Wiki source code of Crestron Zūm Wired
Version 21.1 by Mark Kohlmann on 2026/03/10 16:50
Show last authors
| author | version | line-number | content |
|---|---|---|---|
| 1 | Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management. ShowRunnerCLC™ provides a number of integrations options that allow the designer to optimize the solution design. | ||
| 2 | |||
| 3 | ~*~*~* Specifications are preliminary, the Zūm wired ZUM-HUB4 has not been released ~*~** | ||
| 4 | |||
| 5 | ==== Integration Options ==== | ||
| 6 | |||
| 7 | * **ShowRunnerCLC™ Total Control** - The most comprehensive option. Allows seamless integration of Zūm and non-Zūm Crestron lighting control products. Extensive feature set allows centralized control and management of Zūm rooms. Advanced scheduler provides more flexibility to the facility operator. This solution replaces the ZUM-HUB4 in the system design. | ||
| 8 | * **ShowRunnerCLC™ + ZUM-HUB4** - Provides limited scene recall and room status for Zūm rooms paired with the HUB4. ShowRunnerCLC™ can export its own areas to the HUB4. | ||
| 9 | |||
| 10 | ==== Feature Matrix ==== | ||
| 11 | |||
| 12 | |=Feature|=ShowRunnerCLC™ Total Control|=ShowRunnerCLC™ (External Room Export) + ZUM-HUB44 (Mirror Driver)|=ZUM-HUB44 Only|=Zūm iOS/Android Setup App* | ||
| 13 | |(% colspan="5" %)**Hardware Requirements** | ||
| 14 | |Requires ZUMNET JBox|Y|Y|Y|N | ||
| 15 | |Requires 3 or 4-Series Control System|Y|Y|N|N/A | ||
| 16 | |Requires Physical Presence in Room to Change Scenes|N|N|N|Y | ||
| 17 | |Maximum Rooms|1000|1000|1000|N/A | ||
| 18 | |(% colspan="5" %)**User Interfaces** | ||
| 19 | |Web Browser|((( | ||
| 20 | Crestron SmartGraphics XPanel | ||
| 21 | HTML5 UI | ||
| 22 | )))|ShowRunnerCLC™ - Crestron SmartGraphics XPanel/HTML5 UI | ||
| 23 | ZUM-HUB4 - HTML5 UI|HTML5 UI|N | ||
| 24 | |iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y* | ||
| 25 | |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N | ||
| 26 | |(% colspan="5" %)**Features** | ||
| 27 | |Scene Recall|Y|Y|Y|Y | ||
| 28 | |Override Fade Time for Scene Recall|Y|N|N|N | ||
| 29 | |Scene Save|Y|Y, via HUB4|Y|Y | ||
| 30 | |Load Control|Y|Y, via HUB4|Y|Y | ||
| 31 | |Demand Response|Y|Y, separate triggers for ShowRunnerCLC™ and ZUM-HUB4 required|Y|N | ||
| 32 | |Enable/Disable Occupancy|Y|Y, from HUB4|Y|Y | ||
| 33 | |Override Occupancy Logic|Y|Y, via ShowRunner|N|N | ||
| 34 | |Override|Y|Scene Recall only via ShowRunner|TBD|N/A | ||
| 35 | |Plug Load On/Off|Y|Y|Y|By Hardware | ||
| 36 | |Integration with Non-Zūm Crestron Hardware|Y|N|N|N | ||
| 37 | |Custom Zūm Keypad Programming|Y|TBD|TBD|Y, within the limits of the hardware | ||
| 38 | |New Feature Release Cycle|Aggressive|ShowRunnerCLC™: Aggressive | ||
| 39 | HUB4: 6-12 months|6-12 months|6-12 months | ||
| 40 | |Room Organization|((( | ||
| 41 | Organize According to Defined Nodes, multiple levels | ||
| 42 | Categorization to Filter by Tag | ||
| 43 | )))|ShowRunnerCLC™: See ShowRunnerCLC™ Total Control | ||
| 44 | HUB4: Category/Room|Category/Room|((( | ||
| 45 | N/A | ||
| 46 | ))) | ||
| 47 | |Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|ShowRunnerCLC™: Automatic discovery (Pending) | ||
| 48 | HUB4: Map Mirrored Rooms to ShowRunnerCLC™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A | ||
| 49 | |Network Topology|((( | ||
| 50 | * Flat | ||
| 51 | * Single Handoff to LAN w/ Control Subnet | ||
| 52 | (Requires CP4N/AV4/PRO4) | ||
| 53 | )))|Single Handoff to LAN w/ Control Subnet. ShowRunnerCLC™ can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A | ||
| 54 | |Network Addressing|((( | ||
| 55 | * Manual | ||
| 56 | * Customer (DHCP or Manual) | ||
| 57 | * DHCP: Control Subnet (Requires CP4N/AV4/PRO4) | ||
| 58 | )))|Control Subnet|Control Subnet|N/A | ||
| 59 | |Firmware Updates|PUF Tool | ||
| 60 | Automatic Support on Roadmap|ShowRunnerCLC™: PUF Tool | ||
| 61 | HUB4: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A | ||
| 62 | |Floorplans|Y|ShowRunnerCLC™: Y | ||
| 63 | HUB4: N|N|N/A | ||
| 64 | |(% colspan="5" %)**Calendar/Scheduling** | ||
| 65 | |Logic Type|Event Driven | ||
| 66 | Profile Support (Under Development)|ShowRunnerCLC™: Event Driven | ||
| 67 | HUB4: Pattern assigned to Category|Pattern assigned to Category|N/A | ||
| 68 | |Astronomical Clock|Y|Y, Per Category|Y, Per Category|N/A | ||
| 69 | |Holidays|Pattern|ShowRunnerCLC™: Pattern | ||
| 70 | HUB4: Hard Coded|Hard Coded|N/A | ||
| 71 | |Custom Patterns|Y, Advanced Scheduler License|ShowRunnerCLC™: Y, Advanced Scheduler License | ||
| 72 | HUB4: N|N|N/A | ||
| 73 | |(% colspan="5" %)**Integrations** | ||
| 74 | |A/V Integration: API|Y|ShowRunnerCLC™: Y | ||
| 75 | HUB4: Limited|Limited|N/A | ||
| 76 | |A/V Integration: Crestron EISC|Y|ShowRunnerCLC™: Y | ||
| 77 | HUB4: N|N|N/A | ||
| 78 | |A/V Integration: RS-232|Y|((( | ||
| 79 | ShowRunnerCLC™: Y | ||
| 80 | HUB4: TBD | ||
| 81 | )))|TBD|N/A | ||
| 82 | |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|((( | ||
| 83 | ShowRunnerCLC™: ShowRunnerCLC™ and Crestron Licenses Needed | ||
| 84 | HUB4: Y | ||
| 85 | )))|Y|N/A | ||
| 86 | |BACNET Features|((( | ||
| 87 | Per Area Status: | ||
| 88 | Active Scene | ||
| 89 | Occupied | ||
| 90 | Occupancy Enabled | ||
| 91 | Individual Load Level | ||
| 92 | Photocell Level (per Photocell) | ||
| 93 | Plug Loads Enabled | ||
| 94 | |||
| 95 | System: | ||
| 96 | Demand Response Enabled | ||
| 97 | System Wide Override (Panic/Emergency) | ||
| 98 | |||
| 99 | ~* More Features added upon request | ||
| 100 | )))|((( | ||
| 101 | ShowRunnerCLC™: See list for ShowRunnerCLC™ Total Control | ||
| 102 | HUB4: See list for ZUM-HUB4 | ||
| 103 | )))|((( | ||
| 104 | Per Room Status: | ||
| 105 | Online | ||
| 106 | On | ||
| 107 | Occupied | ||
| 108 | Daylighting Active | ||
| 109 | Device Battery is Low | ||
| 110 | Plug Loads Enabled | ||
| 111 | Occupancy Sensor Enabled | ||
| 112 | Current Daylight Level | ||
| 113 | Active Scene | ||
| 114 | \\System: | ||
| 115 | Demand Response Enabled | ||
| 116 | )))|N/A | ||
| 117 | |BACNET Settings Scope | ||
| 118 | (What Points are Exposed)|Per Area|((( | ||
| 119 | ShowRunnerCLC™: Per Area | ||
| 120 | HUB4: Global | ||
| 121 | )))|Global|N/A | ||
| 122 | |BACNET Points Supported|Depends on Crestron License and Hardware | ||
| 123 | See [[BACnet Integration>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.ShowRunner BACNET Points.WebHome]]|ShowRunnerCLC™: Depends on Crestron License and Hardware | ||
| 124 | HUB4: 9000|1000|N/A | ||
| 125 | |Crestron Fusion|Y|((( | ||
| 126 | ShowRunnerCLC™: Y | ||
| 127 | HUB4: N | ||
| 128 | )))|N|N/A | ||
| 129 | |Export to Zūm HUB4|Y, Licensed|ShowRunnerCLC™: Y, Licensed|N/A|N/A | ||
| 130 | |GLPAC|Y|ShowRunnerCLC™: Y | ||
| 131 | HUB4: Via ShowRunnerCLC™|N|N/A | ||
| 132 | |System to System Link|Y|((( | ||
| 133 | ShowRunnerCLC™: Y | ||
| 134 | HUB4: N | ||
| 135 | )))|N|N/A | ||
| 136 | |Minimum ZUM-NET Firmware|((( | ||
| 137 | CNET Mode: ZUM-WIRED 1.02.10 puf | ||
| 138 | ZUM Mode: ZUM-WIRED 1.xx.xxx puf (Pending) | ||
| 139 | )))|((( | ||
| 140 | ShowRunnerCLC™: TBD | ||
| 141 | HUB4: TBD | ||
| 142 | )))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01 | ||
| 143 | |Minimum SHOWRUNNER™ Version|((( | ||
| 144 | CNET Mode: 3.016 | ||
| 145 | ZUM Mode: TBD | ||
| 146 | )))|N/A|N/A|N/A | ||
| 147 | |ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as HUB4|MASTER|MASTER or SLAVE | ||
| 148 | |ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|Same as HUB4|ZUM|ZUM | ||
| 149 | |||
| 150 | {{id name="caveats"/}} | ||
| 151 | |||
| 152 | ==== Caveats ==== | ||
| 153 | |||
| 154 | * Consult Chief Integrations to verify sequence of operations if there are any concerns. | ||
| 155 | * Additional caveats: | ||
| 156 | ** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron. | ||
| 157 | ** --Raw Occupancy reporting does not work. A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner. ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron. | ||
| 158 | ** Cresnet Discovery is not working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before ShowRunner can auto-discover hardware. | ||
| 159 | |||
| 160 | ==== FAQ: ==== | ||
| 161 | |||
| 162 | * I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-HUB4) and use ShowRunner™ Total Control? | ||
| 163 | //Use a CP4N in lieu of the ZUM-HUB4. A DIN-AP4 is not required. Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails. [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]// | ||
| 164 | * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration? | ||
| 165 | //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.// | ||
| 166 | |||
| 167 | ==== ==== | ||
| 168 | |||
| 169 | ==== Topologies ==== | ||
| 170 | |||
| 171 | **ShowRunnerCLC™ Total Control (Control Subnet or Flat)** | ||
| 172 | [[image:ZumWired_SR-CS\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology Control Subnet"]][[image:ZumWired_SR-Flat\@2x.png||alt="Flat Topology"]] | ||
| 173 | |||
| 174 | **ShowRunnerCLC™ (External Room Export) + ZUM-HUB4 (Mirror Driver)** | ||
| 175 | [[image:ZumWired_SRtoFH\@2x.png||alt="Zum HUB4 + SHOWRUNNER™ Topology"]] | ||
| 176 | |||
| 177 | **ZUM-HUB4 Only** | ||
| 178 | [[image:ZumWired_FH\@2x.png||alt="Zum HUB4 Only"]] |