19.1 | 1 | Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management. ShowRunnerCLC™ provides a number of integrations options that allow the designer to optimize the solution design. |
![]() |
1.1 | 2 | |
3 | ~*~*~* Specifications are preliminary, the Zūm wired ZUM-FLOOR-HUB has not been released ~*~** | ||
4 | |||
5 | ==== Integration Options ==== | ||
6 | |||
![]() |
19.1 | 7 | * **ShowRunnerCLC™ Total Control** - The most comprehensive option. Allows seamless integration of Zūm and non-Zūm Crestron lighting control products. Extensive feature set allows centralized control and management of Zūm rooms. Advanced scheduler provides more flexibility to the facility operator. This solution replaces the ZUM-FLOOR-HUB in the system design. |
8 | * **ShowRunnerCLC™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub. ShowRunnerCLC™ can export its own areas to the Floor Hub. | ||
![]() |
1.1 | 9 | |
10 | ==== Feature Matrix ==== | ||
11 | |||
![]() |
19.1 | 12 | |=Feature|=ShowRunnerCLC™ Total Control|=ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB4 (Mirror Driver)|=ZUM-FLOOR-HUB4 Only|=Zūm iOS/Android Setup App* |
![]() |
1.1 | 13 | |(% colspan="5" %)**Hardware Requirements** |
14 | |Requires ZUMNET JBox|Y|Y|Y|N | ||
15 | |Requires 3 or 4-Series Control System|Y|Y|N|N/A | ||
16 | |Requires Physical Presence in Room to Change Scenes|N|TBD|TBD|Y | ||
![]() |
10.1 | 17 | |Maximum Rooms|TBD|1000|1000|N/A |
![]() |
1.1 | 18 | |(% colspan="5" %)**User Interfaces** |
19 | |Web Browser|((( | ||
20 | Crestron SmartGraphics XPanel | ||
21 | HTML5 UI | ||
![]() |
19.1 | 22 | )))|ShowRunnerCLC™ - Crestron SmartGraphics XPanel/HTML5 UI |
![]() |
1.1 | 23 | ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N |
![]() |
14.1 | 24 | |iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y* |
![]() |
1.1 | 25 | |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N |
26 | |(% colspan="5" %)**Features** | ||
27 | |Scene Recall|Y|Y|Y|Y | ||
28 | |Override Fade Time for Scene Recall|Y|TBD|TBD|TBD | ||
29 | |Scene Save|Y|TBD|TBD|Y | ||
30 | |Load Control|Y|TBD|TBD|Y | ||
![]() |
19.1 | 31 | |Demand Response|Y|Y, separate triggers for ShowRunnerCLC™ and ZUM-FLOOR-HUB required|Y|N |
![]() |
1.1 | 32 | |Enable/Disable Occupancy|Y|Y, from Floor Hub|Y|Y |
33 | |Override Occupancy Logic|Y|TBD|TBD|N | ||
34 | |Override|Y|Scene Recall only via ShowRunner|TBD|N/A | ||
35 | |Plug Load On/Off|Y|Y|Y|By Hardware | ||
36 | |Integration with Non-Zūm Crestron Hardware|Y|N|N|N | ||
37 | |Custom Zūm Keypad Programming|Y|TBD|TBD|Y, within the limits of the hardware | ||
![]() |
19.1 | 38 | |New Feature Release Cycle|Aggressive|ShowRunnerCLC™: Aggressive |
![]() |
1.1 | 39 | Floor Hub: 6-12 months|6-12 months|6-12 months |
40 | |Room Organization|((( | ||
41 | Organize According to Defined Nodes, multiple levels | ||
42 | Categorization to Filter by Tag | ||
![]() |
19.1 | 43 | )))|ShowRunnerCLC™: See ShowRunnerCLC™ Total Control |
![]() |
1.1 | 44 | Floor Hub: Category/Room|Category/Room|((( |
45 | N/A | ||
46 | ))) | ||
![]() |
19.1 | 47 | |Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|ShowRunnerCLC™: Automatic discovery (Pending) |
48 | Floor Hub: Map Mirrored Rooms to ShowRunnerCLC™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A | ||
![]() |
1.1 | 49 | |Network Topology|((( |
50 | * Flat | ||
51 | * Single Handoff to LAN w/ Control Subnet | ||
![]() |
9.1 | 52 | (Requires CP4N/AV4/PRO4) |
![]() |
19.1 | 53 | )))|Single Handoff to LAN w/ Control Subnet. ShowRunnerCLC™ can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A |
![]() |
1.1 | 54 | |Network Addressing|((( |
55 | * Manual | ||
![]() |
9.1 | 56 | * Customer (DHCP or Manual) |
57 | * DHCP: Control Subnet (Requires CP4N/AV4/PRO4) | ||
![]() |
1.1 | 58 | )))|Control Subnet|Control Subnet|N/A |
59 | |Firmware Updates|PUF Tool | ||
![]() |
19.1 | 60 | Automatic Support on Roadmap|ShowRunnerCLC™: PUF Tool |
![]() |
1.1 | 61 | Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A |
![]() |
19.1 | 62 | |Floorplans|Y|ShowRunnerCLC™: Y |
![]() |
11.1 | 63 | Floor Hub: N|N|N/A |
![]() |
1.1 | 64 | |(% colspan="5" %)**Calendar/Scheduling** |
65 | |Logic Type|Event Driven | ||
![]() |
19.1 | 66 | Profile Support (Under Development)|ShowRunnerCLC™: Event Driven |
![]() |
1.1 | 67 | Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A |
68 | |Astronomical Clock|Y|Y, Per Category|Y, Per Category|N/A | ||
![]() |
19.1 | 69 | |Holidays|Pattern|ShowRunnerCLC™: Pattern |
![]() |
1.1 | 70 | Floor Hub: Hard Coded|Hard Coded|N/A |
![]() |
19.1 | 71 | |Custom Patterns|Y, Advanced Scheduler License|ShowRunnerCLC™: Y, Advanced Scheduler License |
![]() |
1.1 | 72 | Floor Hub: N|N|N/A |
73 | |(% colspan="5" %)**Integrations** | ||
![]() |
19.1 | 74 | |A/V Integration: API|Y|ShowRunnerCLC™: Y |
![]() |
1.1 | 75 | Floor Hub: Limited|Limited|N/A |
![]() |
19.1 | 76 | |A/V Integration: Crestron EISC|Y|ShowRunnerCLC™: Y |
![]() |
1.1 | 77 | Floor Hub: N|N|N/A |
78 | |A/V Integration: RS-232|Y|((( | ||
![]() |
19.1 | 79 | ShowRunnerCLC™: Y |
![]() |
12.1 | 80 | Floor Hub: TBD |
81 | )))|TBD|N/A | ||
![]() |
1.1 | 82 | |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|((( |
![]() |
19.1 | 83 | ShowRunnerCLC™: ShowRunnerCLC™ and Crestron Licenses Needed |
![]() |
1.1 | 84 | Floor Hub: Y |
85 | )))|Y|N/A | ||
86 | |BACNET Features|((( | ||
87 | Per Area Status: | ||
88 | Active Scene | ||
89 | Occupied | ||
90 | Occupancy Enabled | ||
91 | Individual Load Level | ||
92 | Photocell Level (per Photocell) | ||
93 | Plug Loads Enabled | ||
94 | |||
95 | System: | ||
96 | Demand Response Enabled | ||
97 | System Wide Override (Panic/Emergency) | ||
98 | |||
99 | ~* More Features added upon request | ||
100 | )))|((( | ||
![]() |
19.1 | 101 | ShowRunnerCLC™: See list for ShowRunnerCLC™ Total Control |
![]() |
1.1 | 102 | Floor Hub: See list for ZUM-FLOOR-HUB |
103 | )))|((( | ||
104 | Per Room Status: | ||
105 | Online | ||
106 | On | ||
107 | Occupied | ||
108 | Daylighting Active | ||
109 | Device Battery is Low | ||
110 | Plug Loads Enabled | ||
111 | Occupancy Sensor Enabled | ||
112 | Current Daylight Level | ||
113 | Active Scene | ||
114 | \\System: | ||
115 | Demand Response Enabled | ||
116 | )))|N/A | ||
117 | |BACNET Settings Scope | ||
118 | (What Points are Exposed)|Per Area|((( | ||
![]() |
19.1 | 119 | ShowRunnerCLC™: Per Area |
![]() |
1.1 | 120 | Floor Hub: Global |
121 | )))|Global|N/A | ||
![]() |
19.1 | 122 | |BACNET Points Supported|Depends on Crestron License and Hardware|ShowRunnerCLC™: Depends on Crestron License and Hardware |
![]() |
1.1 | 123 | Floor Hub: 1000|1000|N/A |
124 | |Crestron Fusion|Y|((( | ||
![]() |
19.1 | 125 | ShowRunnerCLC™: Y |
![]() |
1.1 | 126 | Floor Hub: N |
127 | )))|N|N/A | ||
![]() |
19.1 | 128 | |Export to Zūm Floor Hub|Y, Licensed|ShowRunnerCLC™: Y, Licensed|N/A|N/A |
129 | |GLPAC|Y|ShowRunnerCLC™: Y | ||
130 | Floor Hub: Via ShowRunnerCLC™|N|N/A | ||
![]() |
1.1 | 131 | |System to System Link|Y|((( |
![]() |
19.1 | 132 | ShowRunnerCLC™: Y |
![]() |
1.1 | 133 | Floor Hub: N |
134 | )))|N|N/A | ||
![]() |
13.1 | 135 | |Minimum ZUM-NET Firmware|((( |
![]() |
18.1 | 136 | CNET Mode: ZUM-WIRED 1.02.10 puf |
![]() |
13.1 | 137 | ZUM Mode: ZUM-WIRED 1.xx.xxx puf (Pending) |
![]() |
14.1 | 138 | )))|((( |
![]() |
19.1 | 139 | ShowRunnerCLC™: TBD |
![]() |
14.1 | 140 | Floor Hub: TBD |
141 | )))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01 | ||
![]() |
13.1 | 142 | |Minimum SHOWRUNNER™ Version|((( |
![]() |
18.1 | 143 | CNET Mode: 3.016 |
![]() |
13.1 | 144 | ZUM Mode: TBD |
145 | )))|N/A|N/A|N/A | ||
146 | |ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as Floor Hub|MASTER|MASTER or SLAVE | ||
147 | |ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|Same as Floor Hub|ZUM|ZUM | ||
![]() |
1.1 | 148 | |
149 | {{id name="caveats"/}} | ||
150 | |||
151 | ==== Caveats ==== | ||
152 | |||
153 | * Consult Chief Integrations to verify sequence of operations if there are any concerns. | ||
![]() |
13.1 | 154 | * Additional caveats: |
![]() |
18.1 | 155 | ** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron. |
156 | ** --Raw Occupancy reporting does not work. A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner. ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron. | ||
![]() |
14.1 | 157 | ** Cresnet Discovery is not working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before ShowRunner can auto-discover hardware. |
![]() |
1.1 | 158 | |
![]() |
10.1 | 159 | ==== FAQ: ==== |
160 | |||
161 | * I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control? | ||
![]() |
16.1 | 162 | //Use a CP4N in lieu of the ZUM-FLOOR-HUB. A DIN-AP4 is not required. Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails. [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]// |
![]() |
10.1 | 163 | * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration? |
164 | //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.// | ||
165 | |||
![]() |
18.1 | 166 | ==== ==== |
![]() |
10.1 | 167 | |
![]() |
1.1 | 168 | ==== Topologies ==== |
169 | |||
![]() |
19.1 | 170 | **ShowRunnerCLC™ Total Control (Control Subnet or Flat)** |
![]() |
8.1 | 171 | [[image:ZumWired_SR-CS\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology Control Subnet"]][[image:ZumWired_SR-Flat\@2x.png||alt="Flat Topology"]] |
![]() |
1.1 | 172 | |
![]() |
19.1 | 173 | **ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)** |
![]() |