Changes for page Zūm Net Device Setup

Last modified by Alexander Mott on 2024/10/22 19:55

From version 10.2
edited by Alexander Mott
on 2022/06/17 15:03
Change comment: There is no comment for this version
To version 6.1
edited by Alexander Mott
on 2022/06/16 20:23
Change comment: Uploaded new attachment "1655410981707-782.png", version {1}

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Zūm Net Device Setup
1 +ZUMNET-JBOX Setup
Content
... ... @@ -21,20 +21,10 @@
21 21  1. Identifying which DHCP assigned IP address corresponds to each ZUMNET-JBOX
22 22  1. Connecting to each ZUMNET-JBOX and assigning a permanent static IP address and IP-ID
23 23  
24 -==== Identifying ZUMNET-JBOXs ====
24 +==== Identifying Zūm Net Devices ====
25 25  
26 26  Once all ZUMNET-JBOXs have been assigned temporary IP addresses from the DHCP server, they must each be identified so that the correct IP-ID can be assigned. The goal is to associate each assigned IP address with the room that each ZUMNET-JBOX is meant to control. Then we can connect to each ZUMNET-JBOX and set static IP addresses and update the IP table with the correct IP-ID.
27 27  
28 -There are three primary ways of identifying ZUMNET-JBOXs:
29 -
30 -1. Identifying by hostname
31 -1. Identifying by serial number or MAC address
32 -1. Identifying through Toolbox
33 -
34 -===== Identifying by Hostname =====
35 -
36 -Oftentimes,
37 -
38 38  If the electrical contractor has provided a list of which serial numbers/MAC addresses belong to each installed ZUMNET-JBOX, then it is relatively easy to identify which ZUMNET-JBOX should get which IP-ID:
39 39  
40 40  * Connect to the lighting network and open Device Discovery Tool in Toolbox
... ... @@ -79,39 +79,12 @@
79 79  
80 80  === Zūm Net Specific Configuration ===
81 81  
82 -Zūm Net devices have a two additional settings not present for other devices: Zūm/Cresnet mode and Master/Slave mode.
72 +Zūm Net devices have
83 83  
84 -==== Zūm/Cresnet Mode ====
74 +App vs Cresnet mode
85 85  
86 -ZUMNET-JBOXs should ship in "Zūm Mode" by default, also known as "App Mode" because this is the setting required to be able to configure Zūm Wired rooms using the Crestron Zūm Mobile App.
76 +Master vs Slave
87 87  
88 -If a ZUMNET-JBOX is put into Cresnet mode, it will no longer be able to be configured using the App and all internal logic will be disabled. Generally, Cresnet mode is only required if non Zūm Link devices are connected to the ZUMNET-JBOX (e.g. a GL-EXP-DIMU-CN phase dimmer or C2N-CBD-P Cameo keypads).
89 -
90 -The commands to view or change the Zūm/Cresnet mode are:
91 -
92 -* View current mode: ##zwmode##
93 -* Make Zūm/App mode: ##zwmode zum##
94 -* Make Cresnet mode: ##zwmode cnet##
95 -
96 -A reboot is required if the mode is to be changed. Note that this command will also display the current Master/Slave mode, but will not allow you to change it.
97 -
98 -==== Master/Slave Mode ====
99 -
100 -ZUMNET-JBOXs should ship in "Master" mode by default, and generally this is how they should be configured.
101 -
102 -"Slave" mode effectively turns a ZUMNET-JBOX into a ZUMLINK-JBOX. There are two scenarios in which a ZUMNET-JBOX will need to be configured in "Slave" mode:
103 -
104 -1. It is connected to another ZUMNET-JBOX via the Zūm Link bus
105 -1. It is being used as a Cresnet device, connected to a processor or DIN-CENCN-2 using a Cresnet/Zūm Link adapter
106 -
107 -The commands to view or change the Master/Slave mode are:
108 -
109 -* View current mode: ##zwms##
110 -* Make "master": ##zwms master##
111 -* Make "slave": ##zwms slave##
112 -
113 -A reboot is required if the mode is to be changed.
114 -
115 115  === Changing IP-IDs ===
116 116  
117 117  If ZUMNET-JBOXs must be assigned different IP-IDs than indicated in the SRTakeoff.xlsx, or if Zūm Link devices are moved between ZUMNET-JBOXs, then the configuration file must be updated. Every Zūm Link device in the configuration has a ##"DeviceHostId"## associated with it, which corresponds to the IP-ID of the ZUMNET-JBOX hosting it.
1655410997733-287.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,1 +1,0 @@
1 -2.6 KB
Content
1655411066727-374.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,1 +1,0 @@
1 -3.2 KB
Content