... ... @@ -1,8 +1,15 @@
1 -ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron paid license and total points are limited by the platform.  The processor itself consumes a point.
1 +ShowRunnerCLC™ uses Crestron's BACnet/IP stack and is bound by its licensing and limits. ShowRunnerCLC™'s BACnet feature is licensed, a license from Chief Integrations is required. Integrations of 50 points or less may use the free Crestron BACnet license. More than 50 points require the Crestron paid license and total points are limited by the platform (ZUM-HUB4 processors include a BACnet license, but require a separate license from Crestron to enable ShowRunnerCLC™ installation on the processor). The processor itself consumes a point. BACnet points are assigned during commissioning. A .csv export of the points may be downloaded from the system.
2 2  
3 +BACnet Stack Features:
4 +
5 +* BACnet/IP
6 +* Configurable BACnet UDP port (options may be limited by processor firmware)
7 +* BBMD w/ Foreign Device Registration (Enabled if necessary)
8 +* Points can be discovered using traditional BACnet discovery tools
9 +
3 3  === Crestron BACnet Stack Details ===
4 4  
5 -|=Control System|=Max # of Objects
12 +|=Control System|=Max # of Points
6 6  |(((
7 7  * FT-TSC600 (Not Supported by SR)
8 8  * TPCS-4SM (Not Supported by SR)
... ... @@ -11,41 +11,71 @@
11 11  )))|250
12 12  |(((
13 13  * DIN-AP3
21 +* DIN-AP4
14 14  * DIN-AP3MEX
15 15  * MC3 (Not Supported by SR)
24 +* MC4
16 16  * RMC3
26 +* RMC4
17 17  )))|500
18 18  |(((
19 19  * CP3
30 +* CP4
20 20  * CP3N
32 +* CP4N
21 21  )))|1000
22 22  |(((
23 23  * AV3
36 +* AV4
24 24  * PRO3
38 +* PRO4
25 25  )))|2000
40 +|(((
41 +* ZUM-HUB4
42 +)))|10,000
26 26  
27 27  [[Crestron PICS Statement>>attach:Crestron_PICS.PDF]]
28 28  
29 -=== ShowRunner BACNET Points ===
46 +=== ShowRunnerCLC™ BACnet Points ===
30 30  
31 -AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This the default ShowRunner BACnet mode.
48 +==== Area BACnet Points ====
32 32  
33 -|=Feature|=Type|=Point|=Label|=R/W|=Units
34 -|Area Scene|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
35 -|Occupancy Mode|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
36 -|Occupancy Status|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
37 -|Loads|AV|AreaBaseID + 1000 + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
38 -|Photocell Level|AI|AreaBaseID + 100 + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
50 +Provides control/status for a single area within ShowRunnerCLC™. AreaBaseIDs are assigned automatically and maintained. Points are discoverable. Each of the points may be enabled or disabled by area to optimize the integration. This is the default ShowRunnerCLC™ BACnet mode.
39 39  
40 -=== Zum Floor Hub BACnet Point Emulation ===
52 +{{{Offset is 1000 in configs generated in ShowRunner 3.30 or newer (V2 definition). Offset is 10000 in older configs or using V1 definition.
53 +AreaBaseID = BACnetIndex * Offset}}}
41 41  
42 -ShowRunner can emulate the Zum Floor Hubs BACnet points.
55 +|=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
56 +|Area Scene|Current Scene Active on the Area|MV|AreaBaseID|{AreaId}:{AreaName} Scene|RW|Scene
57 +|Occupancy Mode|Current Occupancy Mode for the Area|MV|AreaBaseID + 2|{AreaId}:{AreaName} Occupancy Mode|RW|Mode
58 +|Occupancy Status|Current Occupancy Status for the Area|BI|AreaBaseID + 1|{AreaId}:{AreaName} Occupied|R|Boolean
59 +|Area Intensity|Current Area Average Intensity/Load Level (v3.010 or later)|AV|AreaBaseID + 3|{AreaId}:{AreaName} Intensity|RW|Percentage
60 +|Area Power|Current Area Power Consumption in Watts (Requires EM License & v3.010 or later)|AI|AreaBaseID + 4|{AreaId}:{AreaName} Power|R|Watts
61 +|Loads|Individual Load intensities for each Load in the Area|AV|AreaBaseID + (V2: 100, V1: 1000) + LoadIndex|{AreaId}:{AreaName} Load{LoadId}:{LoadName}|RW|Percentage
62 +|Photocell Level|Photocell sensor reading for each Photocell in the Area|AI|AreaBaseID + (V2: 50, V1: 100) + PhotocellIndex|{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}|R|Percentage
43 43  
64 +==== Global BACnet Points ====
65 +
66 +|=Feature|=Description|=Type|=Point|=Label|=R/W|=Units
67 +|Master Override|Activates or Deactivates Master Override System Wide|BV|10|Master Override|RW|Boolean
68 +|Demand Response|Activates or Deactivates Demand Response|BV|11|Demand Response|RW|Boolean
69 +|Normal / After Hours|Changes System State between Normal and After Hours|MV|12|Normal / After Hours|RW|(((
70 +1: Normal
71 +2: After Hours
72 +)))
73 +|Device Offline Count|Indicates the number of devices that are offline|AV|20|Device Offline Count|R|Integer
74 +|Alarm|Indicates a critical failure, see user interface for more information|BV|21|Alarm|R|Boolean
75 +
76 +=== Zūm Floor Hub BACnet Point Emulation ===
77 +
78 +ShowRunnerCLC™ can emulate the Zūm Floor Hubs BACnet points as an alternative to the standard ShowRunnerCLC™ mode. Each point may be enabled/disabled individually by Area.  ShowRunner does not expose every point per area that the Zum Hub does, just the points listed below are exposed.
79 +
44 44  Set the following Area properties:
45 45  
46 -{{{BACnetIndex: (ID of the Room, this number of multiplied times 2048 to get the BACnet points, start at 1)
47 -BACnetMode: "ZumEmulation"}}}
82 +{{{BACnetIndex: (ID of the Room, this number of multiplied by 2048 to get the BACnet points, starts at 1)
83 +BACnetMode: "ZumEmulation"
48 48  
85 +AreaBaseID = BACnetIndex * 2048}}}
49 49  
50 50  |=Feature|=(% style="width: 149px;" %)Type|=(% style="width: 341px;" %)Point|=Label|=Description|=R/W|=Units
51 51  |Area Scene|(% style="width:149px" %)MV|(% style="width:341px" %)AreaBaseID + 8|{AreaName}>{AreaId}>ActiveScene>BI|View or change the current scene.  Off scene is 17, Scenes 1 through 16 depend on area configuration.|RW|Scene
... ... @@ -54,4 +54,5 @@
54 54  |Online|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID|{AreaName}>{AreaId}>RoomOnline>BI|Current room online state, this is fixed as true.|R|Boolean
55 55  |On|(% style="width:149px" %)BI|(% style="width:341px" %)AreaBaseID + 1|{AreaName}>{AreaId}>RoomOn>BI|Current room load state.  If any load is on this will be true.|R|Boolean
56 56  
57 -{{{AreaBaseID = BACnetIndex * 2048}}}
94 +{{{
95 + }}}