... ... @@ -106,8 +106,10 @@
106 106  
107 107  == Assigning Permanent Static IP Addresses and IP-IDs ==
108 108  
109 -Once you have identified which IP address has been assigned to each ZUMNET-JBOX, you can begin configuring them with permanent static IP addresses and the correct IP-ID:
109 +Once you have identified which IP address has been assigned to each ZUMNET-JBOX, you can begin configuring them with permanent static IP addresses and the correct IP-ID.
110 110  
111 +Note that static IP addresses are only required on jobs where there is no permanent DHCP server. Manual IP-ID assignment is not required for jobs intended to be used with Zūm Auto Discovery, though it may still be recommended in order to keep track and document which IP-ID is associated with each area (Auto Discovery will auto-assign IP-IDs to ZUMNET-JBOXs without IP-IDs, but if a ZUMNET-JBOX already has an IP table entry it will be imported to the configuration with that pre-existing IP-ID).
112 +
111 111  * Open Text Console in Toolbox and connect to the first ZUMNET-JBOX
112 112  * Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.80**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%); the hostname can be skipped if it has already been configured from the Crestron Zūm App)
113 113  ** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.80**(%%)##
... ... @@ -122,26 +122,14 @@
122 122  
123 123  = Zūm Net Specific Configuration =
124 124  
125 -Zūm Net devices have a two additional settings not present for other devices: Zūm/Cresnet mode and Master/Slave mode. ZUMNET-JBOXs should ship as Master devices in Zūm Mode from the factory, and this is typically the desired setting.
127 +Zūm Net devices have a two additional settings not present for other devices: Primary/Secondary mode and Zūm/Cresnet mode. ZUMNET-JBOX-DALI have a third setting for Group/Legacy DALI mode, and all ZUMNET-JBOX-* that are in CNET mode can optionally be configured to automatically switch back and forth between CNET and App mode depending on whether the control processor is reachable.
126 126  
127 -== Zūm/Cresnet Mode ==
128 -
129 -Zūm Mode (also known as App Mode) is the default setting for new ZUMNET-JBOXs, and allows them to be configured from the Crestron Zūm App. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled. Generally, Cresnet mode is only required if non-Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads) or if certain ShowRunnerCLC™ features are required (such as changing the dimming response curve).
130 -
131 -The commands to view or change the Zūm/Cresnet mode are:
132 -
133 -* View current mode: ##zwmode##
134 -* Make Zūm/App mode: ##zwmode zum##
135 -* Make Cresnet mode: ##zwmode cnet##
136 -
137 -A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it.
138 -
139 139  == Primary/Secondary Mode ==
140 140  
141 141  (% class="box warningmessage" %)
142 142  (((
143 -Zūm Wired firmware v1.03.27 (device firmware v1.002.00026) updates the terminology from "master"/"slave" to "primary"/"secondary", and adds the ##zwps## command in addition to the previous ##zwms## command.
144 -Devices running this newer firmware will not accept commands using "master"/"slave" as arguments, but will still accept either ##zwms## or ##zwps## as the command.
133 +Zūm Wired firmware v1.03.27 (device firmware v1.002.00026) updates the terminology from "master"/"slave" to "primary"/"secondary", and changes the ##zwms## command to ##zwps##
134 +Devices running this newer firmware will not accept commands using "master"/"slave" as arguments.
145 145  )))
146 146  
147 147  ZUMNET-JBOXs can be in either "Primary" or "Secondary" mode. In most situations, "Primary" is the desired mode of operations, as "Secondary" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX and prevents it from discovering devices on the Zūm Link bus or performing any logic. There are two scenarios in which a ZUMNET-JBOX should be configured in "Secondary" mode:
... ... @@ -154,17 +154,48 @@
154 154  * View current mode:
155 155  ** Current FW: ##zwps## or ##zwmode##
156 156  ** Old FW: ##zwms##
157 -* Make "master":
147 +* Make "Primary":
158 158  ** Current FW: ##zwps primary##
159 159  ** Old FW: ##zwms master##
160 -* Make "slave":
161 -* Current FW: ##zwps secondary##
162 -* Old FW: ##zwms slave##
150 +* Make "Secondary":
151 +** Current FW: ##zwps secondary##
152 +** Old FW: ##zwms slave##
163 163  
164 164  A reboot is required if the mode is changed.
165 165  
166 -= Changing IP-IDs =
156 +== Zūm/Cresnet Mode ==
167 167  
158 +Zūm Mode (also known as App Mode) is the default setting for new ZUMNET-JBOXs, and allows them to be configured from the Crestron Zūm App. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled. Generally, Cresnet mode is only required if non-Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads) or if certain ShowRunnerCLC™ features are required (such as changing the dimming response curve).
159 +
160 +The commands to view or change the Zūm/Cresnet mode are:
161 +
162 +* View current mode: ##zwmode##
163 +* Make Zūm/App mode: ##zwmode zum##
164 +* Make Cresnet mode: ##zwmode cnet##
165 +
166 +A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it.
167 +
168 +=== DALI Group/Legacy Mode ===
169 +
170 +ZUMNET-JBOX-DALI that are operating in App mode should be kept in "Groups" DALI mode, and DALI loads must be configured through the Zūm App. ZUMNET-JBOX-DALI that are operating in CNET mode with ShowRunner™ must be changed to "Legacy" DALI mode, and the DALI ballasts must be addressed and grouped using the Crestron Toolbox DALI Commissioning 2.0 Tool.
171 +
172 +To change modes, run the appropriate dalisetmode command, wait 5 seconds, and then reboot the ZUMNET-JBOX-DALI:
173 +
174 +* Set Legacy mode: ##dalisetmode 1 1##
175 +* Set Groups mode: ##dalisetmode 1 2##
176 +
177 +=== Zūm Mode Auto Switch ===
178 +
179 +Zūm Mode Auto Switch is a feature introduced by Crestron in November of 2022 with .puf firmware v1.04.05 (device firmware 1.004.00005). This feature is intended to address concerns that arose from projects using custom programs with ZUMNET-JBOX-* devices in CNET Mode. Previously, if a device in CNET Mode lost connection to the processor, then it would be impossible to maintain any sort of control over the lighting. With Zūm Mode Auto Switch enabled, a ZUMNET-JBOX running in CNET Mode will automatically switch to App Mode and process local logic in the event that it loses connection to the processor.
180 +
181 +Enable Zūm Mode Auto Switch using the command: ##autoswitch on##
182 +
183 +Rebooting after changing Auto Switch modes is not officially required, but is still recommended.
184 +
185 +//Any configuration changes made through the Zūm App should be made while the control processor is disconnected: the easiest ways to accomplish this are to either disconnect the Cat5e/Cat6 cable at the processor or use Text Console commands (//##stopprog -p:01##//)to temporarily suspend the custom program on the processor.//
186 +
187 +== Changing IP-IDs ==
188 +
168 168  If ZUMNET-JBOXs must be assigned different IP-IDs than indicated in the SRTakeoff.xlsx, or if Zūm Link devices are moved between ZUMNET-JBOXs, then the configuration file must be updated. Every Zūm Link device in the configuration has a ##"DeviceHostId"## associated with it, which corresponds to the IP-ID of the ZUMNET-JBOX hosting it.
169 169  
170 170  If a Zūm Link device is moved from one ZUMNET-JBOX to another, then this ##"DeviceHostId"## must be updated with the IP-ID of the new device.