Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -9,7 +9,7 @@
9 9  
10 10  ==== Feature Matrix ====
11 11  
12 -|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
12 +|=Feature|=SHOWRUNNER™ Total Control|=SHOWRUNNER™ (External Room Export) + ZUM-FLOOR-HUB4 (Mirror Driver)|=ZUM-FLOOR-HUB4 Only|=Zūm iOS/Android Setup App*
13 13  |(% colspan="5" %)**Hardware Requirements**
14 14  |Requires ZUMNET JBox|Y|Y|Y|N
15 15  |Requires 3 or 4-Series Control System|Y|Y|N|N/A
... ... @@ -19,7 +19,7 @@
19 19  |Web Browser|(((
20 20  Crestron SmartGraphics XPanel
21 21  HTML5 UI
22 -)))|SHOWRUNNER™ - Crestron SmartGraphics XPanel
22 +)))|SHOWRUNNER™ - Crestron SmartGraphics XPanel/HTML5 UI
23 23  ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
24 24  |iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
25 25  |Touchscreens (Crestron TSW series)|Y|Y, Limited Features for Zūm Rooms|N|N
... ... @@ -44,7 +44,7 @@
44 44  Floor Hub: Category/Room|Category/Room|(((
45 45  N/A
46 46  )))
47 -|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices|SHOWRUNNER™: Automatic discovery
47 +|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|SHOWRUNNER™: Automatic discovery (Pending)
48 48  Floor Hub: Map Mirrored Rooms to SHOWRUNNER™ and Discovery External Rooms|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
49 49  |Network Topology|(((
50 50  * Flat
... ... @@ -132,8 +132,16 @@
132 132  SHOWRUNNER™: Y
133 133  Floor Hub: N
134 134  )))|N|N/A
135 -|Minimum ZUM-NET Firmware|ZUM-WIRED 1.00.08 puf|N/A|See Crestron|See Crestron
136 -|Minimum SHOWRUNNER™ Version|2.208|N/A|N/A|N/A
135 +|Minimum ZUM-NET Firmware|(((
136 +CNET Mode: ZUM-WIRED 1.00.09 puf
137 +ZUM Mode: ZUM-WIRED  1.xx.xxx puf (Pending)
138 +)))|N/A|See Crestron|See Crestron
139 +|Minimum SHOWRUNNER™ Version|(((
140 +CNET Mode: 3.003
141 +ZUM Mode: TBD
142 +)))|N/A|N/A|N/A
143 +|ZWMS (Zum Wired Master/Slave Mode)|MASTER|Same as Floor Hub|MASTER|MASTER or SLAVE
144 +|ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|Same as Floor Hub|ZUM|ZUM
137 137  
138 138  {{id name="caveats"/}}
139 139  
... ... @@ -140,12 +140,15 @@
140 140  ==== Caveats ====
141 141  
142 142  * Consult Chief Integrations to verify sequence of operations if there are any concerns.
143 -* Additional caveats TBD
151 +* Additional caveats:
152 +** Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
153 +** Raw Occupancy reporting does not work.  A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner.  ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored.  This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.
154 +** Cresnet Discovery is not working on ZUMNET-JBOXs.  Crestron has acknowledged a fix has been sent to QE.
144 144  
145 145  ==== FAQ: ====
146 146  
147 147  * I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
148 -//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.//
159 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB.  A DIN-AP4 is not required.  Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails.//
149 149  * Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
150 150  //If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
151 151