Changes for page Crestron Zūm Wireless

Last modified by Scott Kohlmann on 2023/04/20 22:28

From version 27.1
edited by Mark Kohlmann
on 2021/04/12 17:44
Change comment: There is no comment for this version
To version 36.1
edited by Mark Kohlmann
on 2022/06/15 22:26
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ User Guide & Wiki.Design Guide.Hardware Design Guide.WebHome
1 +Design Guide.Hardware Design Guide.WebHome
Content
... ... @@ -2,7 +2,7 @@
2 2  
3 3  ==== Integration Options ====
4 4  
5 -* **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless (see [[Caveats>>||anchor="caveats"]]) integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
5 +* **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless (see [[Caveats>>WebHome||anchor="caveats"]]) integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
6 6  * **SHOWRUNNER™ + AVBRIDGE + Serial Port** - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
7 7  * **SHOWRUNNER™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
8 8  
... ... @@ -36,7 +36,11 @@
36 36  |Override|Y~*~*~*~*~*~*|N|Scene Recall only via ShowRunner|N|N/A
37 37  |Plug Load On/Off|Y|Y|Y|Y|By Hardware
38 38  |Integration with Non-Zūm Crestron Hardware|Y|Y|N|N|N
39 -|Custom Zūm Keypad Programming|N|Y, Zūm AV Keypad Only|N|N|Y, within the limits of the hardware
39 +|Custom Zūm Keypad Programming|(((
40 +Y, per individual button (1 through 4)
41 +AV Keypad not required (v3.004 or later)
42 +[[Details>>doc:SHOWRUNNER™ User Guide & Wiki.Troubleshooting.Zummesh Keypad Custom Programming.WebHome]]
43 +)))|Y, Zūm AV Keypad Only|N|N|Y, within the limits of the hardware
40 40  |New Feature Release Cycle|Aggressive|Aggressive|SHOWRUNNER™: Aggressive
41 41  Floor Hub: 6-12 months|6-12 months|6-12 months
42 42  |Room Organization|(((
... ... @@ -127,8 +127,8 @@
127 127  SHOWRUNNER™: Y
128 128  Floor Hub: N
129 129  )))|N|N/A
130 -|Minimum NETBRIDGE Firmware|v1.12.0130 (PUF Zum MESHNET v1.06.09)|v1.010|N/A|See Crestron|See Crestron
131 -|Minimum Gateway Firmware|v1.4469.00011|N/A|N/A|See Crestron|See Crestron
134 +|Minimum NETBRIDGE Firmware|v1.13.0020 (PUF Zum MESHNET v1.07.16)|v1.010|N/A|See Crestron|See Crestron
135 +|Minimum Gateway Firmware|v1.4469.00022|N/A|N/A|See Crestron|See Crestron
132 132  |Minimum SHOWRUNNER™ Version|2.198|2.198|N/A|N/A|N/A
133 133  
134 134  {{{* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.
... ... @@ -135,8 +135,8 @@
135 135  ** Fade time is automatically applied if scene is set longer than 1 second. Must be triggered from SHOWRUNNER™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).
136 136  *** Zūm wireless does not support direct coupling of fade times and the behavior is different internally within the dimmer versus other Crestron products. Raise/Lower level accuracy is not guaranteed. For best performance when settings scenes, set the slider manually which will send exact levels to the dimmer.
137 137  **** Zūm wireless scenes cannot presently be read on command. Scenes should be created and saved from SHOWRUNNER™ directly. Saved scenes are stored directly on the Zūm wireless dimmer and in ShowRunner. ShowRunner will query the NETBRIDGE after scene recall and attempt to build scene information but operations are done one at a time.
138 -***** Zūm wireless real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner.
139 -****** Zūm wireless does not support a true override but ShowRunner will disable keypads and occupancy sensors.
142 +***** Zūm wireless real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner. Sometimes delays in sending load levels occur. Feature is primarily intended for remotely setting scenes.
143 +****** Zūm wireless does not support a true override but ShowRunner will disable keypads and occupancy sensors and recall scene 15. The occupancy sensor enabled state and current scene will be remembered and recalled when leaving occupancy mode.
140 140  }}}
141 141  
142 142  {{id name="caveats"/}}
... ... @@ -149,7 +149,7 @@
149 149  * Lower operations can turn the load off.  The load will not come on with a raise.  This is a firmware behavior in the Zum hardware.
150 150  * Wireless control presents some additional latency possibilities.  Commands required to provide full functionality (load control/raise/lower) with Zum wireless are more intensive than traditional Crestron hardware and may impact performance under heavy load.  Local operation of the Zum wireless room is not impacted.
151 151  * Real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunner.
152 -* Keypad behaviors cannot be modified in ShowRunner.  Some modifications are permitted within the Zum app.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose.
156 +* Keypad behaviors cannot be modified in ShowRunner.  Some modifications are permitted within the Zum app.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose; or via export buttons ([[Details>>doc:SHOWRUNNER™ User Guide & Wiki.Troubleshooting.Zummesh Keypad Custom Programming.WebHome]]).
153 153  * Zum Partition Sensors do not report back to the system and cannot be used to handle room divide/combine logic externally to the linked Zum rooms.
154 154  * Off Scene cannot be saved and is always room Off
155 155  * Scenes 1 through 16 are supported and may be modified and saved.