Changes for page Crestron Zūm Wired

Last modified by Scott Kohlmann on 2023/04/20 22:22

From version 13.1
edited by Mark Kohlmann
on 2021/10/05 22:11
Change comment: There is no comment for this version
To version 18.3
edited by Alexander Mott
on 2023/03/24 15:32
Change comment: (Autosaved)

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ User Guide & Wiki.Design Guide.Hardware Design Guide.WebHome
1 +Design Guide.Hardware Design Guide.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.mark\.kohlmann@chiefintegrations\.com
1 +XWiki.alexander\.mott@chiefintegrations\.com
Hidden
... ... @@ -1,1 +1,1 @@
1 -false
1 +true
Content
... ... @@ -1,4 +1,4 @@
1 - Crestron Zūm Wired is a locally integrated lighting control system with various global control options.  Zūm rooms are self-contained control units with primary logic occurring at the room level.  Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
1 +Crestron Zūm Wired is a locally integrated lighting control system with various global control options. Zūm rooms are self-contained control units with primary logic occurring at the room level. Central control systems offer scheduling and management.  SHOWRUNNER™ provides a number of integrations options that allow the designer to optimize the solution design.
2 2  
3 3  ~*~*~* Specifications are preliminary, the Zūm wired ZUM-FLOOR-HUB has not been released ~*~**
4 4  
... ... @@ -21,7 +21,7 @@
21 21  HTML5 UI
22 22  )))|SHOWRUNNER™ - Crestron SmartGraphics XPanel/HTML5 UI
23 23  ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
24 -|iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
24 +|iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
25 25  |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
26 26  |(% colspan="5" %)**Features**
27 27  |Scene Recall|Y|Y|Y|Y
... ... @@ -133,11 +133,14 @@
133 133  Floor Hub: N
134 134  )))|N|N/A
135 135  |Minimum ZUM-NET Firmware|(((
136 -CNET Mode: ZUM-WIRED 1.00.09 puf
136 +CNET Mode: ZUM-WIRED 1.02.10 puf
137 137  ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
138 -)))|N/A|See Crestron|See Crestron
138 +)))|(((
139 +SHOWRUNNER™: TBD
140 +Floor Hub: TBD
141 +)))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01
139 139  |Minimum SHOWRUNNER™ Version|(((
140 -CNET Mode: 3.003
143 +CNET Mode: 3.016
141 141  ZUM Mode: TBD
142 142  )))|N/A|N/A|N/A
143 143  |ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as Floor Hub|MASTER|MASTER or SLAVE
... ... @@ -149,14 +149,14 @@
149 149  
150 150  * Consult Chief Integrations to verify sequence of operations if there are any concerns.
151 151  * Additional caveats:
152 -** Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
153 -** Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
154 -** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.
155 +** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.--  Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
156 +** --Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.--  Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
157 +** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.  Discovery must be fixed before ShowRunner can auto-discover hardware.
155 155  
156 156  ==== FAQ: ====
157 157  
158 158  * I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
159 -//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.//
162 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.  [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
160 160  * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
161 161  //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
162 162