ShowRunner BACnet

Version 3.1 by Mark Kohlmann on 2020/06/04 18:30

ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron license and total points are limited by the platform.

Crestron BACnet Stack Details

Control SystemMax # of Objects
  • FT-TSC600 (Not Supported by SR)
  • TPCS-4SM (Not Supported by SR)
  • TPCS-4SMD (Not Supported by SR)
  • TSCW-730 (Not Supported by SR)
250
  • DIN-AP3
  • DIN-AP3MEX
  • MC3 (Not Supported by SR)
  • RMC3
500
  • CP3
  • CP3N
1000
  • AV3
  • PRO3
2000

Crestron PICS Statement

ShowRunner BACNET Points

AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.

FeatureTypePointLabelR/WUnits
Area SceneMVAreaBaseID{AreaId}:{AreaName} SceneRWScene
Occupancy ModeMVAreaBaseID + 2{AreaId}:{AreaName} Occupancy ModeRWMode
Occupancy StatusBIAreaBaseID + 1{AreaId}:{AreaName} OccupiedRBoolean
LoadsAVAreaBaseID + 1000 + LoadIndex{AreaId}:{AreaName} Load{LoadId}:{LoadName}RWPercentage
Photocell LevelAIAreaBaseID + 100 + PhotocellIndex{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}RPercentage