... ... @@ -4,7 +4,7 @@
4 4  
5 5  Much like DIN-CENCN-2s in SHOWRUNNER™ installations, the IP address of the ZUMNET-JBOX also does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. Instead, ZUMNET-JBOXs are identified to the processor via their IP-ID. If devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, then the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet with an IP Table tab that lists all the ZUMNET-JBOX IP-IDs in the program. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
6 6  
7 -=== Identification and IP Configuration ===
7 +=== ZUMNET-JBOX IP Configuration ===
8 8  
9 9  Configuring ZUMNET-JBOXs must be done over Ethernet, and is easiest to do once all ZUMNET-JBOXs have been installed, powered up, and connected to the lighting network. (It is not necessary for all Zūm Link devices to be installed in order to configure ZUMNET-JBOXs.)
10 10