Changes for page Crestron Zūm Wired

Last modified by Mark Kohlmann on 2026/04/07 18:02

From version 22.1
edited by Mark Kohlmann
on 2026/04/07 18:02
Change comment: There is no comment for this version
To version 18.3
edited by Alexander Mott
on 2023/03/24 15:32
Change comment: (Autosaved)

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.mark\.kohlmann@chiefintegrations\.com
1 +XWiki.alexander\.mott@chiefintegrations\.com
Content
... ... @@ -1,56 +1,56 @@
1 -Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management.  ShowRunnerCLC™ provides a number of integrations options that allow the designer to optimize the solution design.
1 +Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
2 2  
3 -**[[Zum Wired App Mode vs CNET Decision Guide>>doc:.Zum Wired App Mode vs CNET Decision Guide.WebHome]]**
3 +~*~*~* Specifications are preliminary, the Zūm wired ZUM-FLOOR-HUB has not been released ~*~**
4 4  
5 5  ==== Integration Options ====
6 6  
7 -* **ShowRunnerCLC™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-HUB4 in the system design.
8 -* **ShowRunnerCLC™ + ZUM-HUB4** - Provides limited scene recall and room status for Zūm rooms paired with the HUB4.  ShowRunnerCLC™ can export its own areas to the HUB4.
7 +* **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
8 +* **SHOWRUNNER™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
9 9  
10 10  ==== Feature Matrix ====
11 11  
12 -|=Feature|=ShowRunnerCLC™ Total Control|=ShowRunnerCLC™ (External Room Export) + ZUM-HUB44 (Mirror Driver)|=ZUM-HUB44 Only|=Zūm iOS/Android Setup App*
12 +|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB4 (Mirror Driver)|=ZUM-FLOOR-HUB4 Only|=Zūm iOS/Android Setup App*
13 13  |(% colspan="5" %)**Hardware Requirements**
14 14  |Requires ZUMNET JBox|Y|Y|Y|N
15 15  |Requires 3 or 4-Series Control System|Y|Y|N|N/A
16 -|Requires Physical Presence in Room to Change Scenes|N|N|N|Y
17 -|Maximum Rooms|1000|1000|1000|N/A
16 +|Requires Physical Presence in Room to Change Scenes|N|TBD|TBD|Y
17 +|Maximum Rooms|TBD|1000|1000|N/A
18 18  |(% colspan="5" %)**User Interfaces**
19 19  |Web Browser|(((
20 20  Crestron SmartGraphics XPanel
21 21  HTML5 UI
22 -)))|ShowRunnerCLC™ - Crestron SmartGraphics XPanel/HTML5 UI
23 -ZUM-HUB4 - HTML5 UI|HTML5 UI|N
22 +)))|SHOWRUNNER™ - Crestron SmartGraphics XPanel/HTML5 UI
23 +ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
24 24  |iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
25 25  |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
26 26  |(% colspan="5" %)**Features**
27 27  |Scene Recall|Y|Y|Y|Y
28 -|Override Fade Time for Scene Recall|Y|N|N|N
29 -|Scene Save|Y|Y, via HUB4|Y|Y
30 -|Load Control|Y|Y, via HUB4|Y|Y
31 -|Demand Response|Y|Y, separate triggers for ShowRunnerCLC™ and ZUM-HUB4 required|Y|N
32 -|Enable/Disable Occupancy|Y|Y, from HUB4|Y|Y
33 -|Override Occupancy Logic|Y|Y, via ShowRunner|N|N
28 +|Override Fade Time for Scene Recall|Y|TBD|TBD|TBD
29 +|Scene Save|Y|TBD|TBD|Y
30 +|Load Control|Y|TBD|TBD|Y
31 +|Demand Response|Y|Y, separate triggers for SHOWRUNNER™ and ZUM-FLOOR-HUB required|Y|N
32 +|Enable/Disable Occupancy|Y|Y, from Floor Hub|Y|Y
33 +|Override Occupancy Logic|Y|TBD|TBD|N
34 34  |Override|Y|Scene Recall only via ShowRunner|TBD|N/A
35 35  |Plug Load On/Off|Y|Y|Y|By Hardware
36 36  |Integration with Non-Zūm Crestron Hardware|Y|N|N|N
37 37  |Custom Zūm Keypad Programming|Y|TBD|TBD|Y, within the limits of the hardware
38 -|New Feature Release Cycle|Aggressive|ShowRunnerCLC™: Aggressive
39 -HUB4: 6-12 months|6-12 months|6-12 months
38 +|New Feature Release Cycle|Aggressive|SHOWRUNNER™: Aggressive
39 +Floor Hub: 6-12 months|6-12 months|6-12 months
40 40  |Room Organization|(((
41 41  Organize According to Defined Nodes, multiple levels
42 42  Categorization to Filter by Tag
43 -)))|ShowRunnerCLC™: See ShowRunnerCLC™ Total Control
44 -HUB4: Category/Room|Category/Room|(((
43 +)))|SHOWRUNNER™: See SHOWRUNNER™ Total Control
44 +Floor Hub: Category/Room|Category/Room|(((
45 45  N/A
46 46  )))
47 -|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|ShowRunnerCLC™: Automatic discovery (Pending)
48 -HUB4: Map Mirrored Rooms to ShowRunnerCLC™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
47 +|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|SHOWRUNNER™: Automatic discovery (Pending)
48 +Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
49 49  |Network Topology|(((
50 50  * Flat
51 51  * Single Handoff to LAN w/ Control Subnet
52 52  (Requires  CP4N/AV4/PRO4)
53 -)))|Single Handoff to LAN w/ Control Subnet.  ShowRunnerCLC™ can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A
53 +)))|Single Handoff to LAN w/ Control Subnet.  ShowRunner can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A
54 54  |Network Addressing|(((
55 55  * Manual
56 56  * Customer (DHCP or Manual)
... ... @@ -57,31 +57,31 @@
57 57  * DHCP: Control Subnet (Requires CP4N/AV4/PRO4)
58 58  )))|Control Subnet|Control Subnet|N/A
59 59  |Firmware Updates|PUF Tool
60 -Automatic Support on Roadmap|ShowRunnerCLC™: PUF Tool
61 -HUB4: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
62 -|Floorplans|Y|ShowRunnerCLC™: Y
63 -HUB4: N|N|N/A
60 +Automatic Support on Roadmap|SHOWRUNNER™: PUF Tool
61 +Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
62 +|Floorplans|Y|SHOWRUNNER™: Y
63 +Floor Hub: N|N|N/A
64 64  |(% colspan="5" %)**Calendar/Scheduling**
65 65  |Logic Type|Event Driven
66 -Profile Support (Under Development)|ShowRunnerCLC™: Event Driven
67 -HUB4: Pattern assigned to Category|Pattern assigned to Category|N/A
66 +Profile Support (Under Development)|SHOWRUNNER™: Event Driven
67 +Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
68 68  |Astronomical Clock|Y|Y, Per Category|Y, Per Category|N/A
69 -|Holidays|Pattern|ShowRunnerCLC™: Pattern
70 -HUB4: Hard Coded|Hard Coded|N/A
71 -|Custom Patterns|Y, Advanced Scheduler License|ShowRunnerCLC™: Y, Advanced Scheduler License
72 -HUB4: N|N|N/A
69 +|Holidays|Pattern|SHOWRUNNER™: Pattern
70 +Floor Hub: Hard Coded|Hard Coded|N/A
71 +|Custom Patterns|Y, Advanced Scheduler License|SHOWRUNNER™: Y, Advanced Scheduler License
72 +Floor Hub: N|N|N/A
73 73  |(% colspan="5" %)**Integrations**
74 -|A/V Integration: API|Y|ShowRunnerCLC™: Y
75 -HUB4: Limited|Limited|N/A
76 -|A/V Integration: Crestron EISC|Y|ShowRunnerCLC™: Y
77 -HUB4: N|N|N/A
74 +|A/V Integration: API|Y|SHOWRUNNER™: Y
75 +Floor Hub: Limited|Limited|N/A
76 +|A/V Integration: Crestron EISC|Y|SHOWRUNNER™: Y
77 +Floor Hub: N|N|N/A
78 78  |A/V Integration: RS-232|Y|(((
79 -ShowRunnerCLC™: Y
80 -HUB4: TBD
79 +SHOWRUNNER™: Y
80 +Floor Hub: TBD
81 81  )))|TBD|N/A
82 82  |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
83 -ShowRunnerCLC™: ShowRunnerCLC™ and Crestron Licenses Needed
84 -HUB4: Y
83 +SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
84 +Floor Hub: Y
85 85  )))|Y|N/A
86 86  |BACNET Features|(((
87 87  Per Area Status:
... ... @@ -98,8 +98,8 @@
98 98  
99 99  ~* More Features added upon request
100 100  )))|(((
101 -ShowRunnerCLC™: See list for ShowRunnerCLC™ Total Control
102 -HUB4: See list for ZUM-HUB4
101 +SHOWRUNNER™: See list for SHOWRUNNER™ Total Control
102 +Floor Hub: See list for ZUM-FLOOR-HUB
103 103  )))|(((
104 104  Per Room Status:
105 105  Online
... ... @@ -116,36 +116,35 @@
116 116  )))|N/A
117 117  |BACNET Settings Scope
118 118  (What Points are Exposed)|Per Area|(((
119 -ShowRunnerCLC™: Per Area
120 -HUB4: Global
119 +SHOWRUNNER™: Per Area
120 +Floor Hub: Global
121 121  )))|Global|N/A
122 -|BACNET Points Supported|Depends on Crestron License and Hardware
123 -See [[BACnet Integration>>doc:SHOWRUNNER™ Integrations Guide.Integration Options.ShowRunner BACNET Points.WebHome]]|ShowRunnerCLC™: Depends on Crestron License and Hardware
124 -HUB4: 9000|1000|N/A
122 +|BACNET Points Supported|Depends on Crestron License and Hardware|SHOWRUNNER™: Depends on Crestron License and Hardware
123 +Floor Hub: 1000|1000|N/A
125 125  |Crestron Fusion|Y|(((
126 -ShowRunnerCLC™: Y
127 -HUB4: N
125 +SHOWRUNNER™: Y
126 +Floor Hub: N
128 128  )))|N|N/A
129 -|Export to Zūm HUB4|Y, Licensed|ShowRunnerCLC™: Y, Licensed|N/A|N/A
130 -|GLPAC|Y|ShowRunnerCLC™: Y
131 -HUB4: Via ShowRunnerCLC™|N|N/A
128 +|Export to Zūm Floor Hub|Y, Licensed|SHOWRUNNER™: Y, Licensed|N/A|N/A
129 +|GLPAC|Y|SHOWRUNNER™: Y
130 +Floor Hub: Via SHOWRUNNER™|N|N/A
132 132  |System to System Link|Y|(((
133 -ShowRunnerCLC™: Y
134 -HUB4: N
132 +SHOWRUNNER™: Y
133 +Floor Hub: N
135 135  )))|N|N/A
136 136  |Minimum ZUM-NET Firmware|(((
137 137  CNET Mode: ZUM-WIRED 1.02.10 puf
138 138  ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
139 139  )))|(((
140 -ShowRunnerCLC™: TBD
141 -HUB4: TBD
139 +SHOWRUNNER™: TBD
140 +Floor Hub: TBD
142 142  )))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01
143 143  |Minimum SHOWRUNNER™ Version|(((
144 144  CNET Mode: 3.016
145 145  ZUM Mode: TBD
146 146  )))|N/A|N/A|N/A
147 -|ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as HUB4|MASTER|MASTER or SLAVE
148 -|ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|Same as HUB4|ZUM|ZUM
146 +|ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as Floor Hub|MASTER|MASTER or SLAVE
147 +|ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|Same as Floor Hub|ZUM|ZUM
149 149  
150 150  {{id name="caveats"/}}
151 151  
... ... @@ -159,8 +159,8 @@
159 159  
160 160  ==== FAQ: ====
161 161  
162 -* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-HUB4) and use ShowRunner™ Total Control?
163 -//Use a CP4N in lieu of the ZUM-HUB4.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.  [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
161 +* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
162 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.  [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
164 164  * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
165 165  //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
166 166  
... ... @@ -168,11 +168,11 @@
168 168  
169 169  ==== Topologies ====
170 170  
171 -**ShowRunnerCLC™ Total Control (Control Subnet or Flat)**
170 +**SHOWRUNNER™ Total Control (Control Subnet or Flat)**
172 172  [[image:ZumWired_SR-CS\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology Control Subnet"]][[image:ZumWired_SR-Flat\@2x.png||alt="Flat Topology"]]
173 173  
174 -**ShowRunnerCLC™ (External Room Export) + ZUM-HUB4 (Mirror Driver)**
175 -[[image:ZumWired_SRtoFH\@2x.png||alt="Zum HUB4 + SHOWRUNNER™ Topology"]]
173 +**SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
174 +[[image:ZumWired_SRtoFH\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]
176 176  
177 -**ZUM-HUB4 Only**
178 -[[image:ZumWired_FH\@2x.png||alt="Zum HUB4 Only"]]
176 +**ZUM-FLOOR-HUB Only**
177 +[[image:ZumWired_FH\@2x.png||alt="Zum Floor Hub Only"]]