Changes for page Crestron Zūm Wired

Last modified by Scott Kohlmann on 2023/04/20 22:22

From version 17.1
edited by Mark Kohlmann
on 2021/12/08 00:15
Change comment: Renamed from xwiki:SHOWRUNNER™ User Guide & Wiki.Design Guide.Hardware Design Guide.Crestron Zūm Wired.WebHome
To version 18.3
edited by Alexander Mott
on 2023/03/24 15:32
Change comment: (Autosaved)

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ User Guide & Wiki.Design Guide.Hardware Design Guide.WebHome
1 +Design Guide.Hardware Design Guide.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.mark\.kohlmann@chiefintegrations\.com
1 +XWiki.alexander\.mott@chiefintegrations\.com
Hidden
... ... @@ -1,1 +1,1 @@
1 -false
1 +true
Content
... ... @@ -1,4 +1,4 @@
1 - Crestron Zūm Wired is a locally integrated lighting control system with various global control options.  Zūm rooms are self-contained control units with primary logic occurring at the room level.  Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
1 +Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
2 2  
3 3  ~*~*~* Specifications are preliminary, the Zūm wired ZUM-FLOOR-HUB has not been released ~*~**
4 4  
... ... @@ -133,7 +133,7 @@
133 133  Floor Hub: N
134 134  )))|N|N/A
135 135  |Minimum ZUM-NET Firmware|(((
136 -CNET Mode: ZUM-WIRED 1.00.09 puf
136 +CNET Mode: ZUM-WIRED 1.02.10 puf
137 137  ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
138 138  )))|(((
139 139  SHOWRUNNER™: TBD
... ... @@ -140,7 +140,7 @@
140 140  Floor Hub: TBD
141 141  )))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01
142 142  |Minimum SHOWRUNNER™ Version|(((
143 -CNET Mode: 3.003
143 +CNET Mode: 3.016
144 144  ZUM Mode: TBD
145 145  )))|N/A|N/A|N/A
146 146  |ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as Floor Hub|MASTER|MASTER or SLAVE
... ... @@ -152,8 +152,8 @@
152 152  
153 153  * Consult Chief Integrations to verify sequence of operations if there are any concerns.
154 154  * Additional caveats:
155 -** Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
156 -** Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
155 +** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.--  Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
156 +** --Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.--  Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
157 157  ** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.  Discovery must be fixed before ShowRunner can auto-discover hardware.
158 158  
159 159  ==== FAQ: ====
... ... @@ -163,7 +163,7 @@
163 163  * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
164 164  //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
165 165  
166 -==== ====
166 +==== ====
167 167  
168 168  ==== Topologies ====
169 169