... ... @@ -146,8 +146,8 @@
146 146  * Lower operations can turn the load off.  The load will not come on with a raise.  This is a firmware behavior in the Zum hardware.
147 147  * Wireless control presents some additional latency possibilities.  Commands required to provide full functionality (load control/raise/lower) with Zum wireless are more intensive than traditional Crestron hardware and may impact performance under heavy load.  Local operation of the Zum wireless room is not impacted.
148 148  * Real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner.
149 -* Keypad behaviors cannot be modified.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose.
150 -* Zum Partition Sensors do not report back to the system and cannot be used to handle room divide/combine logic.
149 +* Keypad behaviors cannot be modified in ShowRunnerSome modifications are permitted within the Zum app.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose.
150 +* Zum Partition Sensors do not report back to the system and cannot be used to handle room divide/combine logic externally to the linked Zum rooms.
151 151  * Off Scene cannot be saved and is always room Off
152 152  * Scenes 1 through 16 are supported and may be modified and saved.
153 153  * Scenes with fade times greater than 1 second will result in loads being commanded individual from ShowRunner and may not be in sync depending on load quantity, RF gateway load, and RF signal integrity.  Zum hardware does not support a fade time as part of the Scene setting.  Fade times must be commanded from ShowRunner.  Scene fade times will be ignored when scenes are activated by Zum keypads or internal occupancy logic.
... ... @@ -158,10 +158,10 @@
158 158  * Blink before timeout is not supported
159 159  * CCT control is presently not supported (ZUMMESH-JBOX-DALI support may be available in the future)
160 160  * RGB loads are not supported
161 -* Minimum/Maximum Levels are not supported when loads are being recalled locally.  ShowRunner will honor them when control occurs from ShowRunner except for raise/lower which is peformed on hardware.
161 +* Minimum/Maximum Levels are not supported when loads are being recalled locally.  ShowRunner will honor them when control occurs from ShowRunner except for raise/lower which is performed on hardware.
162 162  * Dimming curves are not supported when loads are being recalled locally.  Use Zum app to adjust dimming curves if necessary.  Recommended to leave ShowRunner dimming curve set to "Unaffected".
163 163  * BACNET support requires a processor hardware license and ShowRunner BACNET license.  BACNET point availability can be configured per Area.
164 -* Chief Integrations recommends one 3-series processor per building floor at a minimum.
164 +* Chief Integrations recommends one 4-series (preferred) or 3-series processor per building floor at a minimum.
165 165  * Zummesh and infiNET EX devices are not officially supported on the same gateway, discuss with Crestron if needing both.
166 166  
167 167  (% id="HTopologies" %)