Changes for page Zūm Net Device Setup
Last modified by Alexander Mott on 2024/10/22 19:55
From version 18.1
edited by Alexander Mott
on 2022/06/21 18:11
on 2022/06/21 18:11
Change comment:
There is no comment for this version
To version 4.1
edited by Alexander Mott
on 2022/06/14 23:03
on 2022/06/14 23:03
Change comment:
There is no comment for this version
Summary
-
Page properties (3 modified, 0 added, 0 removed)
-
Attachments (0 modified, 0 added, 7 removed)
Details
- Page properties
-
- Title
-
... ... @@ -1,1 +1,1 @@ 1 -Z ūmNetDeviceSetup1 +ZUMNET-JBOX Setup - Parent
-
... ... @@ -1,1 +1,1 @@ 1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide. SHOWRUNNER™ Installation and Network Setup.WebHome1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.WebHome - Content
-
... ... @@ -1,10 +1,10 @@ 1 -=== Z ūmNet Devices in SHOWRUNNER™ ===1 +=== ZUMNET-JBOXs in SHOWRUNNER™ === 2 2 3 -Z ūmNet devices are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting thelocalZūm Linkdevicesin each room to theoveralllightingnetwork throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]],and Zūm Net is an Ethernet protocol, this means thatZūmNet devices can be thought of asAs of Summer 2022, there are only two Zūm Net devices that have been announced and are in production: the ZUMNET-JBOX-16A-LV 0-10V load controller and the ZUMNET-JBOX-DALI DALI load controller. Configuring these devices for use with SHOWRUNNER™ is identical, so they will be referred to collectively as ZUMNET-JBOXs for the purposes of this article.3 +ZUMNET-JBOXs are part of Crestron's latest Zūm Wired system, acting as a the main lighting controller for a Zūm Wired room. In networked applications of Zūm Wired, they also act as bridges connecting the Zūm Link network in each room to the Zūm Net network throughout the building. Since Zūm Link and Cresnet are [[interchangeable>>https://wiki.chiefintegrations.com/SHOWRUNNER%E2%84%A2%20Setup%20Guide/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/#HZ16BmLink]] and Zūm Net is an Ethernet protocol, this means that ZUMNET-JBOXs can be thought of as single-net DIN-CENCN-2s. 4 4 5 -Much like DIN-CENCN-2s in SHOWRUNNER™ installations, ZUMNET-JBOXs identify themselvesto the processor via theirIP-ID,so the specific IPaddress ofany givenZUMNET-JBOX does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. If hosteddevices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, thehichwilllist all theZūmNetandZūm Linkdevices andtheirassociated IP-IDs. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range.5 +Much like DIN-CENCN-2s in SHOWRUNNER™ installations, the IP address of the ZUMNET-JBOX also does not matter as long as it is in the same range as the processor and does not conflict with any other devices on the network. Instead, ZUMNET-JBOXs are identified to the processor via their IP-ID. If devices are moved between ZUMNET-JBOXs, or if the ZUMNET-JBOX needs to have a different IP-ID than it was initially assigned, then the configuration will need to be updated (see below). Chief Integrations typically provides an SRTakeoff.xlsx spreadsheet with an IP Table tab that lists all the ZUMNET-JBOX IP-IDs in the program. If no takeoff is provided, then the processor's IP table can be checked by running the ##ipt -t ##command from the processor after the configuration is loaded. ZUMNET-JBOX's will typically start with IP-IDs in the 30-5F range, but can potentially exceed this range. 6 6 7 -=== IdentificationandIP Configuration ===7 +=== ZUMNET-JBOX IP Configuration === 8 8 9 9 Configuring ZUMNET-JBOXs must be done over Ethernet, and is easiest to do once all ZUMNET-JBOXs have been installed, powered up, and connected to the lighting network. (It is not necessary for all Zūm Link devices to be installed in order to configure ZUMNET-JBOXs.) 10 10 ... ... @@ -19,74 +19,29 @@ 19 19 Configuring ZUMNET-JBOXs can be broken up into two separate processes: 20 20 21 21 1. Identifying which DHCP assigned IP address corresponds to each ZUMNET-JBOX 22 -1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP ad dressandIP-ID22 +1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP and the correct IP-ID 23 23 24 24 ==== Identifying ZUMNET-JBOXs ==== 25 25 26 -Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room 26 +Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID. 27 27 28 - There are threeprimaryways ofidentifyingZUMNET-JBOXs:28 +If the electrical contractor has provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is relatively easy to identify which ZUMNET-JBOX should get which IP-ID: 29 29 30 -1. Identifying by hostname 31 -1. Identifying by serial number or MAC address 32 -1. Identifying through Device Tree View 33 - 34 -Each of these methods involves generating a Device Summary using the Device Discovery Tool in Toolbox. The Device Summary is a file which lists all devices that are discoverable on the network along with useful information such as their hostname, IP address, and MAC address. 35 - 36 -To generate a Device Summary in Toolbox: 37 - 38 38 * Connect to the lighting network and open Device Discovery Tool in Toolbox 39 39 * The Device Discovery tool will automatically report how many Ethernet devices have been discovered 40 -* Verify that the e xpectednumber of Ethernet devices have been discovered, including any TSWs, GLPACs, DIN-CENCN-2s, etc.32 +** Verify that the correct number of Ethernet devices have been discovered, including any TSWs, GLPACs, DIN-CENCN-2s, etc. 41 41 ** Note that only Crestron devices will appear in Device Discovery; non-Crestron devices (such as Pharos or Enttec DMX controllers) will not appear in Device Discovery Tool 42 -** If no devices are discovered, verify that your computer is connected to the network and your IP address is compatible with the network 43 -** If some devices are missing, there may be an issue with your DHCP server settings or the network wiring 44 44 * Click the "Export..." button below the list of discovered devices 45 45 ** If this button says "Address Book", then Toolbox needs to be updated 46 -* Click the Write Device Summary button and save the Device Summary to your computer 47 -** Though saved as a text file, the Device Summary is actually a table of comma separated values 48 -** Renaming DeviceSummary.txt to DeviceSummary.csv will allow it to be opened and manipulated in common spreadsheet software such as Microsoft Excel or LibreOffice Calc 36 +* Click the Write Device Summary and save the DeviceSummary.txt to your computer 37 +* The DeviceSummary.txt provides the IP address, MAC address, and serial number for each device on the network 38 +* Cross reference the DeviceSummary.txt with the serial numbers/MAC addresses provided by the installer in order to determine which ZUMNET-JBOX has been assigned each IP address 39 +* Update the SRTakeoff.xlsx with the device serial number, MAC address, and automatically assigned IP address for all ZUMNET-JBOXs 49 49 50 - Belowisan exampleofa DeviceSummaryforafully-configuredjob:41 +If the electrical contractor has not provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is necessary to connect to each ZUMNET-JBOX individually and identify them individually: 51 51 52 -* DeviceSummary.txt: 53 -[[image:1655487020590-542.png]] 54 -* DeviceSummary.csv: 55 -[[image:1655487132138-904.png]] 56 - 57 -Once the Device Summary has been generated, proceed to identifying each ZUMNET-JBOX using the hostname, SN/MAC, or Device Tree View methods described below. 58 - 59 -===== Identifying by Hostname ===== 60 - 61 -The Crestron Zūm App is used to configure the internal logic of Zūm Wired rooms. This internal logic determines the room behavior when ZUMNET-JBOXs are used in standalone applications or if communication to the processor is lost. Even on SHOWRUNNER™ jobs with a central program running the lighting controls, it is best practice to configure the internal logic to match as closely as possible the SHOWRUNNER™ logic in order to minimize disruption to end-users in the event of a processor or network failure. 62 - 63 -In addition to configuring default room logic, the Crestron Zūm App can be used to change the hostname of the ZUMNET-JBOX for each room. By default, the hostname for a ZUMNET-JBOX is the model followed by the last six digits of the MAC address, e.g. "ZUMNET-JBOX-16A-LV-F2DA94". If you or the electrical contractor already intend to configure the internal logic each ZUMNET-JBOX, it would be a good idea to also change the hostname to something more identifiable. 64 - 65 -To change the hostname using the Crestron Zūm App: 66 - 67 -* Connect to the ZUMNET-JBOX in the App 68 -* Tap "Room Settings" 69 -* Tap "Network" 70 -* Tap the Hostname field and edit the Hostname 71 -* Scroll to the bottom of the page and tap "Save settings" 72 -* Tap "OK" to apply the changes and reboot the ZUMNET-JBOX 73 -** Note that rebooting the JBOX will cause the lights to briefly cut out 74 - 75 -If all hostnames have been set, then it becomes very easy to know which DHCP assigned IP address is associated with each room using the Device Summary. Generate a Device Summary with the new hostnames and proceed to IP configuration. 76 - 77 -===== Identifying by Serial Number or MAC Address ===== 78 - 79 -Both the serial number and MAC address are printed onto each ZUMNET-JBOX. Just like with Cresnet jobs, it is good practice for the electrical contractor to record serial numbers as they install devices. It is also good to collect the MAC addresses, but it is not necessary since Device Summary will have both the serial number and MAC address. 80 - 81 -If the electrical contractor has provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then generate a Device Summary and proceed to IP configuration. 82 - 83 -===== Identifying through Network Device Tree View ===== 84 - 85 -If the electrical contractor has not provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX and nobody intends to rename each ZUMNET-JBOX using the Crestron Zūm App, then the only way to identify which ZUMNET-JBOX is installed where is to use the Device Tree View tool in Toolbox. This is by far the slowest and most disruptive way to identify devices, so it is only recommended as a last resort. 86 - 87 -Putting a ZUMNET-JBOX into identify mode will make it continuously produce an alarm-clock sound and flash any connected loads. Additionally, putting a device into identify mode will stop any programs running on a processor, and taking a device out of identify mode will restart the program. This starting/stopping of the program can be time consuming when a large number of devices are being identified, so it may be a good idea to suspend the program using the ##stopprog -p:01## command on the processor prior to identifying devices. Once all the devices are identified, run the ##progreset## command to resume the program. 88 - 89 -* Generate a Device Summary and note the IP addresses for all installed ZUMNET-JBOXs 43 +* Connect to the lighting network and open Device Discovery Tool in Toolbox 44 +* Note the IP addresses for all of the installed ZUMNET-JBOXs 90 90 * Connect to the first ZUMNET-JBOX using Network Device Tree View 91 91 * Locate the "ZUMNET-JBOX-xx-xx-LOCAL" device in the list of connected devices 92 92 ** The model will vary between 0-10V and DALI JBOXs ... ... @@ -94,76 +94,30 @@ 94 94 * Right click the device and press "Identify This Device..." from the context menu 95 95 * The device will blink any attached fixtures and make an alarm sound 96 96 * Walk around the jobsite until the room/controlled fixtures are located 97 -* Edit theDeviceSummary or SRTakeoff.xlsxsothatyourememberwhichJBOX iswhich98 -* Repeat for each ZUMNET-JBOX until all of the ZUMNET-JBOXs have been identified 52 +* Update the SRTakeoff.xlsx with the device serial number, MAC address, and automatically assigned IP address 53 +* Repeat all steps for each ZUMNET-JBOXs until all of the ZUMNET-JBOXs have been identified 99 99 100 -Once you have determined and recorded which ZUMNET-JBOX is which, you may proceed to IP configuration. 101 - 102 102 ==== Assigning Permanent Static IP Addresses and IP-IDs ==== 103 103 104 104 Once you have identified which IP address has been assigned to each ZUMNET-JBOX, you can begin configuring them with permanent static IP addresses and the correct IP-ID: 105 105 106 106 * Open Text Console in Toolbox and connect to the first ZUMNET-JBOX 107 -* Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0. 80**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%); the hostname can be skipped if it has already been configured from the Crestron Zūm App)108 -** Disable DHCP: ##dhcp off## 109 -** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0. 80**(%%)##60 +* Run the following commands to configure the ZUMNET-JBOXs IP settings (example is for a **10.0.0.0(% style="color:darkgoldenrod" %)/24(%%)** subnet, with a permanent IP address of (% style="color:blue" %)**10.0.0.20**(%%), an IP-ID of (% style="color:olive" %)**30**(%%), a processor IP address of (% style="color:orange" %)**10.0.0.10**(%%), and a hostname of (% style="color:#800080" %)**ZNET-JBOX-RM-201**(%%)) 61 +** Disable DHCP: ##dhcp 0 off## 62 +** Set IP address: ##ipa 0 (% style="color:blue" %)**10.0.0.20**(%%)## 110 110 ** Set IP subnet mask: ##ipm 0 (% style="color:darkgoldenrod" %)**255.255.255.0**(%%)## 111 111 ** Set default gateway: ##defr 0 **10.0.0.1**## 112 112 ** Update IP table: ##addm (% style="color:olive" %)**30**(%%) (% style="color:orange" %)**10.0.0.10**(%%)## 113 113 ** Set hostname: ##host (% style="color:purple" %)**ZNET-JBOX-RM-201**(%%)## 114 114 ** Reboot the ZUMNET-JBOX: ##reboot## 115 -*** Note that rebooting the JBOX will cause the lights to briefly cut out 116 116 * Repeat for all ZUMNET-JBOXs on the job 117 117 118 -=== Z ūmNetSpecific Configuration ===70 +=== ZUMNET-JBOX Specific Configuration === 119 119 120 - Zūm Net devices have a two additional settings notpresentfor other devices:Zūm/Cresnetmodeand Master/Slavemode. ZUMNET-JBOXs should ship as Master devices in Zūm Mode from the factory, and this is typically the desired setting.72 +App vs Cresnet mode 121 121 122 - ==== Zūm/CresnetMode====74 +Master vs Slave 123 123 124 -Zūm Mode (also known as App Mode) is the default setting for new ZUMNET-JBOXs, and allows them to be configured from the Crestron Zūm App. If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the Crestron Zūm App and all internal logic will be disabled. Generally, Cresnet mode is only required if non-Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads) or if certain SHOWRUNNER™ features are required (such as changing the dimming response curve). 125 - 126 -The commands to view or change the Zūm/Cresnet mode are: 127 - 128 -* View current mode: ##zwmode## 129 -* Make Zūm/App mode: ##zwmode zum## 130 -* Make Cresnet mode: ##zwmode cnet## 131 - 132 -A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it. 133 - 134 -==== Master/Slave Mode ==== 135 - 136 -ZUMNET-JBOXs ship in "Master" mode by default, and generally this is how they should be configured. "Slave" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX. There are two scenarios in which a ZUMNET-JBOX will need to be configured in "Slave" mode: 137 - 138 -1. It is connected to another ZUMNET-JBOX via the Zūm Link bus 139 -1. It is being used as a Cresnet device, connected to a processor or DIN-CENCN-2 using a Cresnet/Zūm Link adapter 140 - 141 -The commands to view or change the Master/Slave mode are: 142 - 143 -* View current mode: ##zwms## 144 -* Make "master": ##zwms master## 145 -* Make "slave": ##zwms slave## 146 - 147 -A reboot is required if the mode is to be changed. 148 - 149 -=== Problems Connecting to Zūm Room (Error 13) === 150 - 151 -If you cannot connect to the Zūm Room (i.e., the primary ZUMNET-JBOX for the room) using the Crestron Zūm App: 152 - 153 -* Verify the ZUMNET-JBOX is in "zum" mode 154 -* Verify that the primary ZUMNET-JBOX for the room is in "master" mode 155 -* Confirm you are on an Android device (the iOS app does not currently support Zūm Wired devices) 156 -* If you get an "Error 13" code: 157 -** Uninstall the app 158 -** Reboot your phone 159 -** Reinstall the app 160 -** Navigate to Android Application settings 161 -** Navigate to the Crestron Zūm App 162 -** Clear storage for the Crestron Zūm App 163 -** Open the Crestron Zūm App and accept the license agreements 164 -** Connect to the Zūm Room 165 -** When prompted, input a valid pin (default is 2468) 166 - 167 167 === Changing IP-IDs === 168 168 169 169 If ZUMNET-JBOXs must be assigned different IP-IDs than indicated in the SRTakeoff.xlsx, or if Zūm Link devices are moved between ZUMNET-JBOXs, then the configuration file must be updated. Every Zūm Link device in the configuration has a ##"DeviceHostId"## associated with it, which corresponds to the IP-ID of the ZUMNET-JBOX hosting it.
- 1655410981707-782.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.alexander\.mott@chiefintegrations\.com - Size
-
... ... @@ -1,1 +1,0 @@ 1 -5.6 KB - Content
- 1655410997733-287.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.alexander\.mott@chiefintegrations\.com - Size
-
... ... @@ -1,1 +1,0 @@ 1 -2.6 KB - Content
- 1655411066727-374.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.alexander\.mott@chiefintegrations\.com - Size
-
... ... @@ -1,1 +1,0 @@ 1 -3.2 KB - Content
- 1655487002500-174.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.alexander\.mott@chiefintegrations\.com - Size
-
... ... @@ -1,1 +1,0 @@ 1 -51.5 KB - Content
- 1655487008788-390.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.alexander\.mott@chiefintegrations\.com - Size
-
... ... @@ -1,1 +1,0 @@ 1 -51.5 KB - Content
- 1655487020590-542.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.alexander\.mott@chiefintegrations\.com - Size
-
... ... @@ -1,1 +1,0 @@ 1 -51.5 KB - Content
- 1655487132138-904.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.alexander\.mott@chiefintegrations\.com - Size
-
... ... @@ -1,1 +1,0 @@ 1 -53.0 KB - Content