Wiki source code of Crestron Zūm Wired

Last modified by Scott Kohlmann on 2023/04/20 22:22

Show last authors
1 Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management.  ShowRunnerCLC™ provides a number of integrations options that allow the designer to optimize the solution design.
2
3 ~*~*~* Specifications are preliminary, the Zūm wired ZUM-FLOOR-HUB has not been released ~*~**
4
5 ==== Integration Options ====
6
7 * **ShowRunnerCLC™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
8 * **ShowRunnerCLC™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  ShowRunnerCLC™ can export its own areas to the Floor Hub.
9
10 ==== Feature Matrix ====
11
12 |=Feature|=ShowRunnerCLC™ Total Control|=ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB4 (Mirror Driver)|=ZUM-FLOOR-HUB4 Only|=Zūm iOS/Android Setup App*
13 |(% colspan="5" %)**Hardware Requirements**
14 |Requires ZUMNET JBox|Y|Y|Y|N
15 |Requires 3 or 4-Series Control System|Y|Y|N|N/A
16 |Requires Physical Presence in Room to Change Scenes|N|TBD|TBD|Y
17 |Maximum Rooms|TBD|1000|1000|N/A
18 |(% colspan="5" %)**User Interfaces**
19 |Web Browser|(((
20 Crestron SmartGraphics XPanel
21 HTML5 UI
22 )))|ShowRunnerCLC™ - Crestron SmartGraphics XPanel/HTML5 UI
23 ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
24 |iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
25 |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
26 |(% colspan="5" %)**Features**
27 |Scene Recall|Y|Y|Y|Y
28 |Override Fade Time for Scene Recall|Y|TBD|TBD|TBD
29 |Scene Save|Y|TBD|TBD|Y
30 |Load Control|Y|TBD|TBD|Y
31 |Demand Response|Y|Y, separate triggers for ShowRunnerCLC™ and ZUM-FLOOR-HUB required|Y|N
32 |Enable/Disable Occupancy|Y|Y, from Floor Hub|Y|Y
33 |Override Occupancy Logic|Y|TBD|TBD|N
34 |Override|Y|Scene Recall only via ShowRunner|TBD|N/A
35 |Plug Load On/Off|Y|Y|Y|By Hardware
36 |Integration with Non-Zūm Crestron Hardware|Y|N|N|N
37 |Custom Zūm Keypad Programming|Y|TBD|TBD|Y, within the limits of the hardware
38 |New Feature Release Cycle|Aggressive|ShowRunnerCLC™: Aggressive
39 Floor Hub: 6-12 months|6-12 months|6-12 months
40 |Room Organization|(((
41 Organize According to Defined Nodes, multiple levels
42 Categorization to Filter by Tag
43 )))|ShowRunnerCLC™: See ShowRunnerCLC™ Total Control
44 Floor Hub: Category/Room|Category/Room|(((
45 N/A
46 )))
47 |Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|ShowRunnerCLC™: Automatic discovery (Pending)
48 Floor Hub: Map Mirrored Rooms to ShowRunnerCLC™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
49 |Network Topology|(((
50 * Flat
51 * Single Handoff to LAN w/ Control Subnet
52 (Requires  CP4N/AV4/PRO4)
53 )))|Single Handoff to LAN w/ Control Subnet.  ShowRunnerCLC™ can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A
54 |Network Addressing|(((
55 * Manual
56 * Customer (DHCP or Manual)
57 * DHCP: Control Subnet (Requires CP4N/AV4/PRO4)
58 )))|Control Subnet|Control Subnet|N/A
59 |Firmware Updates|PUF Tool
60 Automatic Support on Roadmap|ShowRunnerCLC™: PUF Tool
61 Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
62 |Floorplans|Y|ShowRunnerCLC™: Y
63 Floor Hub: N|N|N/A
64 |(% colspan="5" %)**Calendar/Scheduling**
65 |Logic Type|Event Driven
66 Profile Support (Under Development)|ShowRunnerCLC™: Event Driven
67 Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
68 |Astronomical Clock|Y|Y, Per Category|Y, Per Category|N/A
69 |Holidays|Pattern|ShowRunnerCLC™: Pattern
70 Floor Hub: Hard Coded|Hard Coded|N/A
71 |Custom Patterns|Y, Advanced Scheduler License|ShowRunnerCLC™: Y, Advanced Scheduler License
72 Floor Hub: N|N|N/A
73 |(% colspan="5" %)**Integrations**
74 |A/V Integration: API|Y|ShowRunnerCLC™: Y
75 Floor Hub: Limited|Limited|N/A
76 |A/V Integration: Crestron EISC|Y|ShowRunnerCLC™: Y
77 Floor Hub: N|N|N/A
78 |A/V Integration: RS-232|Y|(((
79 ShowRunnerCLC™: Y
80 Floor Hub: TBD
81 )))|TBD|N/A
82 |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
83 ShowRunnerCLC™: ShowRunnerCLC™ and Crestron Licenses Needed
84 Floor Hub: Y
85 )))|Y|N/A
86 |BACNET Features|(((
87 Per Area Status:
88 Active Scene
89 Occupied
90 Occupancy Enabled
91 Individual Load Level
92 Photocell Level (per Photocell)
93 Plug Loads Enabled
94
95 System:
96 Demand Response Enabled
97 System Wide Override (Panic/Emergency)
98
99 ~* More Features added upon request
100 )))|(((
101 ShowRunnerCLC™: See list for ShowRunnerCLC™ Total Control
102 Floor Hub: See list for ZUM-FLOOR-HUB
103 )))|(((
104 Per Room Status:
105 Online
106 On
107 Occupied
108 Daylighting Active
109 Device Battery is Low
110 Plug Loads Enabled
111 Occupancy Sensor Enabled
112 Current Daylight Level
113 Active Scene
114 \\System:
115 Demand Response Enabled
116 )))|N/A
117 |BACNET Settings Scope
118 (What Points are Exposed)|Per Area|(((
119 ShowRunnerCLC™: Per Area
120 Floor Hub: Global
121 )))|Global|N/A
122 |BACNET Points Supported|Depends on Crestron License and Hardware|ShowRunnerCLC™: Depends on Crestron License and Hardware
123 Floor Hub: 1000|1000|N/A
124 |Crestron Fusion|Y|(((
125 ShowRunnerCLC™: Y
126 Floor Hub: N
127 )))|N|N/A
128 |Export to Zūm Floor Hub|Y, Licensed|ShowRunnerCLC™: Y, Licensed|N/A|N/A
129 |GLPAC|Y|ShowRunnerCLC™: Y
130 Floor Hub: Via ShowRunnerCLC™|N|N/A
131 |System to System Link|Y|(((
132 ShowRunnerCLC™: Y
133 Floor Hub: N
134 )))|N|N/A
135 |Minimum ZUM-NET Firmware|(((
136 CNET Mode: ZUM-WIRED 1.02.10 puf
137 ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
138 )))|(((
139 ShowRunnerCLC™: TBD
140 Floor Hub: TBD
141 )))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01
142 |Minimum SHOWRUNNER™ Version|(((
143 CNET Mode: 3.016
144 ZUM Mode: TBD
145 )))|N/A|N/A|N/A
146 |ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as Floor Hub|MASTER|MASTER or SLAVE
147 |ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|Same as Floor Hub|ZUM|ZUM
148
149 {{id name="caveats"/}}
150
151 ==== Caveats ====
152
153 * Consult Chief Integrations to verify sequence of operations if there are any concerns.
154 * Additional caveats:
155 ** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.--  Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
156 ** --Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.--  Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
157 ** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.  Discovery must be fixed before ShowRunner can auto-discover hardware.
158
159 ==== FAQ: ====
160
161 * I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
162 //Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.  [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
163 * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
164 //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
165
166 ==== ====
167
168 ==== Topologies ====
169
170 **ShowRunnerCLC™ Total Control (Control Subnet or Flat)**
171 [[image:ZumWired_SR-CS\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology Control Subnet"]][[image:ZumWired_SR-Flat\@2x.png||alt="Flat Topology"]]
172
173 **ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
174 [[image:ZumWired_SRtoFH\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]