communicate with a processor running ShowRunnerCLC™ software, it is operating in a kind of "App Plus" mode, where any actions that are defined in ShowRunnerCLC™ are performed "on top of" the actions defined in the App:
169 -
170 -* A keypad with actions defined in the Zūm App will perform actions defined in ShowRunnerCLC™ in addition to those App-defined actions while the ZUMNET-JBOX is in Zūm Mode
171 -** This is useful when trying to add functionality to a keypad, such as allowing the keypad to control devices not available in the Zūm App (e.g. shades, loads that are controlled by other ZUMNET-JBOXs or Cresnet load controllers, etc.), but can cause confusion in other situations where there are conflicts between the App-defined actions and the ShowRunnerCLC™-defined actions (e.g. if a rocker keypad with the default All On and All Off actions defined in the App is programmed in ShowRunnerCLC™ to act as a single load toggle, it will not work correctly)
172 -** A ZUMLINK-KP that is disabled from ShowRunnerCLC™ (i.e. by using the Keypad Disable function) will not perform any actions
173 -** A ZUMLINK-KP that has null actions defined in the Zūm App will only perform those actions that are defined in ShowRunnerCLC™
174 -* If occupancy sensor load assignments in the App do not match ShowRunnerCLC™, then odd behavior may result
175 -
176 176  The commands to view or change the Zūm/Cresnet mode are:
177 177  
178 178  * View current mode: ##zwmode##