Changes for page Crestron Zūm Wired

Last modified by Scott Kohlmann on 2023/04/20 22:22

From version 8.1
edited by Mark Kohlmann
on 2021/05/05 22:42
Change comment: There is no comment for this version
To version 13.1
edited by Mark Kohlmann
on 2021/10/05 22:11
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -9,16 +9,17 @@
9 9  
10 10  ==== Feature Matrix ====
11 11  
12 -|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
12 +|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB4 (Mirror Driver)|=ZUM-FLOOR-HUB4 Only|=Zūm iOS/Android Setup App*
13 13  |(% colspan="5" %)**Hardware Requirements**
14 14  |Requires ZUMNET JBox|Y|Y|Y|N
15 15  |Requires 3 or 4-Series Control System|Y|Y|N|N/A
16 16  |Requires Physical Presence in Room to Change Scenes|N|TBD|TBD|Y
17 +|Maximum Rooms|TBD|1000|1000|N/A
17 17  |(% colspan="5" %)**User Interfaces**
18 18  |Web Browser|(((
19 19  Crestron SmartGraphics XPanel
20 20  HTML5 UI
21 -)))|SHOWRUNNER™ - Crestron SmartGraphics XPanel
22 +)))|SHOWRUNNER™ - Crestron SmartGraphics XPanel/HTML5 UI
22 22  ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
23 23  |iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
24 24  |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
... ... @@ -43,21 +43,23 @@
43 43  Floor Hub: Category/Room|Category/Room|(((
44 44  N/A
45 45  )))
46 -|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices|SHOWRUNNER™: Automatic discovery
47 +|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|SHOWRUNNER™: Automatic discovery (Pending)
47 47  Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
48 48  |Network Topology|(((
49 49  * Flat
50 50  * Single Handoff to LAN w/ Control Subnet
51 -(Requires  CP3N/CP4N/AV3/AV4/PRO3/PRO4)
52 +(Requires  CP4N/AV4/PRO4)
52 52  )))|Single Handoff to LAN w/ Control Subnet.  ShowRunner can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A
53 53  |Network Addressing|(((
54 54  * Manual
55 -* Customer
56 -* Control Subnet (Requires CP3N/CP4N/AV3/AV4/PRO3/PRO4)
56 +* Customer (DHCP or Manual)
57 +* DHCP: Control Subnet (Requires CP4N/AV4/PRO4)
57 57  )))|Control Subnet|Control Subnet|N/A
58 58  |Firmware Updates|PUF Tool
59 59  Automatic Support on Roadmap|SHOWRUNNER™: PUF Tool
60 60  Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
62 +|Floorplans|Y|SHOWRUNNER™: Y
63 +Floor Hub: N|N|N/A
61 61  |(% colspan="5" %)**Calendar/Scheduling**
62 62  |Logic Type|Event Driven
63 63  Profile Support (Under Development)|SHOWRUNNER™: Event Driven
... ... @@ -74,8 +74,8 @@
74 74  Floor Hub: N|N|N/A
75 75  |A/V Integration: RS-232|Y|(((
76 76  SHOWRUNNER™: Y
77 -Floor Hub: AVBRIDGE per Area
78 -)))|AVBRIDGE per Area|N/A
80 +Floor Hub: TBD
81 +)))|TBD|N/A
79 79  |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
80 80  SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
81 81  Floor Hub: Y
... ... @@ -129,8 +129,16 @@
129 129  SHOWRUNNER™: Y
130 130  Floor Hub: N
131 131  )))|N|N/A
132 -|Minimum ZUM-NET Firmware|ZUM-WIRED 1.00.08 puf|N/A|See Crestron|See Crestron
133 -|Minimum SHOWRUNNER™ Version|2.208|N/A|N/A|N/A
135 +|Minimum ZUM-NET Firmware|(((
136 +CNET Mode: ZUM-WIRED 1.00.09 puf
137 +ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
138 +)))|N/A|See Crestron|See Crestron
139 +|Minimum SHOWRUNNER™ Version|(((
140 +CNET Mode: 3.003
141 +ZUM Mode: TBD
142 +)))|N/A|N/A|N/A
143 +|ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as Floor Hub|MASTER|MASTER or SLAVE
144 +|ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|Same as Floor Hub|ZUM|ZUM
134 134  
135 135  {{id name="caveats"/}}
136 136  
... ... @@ -137,8 +137,20 @@
137 137  ==== Caveats ====
138 138  
139 139  * Consult Chief Integrations to verify sequence of operations if there are any concerns.
140 -* Additional caveats TBD
151 +* Additional caveats:
152 +** Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
153 +** Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
154 +** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.
141 141  
156 +==== FAQ: ====
157 +
158 +* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
159 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.//
160 +* Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
161 +//If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
162 +
163 +==== ====
164 +
142 142  ==== Topologies ====
143 143  
144 144  **SHOWRUNNER™ Total Control (Control Subnet or Flat)**