Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
1 +XWiki.robert\.hoppe@chiefintegrations\.com
Content
... ... @@ -8,7 +8,7 @@
8 8  {{toc/}}
9 9  {{/box}}
10 10  
11 -Zūm Net devices are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the local Zūm Link devices in each room to the overall lighting network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]], and Zūm Net is an Ethernet protocol, this means that Zūm Net devices can be thought of as single-net DIN-CENCN-2s. As of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with ShowRunnerCLC™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.
11 +Zūm Net devices are part of Crestron's latest Zūm Wired system, acting as the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the local Zūm Link devices in each room to the overall lighting network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]], and Zūm Net is an Ethernet protocol, this means that Zūm Net devices can be thought of as single-net DIN-CENCN-2s. As of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with ShowRunnerCLC™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.
12 12  
13 13  Much like DIN-CENCN-2s in ShowRunnerCLC™ installations, ZUMNET-JBOXs identify themselves to the processor via their IP-ID, so the specific IP address of any given ZUMNET-JBOX does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. If hosted devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet which will list all the Zūm Net and Zūm Link devices and their associated IP-IDs. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
14 14  
... ... @@ -106,8 +106,10 @@
106 106  
107 107  == Assigning Permanent Static IP Addresses and IP-IDs ==
108 108  
109 -Once you have identified which IP address has been assigned to each ZUMNET-JBOX, you can begin configuring them with permanent static IP addresses and the correct IP-ID:
109 +Once you have identified which IP address has been assigned to each ZUMNET-JBOX, you can begin configuring them with permanent static IP addresses and the correct IP-ID.
110 110  
111 +Note that static IP addresses are only required on jobs where there is no permanent DHCP server. Manual IP-ID assignment is not required for jobs intended to be used with Zūm Auto Discovery, though it may still be recommended in order to keep track and document which IP-ID is associated with each area (Auto Discovery will auto-assign IP-IDs to ZUMNET-JBOXs without IP-IDs, but if a ZUMNET-JBOX already has an IP table entry it will be imported to the configuration with that pre-existing IP-ID).
112 +
111 111  * Open Text Console in Toolbox and connect to the first ZUMNET-JBOX
112 112  * Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.80**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%); the hostname can be skipped if it has already been configured from the Crestron Zūm App)
113 113  ** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.80**(%%)##
... ... @@ -176,6 +176,8 @@
176 176  
177 177  Zūm Mode Auto Switch is a feature introduced by Crestron in November of 2022 with .puf firmware v1.04.05 (device firmware 1.004.00005). This feature is intended to address concerns that arose from projects using custom programs with ZUMNET-JBOX-* devices in CNET Mode. Previously, if a device in CNET Mode lost connection to the processor, then it would be impossible to maintain any sort of control over the lighting. With Zūm Mode Auto Switch enabled, a ZUMNET-JBOX running in CNET Mode will automatically switch to App Mode and process local logic in the event that it loses connection to the processor.
178 178  
181 +Note that on 0-10V and switched JBOXs, the connected loads will flash once when rebooting. On ZUMNET-DALI-JBOX models, the JBOX will reboot once when switching to App mode and twice when switching back to CNET mode (once to switch to CNET, and a second time to switch to Legacy DALI mode)
182 +
179 179  Enable Zūm Mode Auto Switch using the command: ##autoswitch on##
180 180  
181 181  Rebooting after changing Auto Switch modes is not officially required, but is still recommended.