Content
... ... @@ -1,8 +1,8 @@
1 -=== ZUMNET-JBOXs in SHOWRUNNER™ ===
1 +=== Zūm Net Devices in SHOWRUNNER™ ===
2 2  
3 -ZUMNET-JBOXs are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the Zūm Link network in each room to the Zūm Net network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]] and Zūm Net is an Ethernet protocol, this means that ZUMNET-JBOXs can be thought of as single-net DIN-CENCN-2s.
3 +Zūm Net devices are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the local Zūm Link devices in each room to the overall lighting network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]], and Zūm Net is an Ethernet protocol, this means that Zūm Net devices can be thought of as single-net DIN-CENCN-2s. As of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with SHOWRUNNER™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.
4 4  
5 -Much like DIN-CENCN-2s in SHOWRUNNER™ installations, the IP address of the ZUMNET-JBOX also does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. Instead, ZUMNET-JBOXs are identified to the processor via their IP-ID. If devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, then the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet with an IP Table tab that lists all the ZUMNET-JBOX IP-IDs in the program. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
5 +Much like DIN-CENCN-2s in SHOWRUNNER™ installations, ZUMNET-JBOXs identify themselves to the processor via their IP-ID, so the specific IP address of any given ZUMNET-JBOX does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. If hosted devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet which will list all the Zūm Net and Zūm Link devices and their associated IP-IDs. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
6 6  
7 7  === Identification and IP Configuration ===
8 8  
... ... @@ -19,12 +19,38 @@
19 19  Configuring ZUMNET-JBOXs can be broken up into two separate processes:
20 20  
21 21  1. Identifying which DHCP assigned IP address corresponds to each ZUMNET-JBOX
22 -1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP and the correct IP-ID
22 +1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP address and IP-ID
23 23  
24 24  ==== Identifying ZUMNET-JBOXs ====
25 25  
26 -Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID.
26 +Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID.
27 27  
28 +There are three primary ways of identifying ZUMNET-JBOXs:
29 +
30 +1. Identifying by hostname
31 +1. Identifying by serial number or MAC address
32 +1. Identifying through Toolbox
33 +
34 +Each of these methods involves generating a Device Summary using the Device Discovery Tool in Toolbox. The Device Summary is a file which lists all devices that are discoverable on the network along with useful information such as their hostname, IP address, and MAC address.
35 +
36 +To generate a Device Summary in Toolbox:
37 +
38 +* Connect to the lighting network and open Device Discovery Tool in Toolbox
39 +* The Device Discovery tool will automatically report how many Ethernet devices have been discovered
40 +* Verify that the expected number of Ethernet devices have been discovered, including any TSWs, GLPACs, DIN-CENCN-2s, etc.
41 +** Note that only Crestron devices will appear in Device Discovery; non-Crestron devices (such as Pharos or Enttec DMX controllers) will not appear in Device Discovery Tool
42 +** If no devices are discovered, verify that your computer is connected to the network and your IP address is compatible with the network
43 +** If some devices are missing, there may be an issue with your DHCP server settings or the network wiring
44 +* Click the "Export..." button below the list of discovered devices
45 +** If this button says "Address Book", then Toolbox needs to be updated
46 +* Click the Write Device Summary button and save the Device Summary to your computer
47 +** Though saved as a text file, the Device Summary is actually a table of comma separated values
48 +** Renaming DeviceSummary.txt to DeviceSummary.csv will allow it to be opened and manipulated in common spreadsheet software such as Microsoft Excel or LibreOffice Calc
49 +
50 +===== Identifying by Hostname =====
51 +
52 +Oftentimes,
53 +
28 28  If the electrical contractor has provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is relatively easy to identify which ZUMNET-JBOX should get which IP-ID:
29 29  
30 30  * Connect to the lighting network and open Device Discovery Tool in Toolbox
... ... @@ -33,12 +33,12 @@
33 33  ** Note that only Crestron devices will appear in Device Discovery; non-Crestron devices (such as Pharos or Enttec DMX controllers) will not appear in Device Discovery Tool
34 34  * Click the "Export..." button below the list of discovered devices
35 35  ** If this button says "Address Book", then Toolbox needs to be updated
36 -* Click the Write Device Summary and save the DeviceSummary.txt to your computer
62 +* Click the Write Device Summary button and save the DeviceSummary.txt to your computer
37 37  * The DeviceSummary.txt provides the IP address, MAC address, and serial number for each device on the network
38 38  * Cross reference the DeviceSummary.txt with the serial numbers/MAC addresses provided by the installer in order to determine which ZUMNET-JBOX has been assigned each IP address
39 39  * Update the SRTakeoff.xlsx with the device serial number, MAC address, and automatically assigned IP address for all ZUMNET-JBOXs
40 40  
41 -If the electrical contractor has not provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is necessary to connect to each ZUMNET-JBOX individually and identify them individually:
67 +If the electrical contractor has not provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is necessary to connect to each ZUMNET-JBOX individually and identify them through Toolbox. Putting a device into identify will stop any programs running on a processor, and taking a device out of identify mode will restart the program. This starting/stopping of the program can be time consuming when a large number of devices are being identified, so it may be a good idea to run the ##stopprog -p:01## command on the processor prior to identifying devices. Once all the devices are identified, run the ##progreset## command to resume the program.
42 42  
43 43  * Connect to the lighting network and open Device Discovery Tool in Toolbox
44 44  * Note the IP addresses for all of the installed ZUMNET-JBOXs
... ... @@ -57,9 +57,9 @@
57 57  Once you have identified which IP address has been assigned to each ZUMNET-JBOX, you can begin configuring them with permanent static IP addresses and the correct IP-ID:
58 58  
59 59  * Open Text Console in Toolbox and connect to the first ZUMNET-JBOX
60 -* Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.20**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%))
61 -** Disable DHCP: ##dhcp 0 off##
62 -** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.20**(%%)##
86 +* Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.80**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%))
87 +** Disable DHCP: ##dhcp off##
88 +** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.80**(%%)##
63 63  ** Set IP subnet mask: ##ipm 0 (% style="color:darkgoldenrod" %)**255.255.255.0**(%%)##
64 64  ** Set default gateway: ##defr 0 **10.0.0.1**##
65 65  ** Update IP table: ##addm (% style="color:olive" %)**30**(%%) (% style="color:orange" %)**10.0.0.10**(%%)##
... ... @@ -67,12 +67,41 @@
67 67  ** Reboot the ZUMNET-JBOX: ##reboot##
68 68  * Repeat for all ZUMNET-JBOXs on the job
69 69  
70 -=== ZUMNET-JBOX Specific Configuration ===
96 +=== Zūm Net Specific Configuration ===
71 71  
72 -App vs Cresnet mode
98 +Zūm Net devices have a two additional settings not present for other devices: Zūm/Cresnet mode and Master/Slave mode.
73 73  
74 -Master vs Slave
100 +==== Zūm/Cresnet Mode ====
75 75  
102 +ZUMNET-JBOXs should ship in "Zūm Mode" by default, also known as "App Mode" because this is the setting required to be able to configure Zūm Wired rooms using the Crestron Zūm Mobile App.
103 +
104 +If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the App and all internal logic will be disabled. Generally, Cresnet mode is only required if non Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads).
105 +
106 +The commands to view or change the Zūm/Cresnet mode are:
107 +
108 +* View current mode: ##zwmode##
109 +* Make Zūm/App mode: ##zwmode zum##
110 +* Make Cresnet mode: ##zwmode cnet##
111 +
112 +A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it.
113 +
114 +==== Master/Slave Mode ====
115 +
116 +ZUMNET-JBOXs should ship in "Master" mode by default, and generally this is how they should be configured.
117 +
118 +"Slave" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX. There are two scenarios in which a ZUMNET-JBOX will need to be configured in "Slave" mode:
119 +
120 +1. It is connected to another ZUMNET-JBOX via the Zūm Link bus
121 +1. It is being used as a Cresnet device, connected to a processor or DIN-CENCN-2 using a Cresnet/Zūm Link adapter
122 +
123 +The commands to view or change the Master/Slave mode are:
124 +
125 +* View current mode: ##zwms##
126 +* Make "master": ##zwms master##
127 +* Make "slave": ##zwms slave##
128 +
129 +A reboot is required if the mode is to be changed.
130 +
76 76  === Changing IP-IDs ===
77 77  
78 78  If ZUMNET-JBOXs must be assigned different IP-IDs than indicated in the SRTakeoff.xlsx, or if Zūm Link devices are moved between ZUMNET-JBOXs, then the configuration file must be updated. Every Zūm Link device in the configuration has a ##"DeviceHostId"## associated with it, which corresponds to the IP-ID of the ZUMNET-JBOX hosting it.
1655410981707-782.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,0 +1,1 @@
1 +5.6 KB
Content
1655410997733-287.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,0 +1,1 @@
1 +2.6 KB
Content
1655411066727-374.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,0 +1,1 @@
1 +3.2 KB
Content