ShowRunner BACnet
Version 6.1 by Mark Kohlmann on 2021/02/10 20:09
ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits. ShowRunner's BACnet feature is licensed. Integrations of 50 points or less may use the free Crestron BACNET license. More than 50 points require the Crestron paid license and total points are limited by the platform. The processor itself consumes a point.
Crestron BACnet Stack Details
Control System | Max # of Objects |
---|---|
| 250 |
| 500 |
| 1000 |
| 2000 |
ShowRunner BACNET Points
AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This the default ShowRunner BACnet mode.
Feature | Type | Point | Label | R/W | Units |
---|---|---|---|---|---|
Area Scene | MV | AreaBaseID | {AreaId}:{AreaName} Scene | RW | Scene |
Occupancy Mode | MV | AreaBaseID + 2 | {AreaId}:{AreaName} Occupancy Mode | RW | Mode |
Occupancy Status | BI | AreaBaseID + 1 | {AreaId}:{AreaName} Occupied | R | Boolean |
Loads | AV | AreaBaseID + 1000 + LoadIndex | {AreaId}:{AreaName} Load{LoadId}:{LoadName} | RW | Percentage |
Photocell Level | AI | AreaBaseID + 100 + PhotocellIndex | {AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName} | R | Percentage |
Zum Floor Hub BACnet Point Emulation
ShowRunner can emulate the Zum Floor Hubs BACnet points.
Set the following Area properties:
BACnetIndex: (ID of the Room, this number of multiplied times 2048 to get the BACnet points, start at 1) BACnetMode: "ZumEmulation"
Feature | Type | Point | Label | Description | R/W | Units |
---|---|---|---|---|---|---|
Area Scene | MV | AreaBaseID + 8 | {AreaName}>{AreaId}>ActiveScene>BI | View or change the current scene. Off scene is 17, Scenes 1 through 16 depend on area configuration. | RW | Scene |
Occupancy Mode | BV | AreaBaseID + 6 | {AreaName}>{AreaId}>OccupancySensorEnabled>BV | Enable or disable the occupancy sensor. Enable will activate the last occupancy/vacancy mode. | RW | Boolean |
Occupancy Status | BI | AreaBaseID + 2 | {AreaName}>{AreaId}>RoomOccupied>BI | Current room occupancy state | R | Boolean |
Online | BI | AreaBaseID | {AreaName}>{AreaId}>RoomOnline>BI | Current room online state, this is fixed as true. | R | Boolean |
On | BI | AreaBaseID + 1 | {AreaName}>{AreaId}>RoomOn>BI | Current room load state. If any load is on this will be true. | R | Boolean |
AreaBaseID = BACnetIndex * 2048