Crestron Zūm Wireless

Version 7.1 by Mark Kohlmann on 2020/04/15 16:09

Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.  SHOWRUNNER™

Integration Options

  • SHOWRUNNER™ Total Control - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB.
  • SHOWRUNNER™ + AVBRIDGE + Serial Port - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
  • SHOWRUNNER™ + ZUM-FLOOR-HUB - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.

Feature Matrix

FeatureSHOWRUNNER™ Total ControlSHOWRUNNER™ + AVBRIDGE + Serial PortSHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)ZUM-FLOOR-HUB OnlyZūm iOS/Android Setup App*
Hardware Requirements
Requires JBOX with ZUMMESH-NETBRIDGEYNYYY
Requires ZUMMESH-GATEWAYYNYYN/A
Requires Dedicated RS-232 Serial Port per RoomNYNNN/A
Requires 3 or 4-Series Control SystemYYYNN/A
Physical Presence in Room to Change ScenesNNY, via Zūm Setup AppY, via Zūm Setup AppY
User Interfaces
Web Browser

Crestron SmartGraphics XPanel
HTML5 UI Under Development (Q4 2020)

Crestron SmartGraphics XPanel
HTML5 UI Under Development (Q4 2020)
SHOWRUNNER™ - Crestron SmartGraphics XPanel
ZUM-FLOOR-HUB - HTML5 UI
HTML5 UIN
iOS/AndroidY, Crestron App (Paid Upgrade)Y, Crestron App (Paid Upgrade)Y, Crestron App (Paid Upgrade), Limited Features for Zūm RoomsNY*
Touchscreens (Crestron TSW series)YYY, Limited Features for Zūm RoomsNN
Features
Scene RecallYYYYY
Override Fade Time for Scene Recall**YNNNN
Scene SaveYYNNY
Load ControlYYNNY
Demand ResponseYNY, separate triggers for SHOWRUNNER™ and ZUM-FLOOR-HUB requiredYN
Enable/Disable OccupancyYYY, from Floor HubYY
Override Occupancy LogicYYNNN
Plug Load On/OffYYYYBy Hardware
Integration with Non-Zūm Crestron HardwareYYNNN
Custom Zūm Keypad ProgrammingNY, Zūm AV Keypad OnlyNNY, within the limits of the hardware
New Feature Release CycleAggressiveAggressiveSHOWRUNNER™: Aggressive
Floor Hub: 6-12 months
6-12 months6-12 months
Room Organization

Under Development:
Building/Floor/Sub-Group/Area
Categorization to Filter by Category/Tag

See SHOWRUNNER™ Total ControlSHOWRUNNER™: See SHOWRUNNER™ Total Control
Floor Hub: Category/Room
Category/Room

N/A

Room DiscoveryAutomatic Discovery of Gateways and NETBRIDGESPre-Configured at OrderSHOWRUNNER™: Pre-Configured at Order
Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms
Automatic Discovery of Gateways and NETBRIDGESN/A
Firmware UpdatesPUF Tool
Automatic Support on Roadmap

PUF Tool
Automatic Support on Roadmap

SHOWRUNNER™: PUF Tool
Floor Hub: Automatic, Internet Connection Required
Automatic, Internet Connection RequiredN/A
Calendar/Scheduling
Logic TypeEvent Driven
Profile Support (Under Development)
Event Driven
Profile Support (Under Development)
SHOWRUNNER™: Event Driven
Floor Hub: Pattern assigned to Category
Pattern assigned to CategoryN/A
Astronomical ClockYYY, Per CategoryY, Per CategoryN/A
HolidaysPatternPatternSHOWRUNNER™: Pattern
Floor Hub: Hard Coded
Hard CodedN/A
Custom PatternsY, Advanced Scheduler LicenseY, Advanced Scheduler LicenseSHOWRUNNER™: Y, Advanced Scheduler License
Floor Hub: N
NN/A
Integrations
A/V Integration: APIYYSHOWRUNNER™: Y
Floor Hub: Limited
LimitedN/A
A/V Integration: Crestron EISCYYSHOWRUNNER™: Y
Floor Hub: N
NN/A
A/V Integration: RS-232YY

SHOWRUNNER™: Y
Floor Hub: AVBRIDGE per Area

AVBRIDGE per AreaN/A
BACNETY, SHOWRUNNER™ and Crestron Licenses NeededY, SHOWRUNNER™ and Crestron Licenses Needed

SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
Floor Hub: Y

YN/A
BACNET Features

Per Area Status:
Active Scene
Occupied
Occupancy Enabled
Individual Load Level
Photocell Level (per Photocell)
Plug Loads Enabled

System:
Demand Response Enabled
System Wide Override (Panic/Emergency)

* More Features added upon request

See list for SHOWRUNNER™ Total Control

SHOWRUNNER™: See list for SHOWRUNNER™ Total Control
Floor Hub: See list for ZUM-FLOOR-HUB

Per Room Status:
Online
On
Occupied
Daylighting Active
Device Battery is Low
Plug Loads Enabled
Occupancy Sensor Enabled
Current Daylight Level
Active Scene

System:
Demand Response Enabled

N/A
BACNET Settings Scope
(What Points are Exposed)
Per AreaPer Area

SHOWRUNNER™: Per Area
Floor Hub: Global

GlobalN/A
BACNET Points SupportedDepends on Crestron License and HardwareDepends on Crestron License and HardwareSHOWRUNNER™: Depends on Crestron License and Hardware
Floor Hub: 1000
1000N/A
Crestron FusionYY

SHOWRUNNER™: Y
Floor Hub: N

NN/A
Export to Zūm Floor HubY, LicensedY, LicensedSHOWRUNNER™: Y, LicensedN/AN/A
GLPACYYSHOWRUNNER™: Y
Floor Hub: Via SHOWRUNNER™
NN/A
System to System LinkYY

SHOWRUNNER™: Y
Floor Hub: N

NN/A

* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.
** Fade time is automatically applied if scene is set longer than 1 second.  Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).