... ... @@ -1,15 +1,15 @@
1 -Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
1 +Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management.  ShowRunnerCLC™ provides a number of integrations options that allow the designer to optimize the solution design.
2 2  
3 3  ~*~*~* Specifications are preliminary, the Zūm wired ZUM-FLOOR-HUB has not been released ~*~**
4 4  
5 5  ==== Integration Options ====
6 6  
7 -* **SHOWRUNNER™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
8 -* **SHOWRUNNER™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  SHOWRUNNER™ can export its own areas to the Floor Hub.
7 +* **ShowRunnerCLC™ Total Control** - The most comprehensive option.  Allows seamless integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
8 +* **ShowRunnerCLC™ + ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  ShowRunnerCLC™ can export its own areas to the Floor Hub.
9 9  
10 10  ==== Feature Matrix ====
11 11  
12 -|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB4 (Mirror Driver)|=ZUM-FLOOR-HUB4 Only|=Zūm iOS/Android Setup App*
12 +|=Feature|=ShowRunnerCLC™ Total Control|=ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB4 (Mirror Driver)|=ZUM-FLOOR-HUB4 Only|=Zūm iOS/Android Setup App*
13 13  |(% colspan="5" %)**Hardware Requirements**
14 14  |Requires ZUMNET JBox|Y|Y|Y|N
15 15  |Requires 3 or 4-Series Control System|Y|Y|N|N/A
... ... @@ -19,7 +19,7 @@
19 19  |Web Browser|(((
20 20  Crestron SmartGraphics XPanel
21 21  HTML5 UI
22 -)))|SHOWRUNNER™ - Crestron SmartGraphics XPanel/HTML5 UI
22 +)))|ShowRunnerCLC™ - Crestron SmartGraphics XPanel/HTML5 UI
23 23  ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
24 24  |iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
25 25  |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
... ... @@ -28,7 +28,7 @@
28 28  |Override Fade Time for Scene Recall|Y|TBD|TBD|TBD
29 29  |Scene Save|Y|TBD|TBD|Y
30 30  |Load Control|Y|TBD|TBD|Y
31 -|Demand Response|Y|Y, separate triggers for SHOWRUNNER™ and ZUM-FLOOR-HUB required|Y|N
31 +|Demand Response|Y|Y, separate triggers for ShowRunnerCLC™ and ZUM-FLOOR-HUB required|Y|N
32 32  |Enable/Disable Occupancy|Y|Y, from Floor Hub|Y|Y
33 33  |Override Occupancy Logic|Y|TBD|TBD|N
34 34  |Override|Y|Scene Recall only via ShowRunner|TBD|N/A
... ... @@ -35,22 +35,22 @@
35 35  |Plug Load On/Off|Y|Y|Y|By Hardware
36 36  |Integration with Non-Zūm Crestron Hardware|Y|N|N|N
37 37  |Custom Zūm Keypad Programming|Y|TBD|TBD|Y, within the limits of the hardware
38 -|New Feature Release Cycle|Aggressive|SHOWRUNNER™: Aggressive
38 +|New Feature Release Cycle|Aggressive|ShowRunnerCLC™: Aggressive
39 39  Floor Hub: 6-12 months|6-12 months|6-12 months
40 40  |Room Organization|(((
41 41  Organize According to Defined Nodes, multiple levels
42 42  Categorization to Filter by Tag
43 -)))|SHOWRUNNER™: See SHOWRUNNER™ Total Control
43 +)))|ShowRunnerCLC™: See ShowRunnerCLC™ Total Control
44 44  Floor Hub: Category/Room|Category/Room|(((
45 45  N/A
46 46  )))
47 -|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|SHOWRUNNER™: Automatic discovery (Pending)
48 -Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
47 +|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|ShowRunnerCLC™: Automatic discovery (Pending)
48 +Floor Hub: Map Mirrored Rooms to ShowRunnerCLC™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
49 49  |Network Topology|(((
50 50  * Flat
51 51  * Single Handoff to LAN w/ Control Subnet
52 52  (Requires  CP4N/AV4/PRO4)
53 -)))|Single Handoff to LAN w/ Control Subnet.  ShowRunner can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A
53 +)))|Single Handoff to LAN w/ Control Subnet.  ShowRunnerCLC™ can be on LAN or Control Subnet|Single Handoff to LAN w/ Control Subnet|N/A
54 54  |Network Addressing|(((
55 55  * Manual
56 56  * Customer (DHCP or Manual)
... ... @@ -57,30 +57,30 @@
57 57  * DHCP: Control Subnet (Requires CP4N/AV4/PRO4)
58 58  )))|Control Subnet|Control Subnet|N/A
59 59  |Firmware Updates|PUF Tool
60 -Automatic Support on Roadmap|SHOWRUNNER™: PUF Tool
60 +Automatic Support on Roadmap|ShowRunnerCLC™: PUF Tool
61 61  Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
62 -|Floorplans|Y|SHOWRUNNER™: Y
62 +|Floorplans|Y|ShowRunnerCLC™: Y
63 63  Floor Hub: N|N|N/A
64 64  |(% colspan="5" %)**Calendar/Scheduling**
65 65  |Logic Type|Event Driven
66 -Profile Support (Under Development)|SHOWRUNNER™: Event Driven
66 +Profile Support (Under Development)|ShowRunnerCLC™: Event Driven
67 67  Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
68 68  |Astronomical Clock|Y|Y, Per Category|Y, Per Category|N/A
69 -|Holidays|Pattern|SHOWRUNNER™: Pattern
69 +|Holidays|Pattern|ShowRunnerCLC™: Pattern
70 70  Floor Hub: Hard Coded|Hard Coded|N/A
71 -|Custom Patterns|Y, Advanced Scheduler License|SHOWRUNNER™: Y, Advanced Scheduler License
71 +|Custom Patterns|Y, Advanced Scheduler License|ShowRunnerCLC™: Y, Advanced Scheduler License
72 72  Floor Hub: N|N|N/A
73 73  |(% colspan="5" %)**Integrations**
74 -|A/V Integration: API|Y|SHOWRUNNER™: Y
74 +|A/V Integration: API|Y|ShowRunnerCLC™: Y
75 75  Floor Hub: Limited|Limited|N/A
76 -|A/V Integration: Crestron EISC|Y|SHOWRUNNER™: Y
76 +|A/V Integration: Crestron EISC|Y|ShowRunnerCLC™: Y
77 77  Floor Hub: N|N|N/A
78 78  |A/V Integration: RS-232|Y|(((
79 -SHOWRUNNER™: Y
79 +ShowRunnerCLC™: Y
80 80  Floor Hub: TBD
81 81  )))|TBD|N/A
82 82  |BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|(((
83 -SHOWRUNNER™: SHOWRUNNER™ and Crestron Licenses Needed
83 +ShowRunnerCLC™: ShowRunnerCLC™ and Crestron Licenses Needed
84 84  Floor Hub: Y
85 85  )))|Y|N/A
86 86  |BACNET Features|(((
... ... @@ -98,7 +98,7 @@
98 98  
99 99  ~* More Features added upon request
100 100  )))|(((
101 -SHOWRUNNER™: See list for SHOWRUNNER™ Total Control
101 +ShowRunnerCLC™: See list for ShowRunnerCLC™ Total Control
102 102  Floor Hub: See list for ZUM-FLOOR-HUB
103 103  )))|(((
104 104  Per Room Status:
... ... @@ -116,20 +116,20 @@
116 116  )))|N/A
117 117  |BACNET Settings Scope
118 118  (What Points are Exposed)|Per Area|(((
119 -SHOWRUNNER™: Per Area
119 +ShowRunnerCLC™: Per Area
120 120  Floor Hub: Global
121 121  )))|Global|N/A
122 -|BACNET Points Supported|Depends on Crestron License and Hardware|SHOWRUNNER™: Depends on Crestron License and Hardware
122 +|BACNET Points Supported|Depends on Crestron License and Hardware|ShowRunnerCLC™: Depends on Crestron License and Hardware
123 123  Floor Hub: 1000|1000|N/A
124 124  |Crestron Fusion|Y|(((
125 -SHOWRUNNER™: Y
125 +ShowRunnerCLC™: Y
126 126  Floor Hub: N
127 127  )))|N|N/A
128 -|Export to Zūm Floor Hub|Y, Licensed|SHOWRUNNER™: Y, Licensed|N/A|N/A
129 -|GLPAC|Y|SHOWRUNNER™: Y
130 -Floor Hub: Via SHOWRUNNER™|N|N/A
128 +|Export to Zūm Floor Hub|Y, Licensed|ShowRunnerCLC™: Y, Licensed|N/A|N/A
129 +|GLPAC|Y|ShowRunnerCLC™: Y
130 +Floor Hub: Via ShowRunnerCLC™|N|N/A
131 131  |System to System Link|Y|(((
132 -SHOWRUNNER™: Y
132 +ShowRunnerCLC™: Y
133 133  Floor Hub: N
134 134  )))|N|N/A
135 135  |Minimum ZUM-NET Firmware|(((
... ... @@ -136,7 +136,7 @@
136 136  CNET Mode: ZUM-WIRED 1.02.10 puf
137 137  ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
138 138  )))|(((
139 -SHOWRUNNER™: TBD
139 +ShowRunnerCLC™: TBD
140 140  Floor Hub: TBD
141 141  )))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01
142 142  |Minimum SHOWRUNNER™ Version|(((
... ... @@ -167,10 +167,10 @@
167 167  
168 168  ==== Topologies ====
169 169  
170 -**SHOWRUNNER™ Total Control (Control Subnet or Flat)**
170 +**ShowRunnerCLC™ Total Control (Control Subnet or Flat)**
171 171  [[image:ZumWired_SR-CS\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology Control Subnet"]][[image:ZumWired_SR-Flat\@2x.png||alt="Flat Topology"]]
172 172  
173 -**SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
173 +**ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
174 174  [[image:ZumWired_SRtoFH\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]
175 175  
176 176  **ZUM-FLOOR-HUB Only**