... ... @@ -14,6 +14,7 @@
14 14  |Requires ZUMNET JBox|Y|Y|Y|N
15 15  |Requires 3 or 4-Series Control System|Y|Y|N|N/A
16 16  |Requires Physical Presence in Room to Change Scenes|N|TBD|TBD|Y
17 +|Maximum Rooms|TBD|1000|1000|N/A
17 17  |(% colspan="5" %)**User Interfaces**
18 18  |Web Browser|(((
19 19  Crestron SmartGraphics XPanel
... ... @@ -139,6 +139,17 @@
139 139  * Consult Chief Integrations to verify sequence of operations if there are any concerns.
140 140  * Additional caveats TBD
141 141  
143 +==== FAQ: ====
144 +
145 +* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
146 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.//
147 +* Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
148 +//If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
149 +
150 +(% class="wikigeneratedid" %)
151 +==== ====
152 +