Changes for page Zūm Net Device Setup

Last modified by Alexander Mott on 2024/10/22 19:55

From version 32.1
edited by Alexander Mott
on 2022/09/22 16:01
Change comment: There is no comment for this version
To version 43.1
edited by Alexander Mott
on 2023/05/16 14:29
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,6 +1,7 @@
1 1  (% class="box warningmessage" %)
2 2  (((
3 3  This article is for configuring Zūm Net devices using Crestron Toolbox. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
4 +For details on using the Zūm Discovery feature to automatically build a ShowRunnerCLC™ configuration based on the Zūm App settings, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.Zūm Discovery.WebHome]].
4 4  )))
5 5  
6 6  {{box cssClass="floatinginfobox" title="**CONTENTS**"}}
... ... @@ -7,11 +7,9 @@
7 7  {{toc/}}
8 8  {{/box}}
9 9  
10 -(% class="row" %)
11 -(((
12 -Zūm Net devices are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the local Zūm Link devices in each room to the overall lighting network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]], and Zūm Net is an Ethernet protocol, this means that Zūm Net devices can be thought of as single-net DIN-CENCN-2s. As of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with SHOWRUNNER™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.
11 +Zūm Net devices are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the local Zūm Link devices in each room to the overall lighting network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]], and Zūm Net is an Ethernet protocol, this means that Zūm Net devices can be thought of as single-net DIN-CENCN-2s. As of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with ShowRunnerCLC™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.
13 13  
14 -Much like DIN-CENCN-2s in SHOWRUNNER™ installations, ZUMNET-JBOXs identify themselves to the processor via their IP-ID, so the specific IP address of any given ZUMNET-JBOX does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. If hosted devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet which will list all the Zūm Net and Zūm Link devices and their associated IP-IDs. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
13 +Much like DIN-CENCN-2s in ShowRunnerCLC™ installations, ZUMNET-JBOXs identify themselves to the processor via their IP-ID, so the specific IP address of any given ZUMNET-JBOX does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. If hosted devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet which will list all the Zūm Net and Zūm Link devices and their associated IP-IDs. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.
15 15  
16 16  = Identification and IP Configuration =
17 17  
... ... @@ -20,7 +20,7 @@
20 20  Since there is no option to configure ZUMNET-JBOXs via USB, a DHCP server is required. There are three options for DHCP servers:
21 21  
22 22  * Using a processor with a Control Subnet (only available on certain processors)
23 -* Using the built-in [[SHOWRUNNER™ DHCP Server>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Advanced Tools.DHCP Server.WebHome]] (available on all processors running SHOWRUNNER™ v3.009 or newer)
22 +* Using the built-in [[ShowRunnerCLC™ DHCP Server>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Advanced Tools.DHCP Server.WebHome]] (available on all processors running ShowRunnerCLC™ v3.009 or newer)
24 24  * Using third party DHCP server software on your computer
25 25  
26 26  Most devices (DIN-CENCN-2, TSW, ZUMNET-JBOXs) rely only on IP-ID to identify themselves to the processor, but some devices (such as GLPACs, DMX controllers, and other processors) have IP addresses that are explicitly defined in the configuration file. The DHCP server should be configured to assign IP addresses that are visible to the processor, but excluded from assigning these explicitly defined IP addresses if possible.
... ... @@ -56,18 +56,13 @@
56 56  ** Though saved as a text file, the Device Summary is actually a table of comma separated values
57 57  ** Renaming DeviceSummary.txt to DeviceSummary.csv will allow it to be opened and manipulated in common spreadsheet software such as Microsoft Excel or LibreOffice Calc
58 58  
59 -Below is an example of a Device Summary for a fully-configured job:
58 +See the [[Export to Device Summary>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Toolbox Basics.WebHome||anchor="HExporttoDeviceSummary"]] section of the Toolbox Basics page for more detail.
60 60  
61 -* DeviceSummary.txt:
62 -[[image:1655487020590-542.png]]
63 -* DeviceSummary.csv:
64 -[[image:1655487132138-904.png]]
65 -
66 66  Once the Device Summary has been generated, proceed to identifying each ZUMNET-JBOX using the hostname, SN/MAC, or Device Tree View methods described below.
67 67  
68 68  === Identifying by Hostname ===
69 69  
70 -The Crestron Zūm App is used to configure the internal logic of Zūm Wired rooms. This internal logic determines the room behavior when ZUMNET-JBOXs are used in standalone applications or if communication to the processor is lost. Even on SHOWRUNNER jobs with a central program running the lighting controls, it is best practice to configure the internal logic to match as closely as possible the SHOWRUNNER™ logic in order to minimize disruption to end-users in the event of a processor or network failure.
64 +The Crestron Zūm App is used to configure the internal logic of Zūm Wired rooms. This internal logic determines the room behavior when ZUMNET-JBOXs are used in standalone applications or if communication to the processor is lost. Even on ShowRunnerCLC jobs with a central program running the lighting controls, it is best practice to configure the internal logic to match as closely as possible the ShowRunnerCLC™ logic in order to minimize disruption to end-users in the event of a processor or network failure.
71 71  
72 72  In addition to configuring default room logic, the Crestron Zūm App can be used to change the hostname of the ZUMNET-JBOX for each room. By default, the hostname for a ZUMNET-JBOX is the model followed by the last six digits of the MAC address, e.g. "ZUMNET-JBOX-16A-LV-F2DA94". If you or the electrical contractor already intend to configure the internal logic each ZUMNET-JBOX, it would be a good idea to also change the hostname to something more identifiable.
73 73  
... ... @@ -116,12 +116,12 @@
116 116  
117 117  * Open Text Console in Toolbox and connect to the first ZUMNET-JBOX
118 118  * Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.80**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%); the hostname can be skipped if it has already been configured from the Crestron Zūm App)
119 -** Disable DHCP: ##dhcp off##
120 120  ** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.80**(%%)##
121 121  ** Set IP subnet mask: ##ipm 0 (% style="color:darkgoldenrod" %)**255.255.255.0**(%%)##
122 122  ** Set default gateway: ##defr 0 **10.0.0.1**##
123 123  ** Update IP table: ##addm (% style="color:olive" %)**30**(%%) (% style="color:orange" %)**10.0.0.10**(%%)##
124 124  ** Set hostname: ##host (% style="color:purple" %)**ZNET-JBOX-RM-201**(%%)##
118 +** Disable DHCP: ##dhcp off##
125 125  ** Reboot the ZUMNET-JBOX: ##reboot##
126 126  *** Note that rebooting the JBOX will cause the lights to briefly cut out
127 127  * Repeat for all ZUMNET-JBOXs on the job
... ... @@ -132,7 +132,7 @@
132 132  
133 133  == Zūm/Cresnet Mode ==
134 134  
135 -Zūm Mode (also known as App Mode) is the default setting for new ZUMNET-JBOXs, and allows them to be configured from the Crestron Zūm App. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled. Generally, Cresnet mode is only required if non-Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads) or if certain SHOWRUNNER™ features are required (such as changing the dimming response curve).
129 +Zūm Mode (also known as App Mode) is the default setting for new ZUMNET-JBOXs, and allows them to be configured from the Crestron Zūm App. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled. Generally, Cresnet mode is only required if non-Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads) or if certain ShowRunnerCLC™ features are required (such as changing the dimming response curve).
136 136  
137 137  The commands to view or change the Zūm/Cresnet mode are:
138 138  
... ... @@ -142,20 +142,32 @@
142 142  
143 143  A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it.
144 144  
145 -== Master/Slave Mode ==
139 +== Primary/Secondary Mode ==
146 146  
147 -ZUMNET-JBOXs ship in "Master" mode by default, and generally this is how they should be configured. "Slave" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX. There are two scenarios in which a ZUMNET-JBOX will need to be configured in "Slave" mode:
141 +(% class="box warningmessage" %)
142 +(((
143 +Zūm Wired firmware v1.03.27 (device firmware v1.002.00026) updates the terminology from "master"/"slave" to "primary"/"secondary", and changes the ##zwms## command to ##zwps##
144 +Devices running this newer firmware will not accept commands using "master"/"slave" as arguments.
145 +)))
148 148  
147 +ZUMNET-JBOXs can be in either "Primary" or "Secondary" mode. In most situations, "Primary" is the desired mode of operations, as "Secondary" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX and prevents it from discovering devices on the Zūm Link bus or performing any logic. There are two scenarios in which a ZUMNET-JBOX should be configured in "Secondary" mode:
148 +
149 149  1. It is connected to another ZUMNET-JBOX via the Zūm Link bus
150 150  1. It is being used as a Cresnet device, connected to a processor or DIN-CENCN-2 using a Cresnet/Zūm Link adapter
151 151  
152 -The commands to view or change the Master/Slave mode are:
152 +ZUMNET-JBOXs with firmware 1.006.00012 or newer will ship from the factory in "Primary" mode, but will go to "Secondary" mode if a hardware reset is performed. ZUMNET-JBOXs with older firmware will ship in "Secondary" mode. The commands to view or change the Primary/Secondary mode are:
153 153  
154 -* View current mode: ##zwms##
155 -* Make "master": ##zwms master##
156 -* Make "slave": ##zwms slave##
154 +* View current mode:
155 +** Current FW: ##zwps## or ##zwmode##
156 +** Old FW: ##zwms##
157 +* Make "Primary":
158 +** Current FW: ##zwps primary##
159 +** Old FW: ##zwms master##
160 +* Make "Secondary":
161 +** Current FW: ##zwps secondary##
162 +** Old FW: ##zwms slave##
157 157  
158 -A reboot is required if the mode is to be changed.
164 +A reboot is required if the mode is changed.
159 159  
160 160  = Changing IP-IDs =
161 161  
... ... @@ -170,8 +170,3 @@
170 170  [[image:1655247008527-737.png]]
171 171  
172 172  [[image:1655246948921-246.png]]
173 -
174 -= Crestron Zūm App =
175 -
176 -If the Zūm rooms are configured using the Crestron Zūm App, then it is possible to build a SHOWRUNNER™ configuration using the Zūm Autodiscovery feature of showrunner.
177 -See [[this>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]] page for details on using the Crestron Zūm App, and [[this>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.Zūm Autodiscovery.WebHome]] page for details on using the Zūm Autodiscovery feature to build a configuration.