Wiki source code of Crestron Zūm Wired

Version 10.1 by Mark Kohlmann on 2021/05/06 15:18

Show last authors
1 Crestron Zūm Wired is a locally integrated lighting control system with various global control options.  Zūm rooms are self-contained control units with primary logic occurring at the room level.  Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
2
3 ~*~*~* Specifications are preliminary, the Zūm wired ZUM-FLOOR-HUB has not been released ~*~**
4
5 ==== Integration Options ====
6
7 * **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
8 * **SHOWRUNNER™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
9
10 ==== Feature Matrix ====
11
12 |=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
13 |(% colspan="5" %)**Hardware Requirements**
14 |Requires ZUMNET JBox|Y|Y|Y|N
15 |Requires 3 or 4-Series Control System|Y|Y|N|N/A
16 |Requires Physical Presence in Room to Change Scenes|N|TBD|TBD|Y
17 |Maximum Rooms|TBD|1000|1000|N/A
18 |(% colspan="5" %)**User Interfaces**
19 |Web Browser|(((
20 Crestron SmartGraphics XPanel
21 HTML5 UI
22 )))|SHOWRUNNER™ - Crestron SmartGraphics XPanel
23 ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
24 |iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
25 |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
26 |(% colspan="5" %)**Features**
27 |Scene Recall|Y|Y|Y|Y
28 |Override Fade Time for Scene Recall|Y|TBD|TBD|TBD
29 |Scene Save|Y|TBD|TBD|Y
30 |Load Control|Y|TBD|TBD|Y
31 |Demand Response|Y|Y, separate triggers for SHOWRUNNER™ and ZUM-FLOOR-HUB required|Y|N
32 |Enable/Disable Occupancy|Y|Y, from Floor Hub|Y|Y
33 |Override Occupancy Logic|Y|TBD|TBD|N
34 |Override|Y|Scene Recall only via ShowRunner|TBD|N/A
35 |Plug Load On/Off|Y|Y|Y|By Hardware
36 |Integration with Non-Zūm Crestron Hardware|Y|N|N|N
37 |Custom Zūm Keypad Programming|Y|TBD|TBD|Y, within the limits of the hardware
38 |New Feature Release Cycle|Aggressive|SHOWRUNNER™: Aggressive
39 Floor Hub: 6-12 months|6-12 months|6-12 months
40 |Room Organization|(((
41 Organize According to Defined Nodes, multiple levels
42 Categorization to Filter by Tag
43 )))|SHOWRUNNER™: See SHOWRUNNER™ Total Control
44 Floor Hub: Category/Room|Category/Room|(((
45 N/A
46 )))
47 |Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices|SHOWRUNNER™: Automatic discovery
48 Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
49 |Network Topology|(((
50 * Flat
51 * Single Handoff to LAN w/ Control Subnet
52 (Requires  CP4N/AV4/PRO4)
53 )))|Single Handoff to LAN w/ Control Subnet.  ShowRunner can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A
54 |Network Addressing|(((
55 * Manual
56 * Customer (DHCP or Manual)
57 * DHCP: Control Subnet (Requires CP4N/AV4/PRO4)
58 )))|Control Subnet|Control Subnet|N/A
59 |Firmware Updates|PUF Tool
60 Automatic Support on Roadmap|SHOWRUNNER™: PUF Tool
61 Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
62 |(% colspan="5" %)**Calendar/Scheduling**
63 |Logic Type|Event Driven
64 Profile Support (Under Development)|SHOWRUNNER™: Event Driven
65 Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
66 |Astronomical Clock|Y|Y, Per Category|Y, Per Category|N/A
67 |Holidays|Pattern|SHOWRUNNER™: Pattern
68 Floor Hub: Hard Coded|Hard Coded|N/A
69 |Custom Patterns|Y, Advanced Scheduler License|SHOWRUNNER™: Y, Advanced Scheduler License
70 Floor Hub: N|N|N/A
71 |(% colspan="5" %)**Integrations**
72 |A/V Integration: API|Y|SHOWRUNNER™: Y
73 Floor Hub: Limited|Limited|N/A
74 |A/V Integration: Crestron EISC|Y|SHOWRUNNER™: Y
75 Floor Hub: N|N|N/A
76 |A/V Integration: RS-232|Y|(((
77 SHOWRUNNER™: Y
78 Floor Hub: AVBRIDGE per Area
79 )))|AVBRIDGE per Area|N/A
80 |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
81 SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
82 Floor Hub: Y
83 )))|Y|N/A
84 |BACNET Features|(((
85 Per Area Status:
86 Active Scene
87 Occupied
88 Occupancy Enabled
89 Individual Load Level
90 Photocell Level (per Photocell)
91 Plug Loads Enabled
92
93 System:
94 Demand Response Enabled
95 System Wide Override (Panic/Emergency)
96
97 ~* More Features added upon request
98 )))|(((
99 SHOWRUNNER™: See list for SHOWRUNNER™ Total Control
100 Floor Hub: See list for ZUM-FLOOR-HUB
101 )))|(((
102 Per Room Status:
103 Online
104 On
105 Occupied
106 Daylighting Active
107 Device Battery is Low
108 Plug Loads Enabled
109 Occupancy Sensor Enabled
110 Current Daylight Level
111 Active Scene
112 \\System:
113 Demand Response Enabled
114 )))|N/A
115 |BACNET Settings Scope
116 (What Points are Exposed)|Per Area|(((
117 SHOWRUNNER™: Per Area
118 Floor Hub: Global
119 )))|Global|N/A
120 |BACNET Points Supported|Depends on Crestron License and Hardware|SHOWRUNNER™: Depends on Crestron License and Hardware
121 Floor Hub: 1000|1000|N/A
122 |Crestron Fusion|Y|(((
123 SHOWRUNNER™: Y
124 Floor Hub: N
125 )))|N|N/A
126 |Export to Zūm Floor Hub|Y, Licensed|SHOWRUNNER™: Y, Licensed|N/A|N/A
127 |GLPAC|Y|SHOWRUNNER™: Y
128 Floor Hub: Via SHOWRUNNER™|N|N/A
129 |System to System Link|Y|(((
130 SHOWRUNNER™: Y
131 Floor Hub: N
132 )))|N|N/A
133 |Minimum ZUM-NET Firmware|ZUM-WIRED 1.00.08 puf|N/A|See Crestron|See Crestron
134 |Minimum SHOWRUNNER™ Version|2.208|N/A|N/A|N/A
135
136 {{id name="caveats"/}}
137
138 ==== Caveats ====
139
140 * Consult Chief Integrations to verify sequence of operations if there are any concerns.
141 * Additional caveats TBD
142
143 ==== FAQ: ====
144
145 * I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
146 //Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.//
147 * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
148 //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
149
150 (% class="wikigeneratedid" %)
151 ==== ====
152
153 (% class="wikigeneratedid" %)
154 ==== Topologies ====
155
156 **SHOWRUNNER™ Total Control (Control Subnet or Flat)**
157 [[image:ZumWired_SR-CS\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology Control Subnet"]][[image:ZumWired_SR-Flat\@2x.png||alt="Flat Topology"]]
158
159 **SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
160 [[image:ZumWired_SRtoFH\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]
161
162 **ZUM-FLOOR-HUB Only**
163 [[image:ZumWired_FH\@2x.png||alt="Zum Floor Hub Only"]]