Changes for page Crestron Zūm Wired

Last modified by Scott Kohlmann on 2023/04/20 22:22

From version 17.1
edited by Mark Kohlmann
on 2021/12/08 00:15
Change comment: Renamed from xwiki:SHOWRUNNER™ User Guide & Wiki.Design Guide.Hardware Design Guide.Crestron Zūm Wired.WebHome
To version 13.1
edited by Mark Kohlmann
on 2021/10/05 22:11
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -21,7 +21,7 @@
21 21  HTML5 UI
22 22  )))|SHOWRUNNER™ - Crestron SmartGraphics XPanel/HTML5 UI
23 23  ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
24 -|iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
24 +|iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
25 25  |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
26 26  |(% colspan="5" %)**Features**
27 27  |Scene Recall|Y|Y|Y|Y
... ... @@ -135,10 +135,7 @@
135 135  |Minimum ZUM-NET Firmware|(((
136 136  CNET Mode: ZUM-WIRED 1.00.09 puf
137 137  ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
138 -)))|(((
139 -SHOWRUNNER™: TBD
140 -Floor Hub: TBD
141 -)))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01
138 +)))|N/A|See Crestron|See Crestron
142 142  |Minimum SHOWRUNNER™ Version|(((
143 143  CNET Mode: 3.003
144 144  ZUM Mode: TBD
... ... @@ -154,16 +154,16 @@
154 154  * Additional caveats:
155 155  ** Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
156 156  ** Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
157 -** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.  Discovery must be fixed before ShowRunner can auto-discover hardware.
154 +** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.
158 158  
159 159  ==== FAQ: ====
160 160  
161 161  * I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
162 -//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.  [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
159 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.//
163 163  * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
164 164  //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
165 165  
166 -==== ====
163 +==== ====
167 167  
168 168  ==== Topologies ====