ShowRunner uses Crestron's BACnet stack and is bound by its licensing and limits.  ShowRunner's BACnet feature is licensed.  Integrations of 50 points or less may use the free Crestron BACNET license.  More than 50 points require the Crestron paid license and total points are limited by the platform.  The processor itself consumes a point.  BACnet points are assigned during commissioning.  A csv export of the points may be downloaded from the system.

Crestron BACnet Stack Details

Control SystemMax # of Points
  • FT-TSC600 (Not Supported by SR)
  • TPCS-4SM (Not Supported by SR)
  • TPCS-4SMD (Not Supported by SR)
  • TSCW-730 (Not Supported by SR)
250
  • DIN-AP3
  • DIN-AP4
  • DIN-AP3MEX
  • MC3 (Not Supported by SR)
  • MC4
  • RMC3
  • RMC4
500
  • CP3
  • CP4
  • CP3N
  • CP4N
1000
  • AV3
  • AV4
  • PRO3
  • PRO4
2000

Crestron PICS Statement

ShowRunner BACNET Points

Area BACNET Points

AreaBaseIDs are assigned automatically and maintained.  Points are discoverable.  Each of the points may be enabled or disabled by area to optimize the integration.  This is the default ShowRunner BACnet mode.

FeatureDescriptionTypePointLabelR/WUnits
Area SceneCurrent Scene Active on the AreaMVAreaBaseID{AreaId}:{AreaName} SceneRWScene
Occupancy ModeCurrent Occupancy Mode for the AreaMVAreaBaseID + 2{AreaId}:{AreaName} Occupancy ModeRWMode
Occupancy StatusCurrent Occupancy Status for the AreaBIAreaBaseID + 1{AreaId}:{AreaName} OccupiedRBoolean
Area IntensityCurrent Area Average Intensity/Load Level (v3.010 or later)AVAreaBaseID + 3{AreaId}:{AreaName} IntensityRWPercentage
Area PowerCurrent Area Power Consumption in Watts (Requires EM License & v3.010 or later)AIAreaBaseID + 4{AreaId}:{AreaName} PowerRWatts
LoadsIndividual Load intensities for each Load in the AreaAVAreaBaseID + 1000 + LoadIndex{AreaId}:{AreaName} Load{LoadId}:{LoadName}RWPercentage
Photocell LevelPhotocell sensor reading for each Photocell in the AreaAIAreaBaseID + 100 + PhotocellIndex{AreaId}:{AreaName} Photocell{PhotocellId}:{PhotocellName}RPercentage

Global BACNET Points

FeatureDescriptionTypePointLabelR/WUnits
Master OverrideActivates or Deactivates Master Override System WideBV10Master OverrideRWBoolean
Demand ResponseActivates or Deactivates Demand ResponseBV11Demand ResponseRWBoolean
Normal / After HoursChanges System State between Normal and After HoursMV12Normal / After HoursRW

1: Normal
2: After Hours

Device Offline CountIndicates the number of devices that are offlineAV20Device Offline CountRInteger
AlarmIndicates a critical failure, see user interface for more informationBV21AlarmRBoolean

Zum Floor Hub BACnet Point Emulation

ShowRunner can emulate the Zum Floor Hubs BACnet points as an alternative to the standard ShowRunner mode.  Each point may be enabled/disabled individually by Area.

Set the following Area properties:

BACnetIndex: (ID of the Room, this number of multiplied times 2048 to get the BACnet points, start at 1)
BACnetMode: "ZumEmulation"
FeatureTypePointLabelDescriptionR/WUnits
Area SceneMVAreaBaseID + 8{AreaName}>{AreaId}>ActiveScene>BIView or change the current scene.  Off scene is 17, Scenes 1 through 16 depend on area configuration.RWScene
Occupancy ModeBVAreaBaseID + 6{AreaName}>{AreaId}>OccupancySensorEnabled>BVEnable or disable the occupancy sensor.  Enable will activate the last occupancy/vacancy mode.RWBoolean
Occupancy StatusBIAreaBaseID + 2{AreaName}>{AreaId}>RoomOccupied>BICurrent room occupancy stateRBoolean
OnlineBIAreaBaseID{AreaName}>{AreaId}>RoomOnline>BICurrent room online state, this is fixed as true.RBoolean
OnBIAreaBaseID + 1{AreaName}>{AreaId}>RoomOn>BICurrent room load state.  If any load is on this will be true.RBoolean
AreaBaseID = BACnetIndex * 2048