Changes for page ShowRunnerCLC™ BACnet

Last modified by Alexander Mott on 2024/06/14 18:19

From version 8.1
edited by Mark Kohlmann
on 2021/06/16 17:40
Change comment: There is no comment for this version
To version 6.1
edited by Mark Kohlmann
on 2021/02/10 20:09
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -11,23 +11,17 @@
11 11  )))|250
12 12  |(((
13 13  * DIN-AP3
14 -* DIN-AP4
15 15  * DIN-AP3MEX
16 16  * MC3 (Not Supported by SR)
17 17  * RMC3
18 -* RMC4
19 19  )))|500
20 20  |(((
21 21  * CP3
22 -* CP4
23 23  * CP3N
24 -* CP4N
25 25  )))|1000
26 26  |(((
27 27  * AV3
28 -* AV4
29 29  * PRO3
30 -* PRO4
31 31  )))|2000
32 32  
33 33  [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
... ... @@ -36,16 +36,16 @@
36 36  
37 37  AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This the default ShowRunner BACnet mode.
38 38  
39 -|=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
40 -|Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
41 -|Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
42 -|Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
43 -|Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
44 -|Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
33 +|=Feature|=Type|=Point|=Label|=R/W|=Units
34 +|Area Scene|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
35 +|Occupancy Mode|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
36 +|Occupancy Status|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
37 +|Loads|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
38 +|Photocell Level|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
45 45  
46 46  === Zum Floor Hub BACnet Point Emulation ===
47 47  
48 -ShowRunner can emulate the Zum Floor Hubs BACnet points as an alternative to the standard ShowRunner mode.  Each point may be enabled/disabled individually by Area.
42 +ShowRunner can emulate the Zum Floor Hubs BACnet points.
49 49  
50 50  Set the following Area properties:
51 51