Show last authors
1 Crestron Zūm Wireless is a locally integrated lighting control system with various global control options.  Zūm rooms are self-contained control units with primary logic occurring at the room level.  Central control systems offer scheduling and management.  ShowRunnerCLC™ provides a number of integrations options that allow the designer to optimize the solution design.
2
3 ==== Integration Options ====
4
5 * **ShowRunnerCLC™ Total Control** - The most comprehensive option.  Allows seamless (see [[Caveats>>WebHome||anchor="caveats"]]) integration of Zūm and non-Zūm Crestron lighting control products.  Extensive feature set allows centralized control and management of Zūm rooms.  Advanced scheduler provides more flexibility to the facility operator.  This solution replaces the ZUM-FLOOR-HUB in the system design.
6 * **ShowRunnerCLC™ + AVBRIDGE + Serial Port** - Provides scene setting and load control via a dedicated AVBRIDGE in each Zūm room.  Requires a dedicated serial port (C2N-IO/CEN-IO-COM2/etc) and a dedicated ZUMMESH-AVBRIDGE per room.
7 * **ShowRunnerCLC™+ ZUM-FLOOR-HUB** - Provides limited scene recall and room status for Zūm rooms paired with the Floor Hub.  ShowRunnerCLC™ can export its own areas to the Floor Hub.
8
9 ==== Feature Matrix ====
10
11 (% border="1" style="margin-left:auto; margin-right:auto" %)
12 |=Feature|=ShowRunnerCLC™ Total Control|=ShowRunnerCLC™ + AVBRIDGE + Serial Port|=ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)|=ZUM-FLOOR-HUB Only|=Zūm iOS/Android Setup App*
13 |(% colspan="6" %)**Hardware Requirements**
14 |Requires JBOX with ZUMMESH-NETBRIDGE|Y|N|Y|Y|Y
15 |Requires ZUMMESH-GATEWAY|Y|N|Y|Y|N/A
16 |Requires Dedicated RS-232 Serial Port per Room|N|Y|N|N|N/A
17 |Requires 3 or 4-Series Control System|Y|Y|Y|N|N/A
18 |Requires Physical Presence in Room to Change Scenes|N|N|Y, via Zūm Setup App|Y, via Zūm Setup App|Y
19 |(% colspan="6" %)**User Interfaces**
20 |Web Browser|(((
21 Crestron SmartGraphics XPanel
22 HTML5 UI Under Development (Q2 2021)
23 )))|Crestron SmartGraphics XPanel
24 HTML5 UI Under Development (Q2 2021)|ShowRunnerCLC™ - Crestron SmartGraphics XPanel
25 ZUM-FLOOR-HUB - HTML5 UI|HTML5 UI|N
26 |iOS/Android|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade)|Y, Crestron App (Paid Upgrade), Limited Features for Zūm Rooms|N|Y*
27 |Touchscreens (Crestron TSW series)|Y|Y|Y, Limited Features for Zūm Rooms|N|N
28 |(% colspan="6" %)**Features**
29 |Scene Recall|Y ~*~*~*~*|Y ~*~*~*~*|Y|Y|Y
30 |Override Fade Time for Scene Recall ~*~*|Y|N|N|N|N
31 |Scene Save|Y ~*~*~*~*|Y ~*~*~*~*|N|N|Y
32 |Load Control|Y ~*~**/~*~*~*~**|Y ~*~**|N|N|Y
33 |Demand Response|Y|N|Y, separate triggers for ShowRunnerCLC™ and ZUM-FLOOR-HUB required|Y|N
34 |Enable/Disable Occupancy|Y|Y|Y, from Floor Hub|Y|Y
35 |Override Occupancy Logic|Y|Y|N|N|N
36 |Override|Y~*~*~*~*~*~*|N|Scene Recall only via ShowRunnerCLC™|N|N/A
37 |Plug Load On/Off|Y|Y|Y|Y|By Hardware
38 |Integration with Non-Zūm Crestron Hardware|Y|Y|N|N|N
39 |Custom Zūm Keypad Programming|(((
40 Y, per individual button (1 through 4)
41 AV Keypad not required (v3.004 or later)
42 [[Details>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Advanced Tools.Zummesh Keypad Custom Programming.WebHome]]
43 )))|Y, Zūm AV Keypad Only|N|N|Y, within the limits of the hardware
44 |New Feature Release Cycle|Aggressive|Aggressive|ShowRunnerCLC™: Aggressive
45 Floor Hub: 6-12 months|6-12 months|6-12 months
46 |Room Organization|(((
47 Under Development:
48 Building/Floor/Sub-Group/Area
49 Categorization to Filter by Category/Tag
50 )))|See ShowRunnerCLC™ Total Control|ShowRunnerCLC™: See ShowRunnerCLC™ Total Control
51 Floor Hub: Category/Room|Category/Room|(((
52 N/A
53 )))
54 |Room Discovery|Automatic Discovery of Gateways and NETBRIDGES|Pre-Configured at Order|ShowRunnerCLC™: Pre-Configured at Order
55 Floor Hub: Map Mirrored Rooms to ShowRunnerCLC™ and Discovery External Rooms|Automatic Discovery of Gateways and NETBRIDGES|N/A
56 |Firmware Updates|PUF Tool
57 Automatic Support on Roadmap|(((
58 PUF Tool
59 Automatic Support on Roadmap
60 )))|ShowRunnerCLC™: PUF Tool
61 Floor Hub: Automatic, Internet Connection Required|Automatic, Internet Connection Required|N/A
62 |(% colspan="6" %)**Calendar/Scheduling**
63 |Logic Type|Event Driven
64 Profile Support (Under Development)|Event Driven
65 Profile Support (Under Development)|ShowRunnerCLC™: Event Driven
66 Floor Hub: Pattern assigned to Category|Pattern assigned to Category|N/A
67 |Astronomical Clock|Y|Y|Y, Per Category|Y, Per Category|N/A
68 |Holidays|Pattern|Pattern|ShowRunnerCLC™: Pattern
69 Floor Hub: Hard Coded|Hard Coded|N/A
70 |Custom Patterns|Y, Advanced Scheduler License|Y, Advanced Scheduler License|ShowRunnerCLC™: Y, Advanced Scheduler License
71 Floor Hub: N|N|N/A
72 |(% colspan="6" %)**Integrations**
73 |A/V Integration: API|Y|Y|ShowRunnerCLC™: Y
74 Floor Hub: Limited|Limited|N/A
75 |A/V Integration: Crestron EISC|Y|Y|ShowRunnerCLC™: Y
76 Floor Hub: N|N|N/A
77 |A/V Integration: RS-232|Y|Y|(((
78 ShowRunnerCLC™: Y
79 Floor Hub: AVBRIDGE per Area
80 )))|AVBRIDGE per Area|N/A
81 |BACNET|Y, ShowRunnerCLC™ and Crestron Licenses Needed|Y, ShowRunnerCLC™ and Crestron Licenses Needed|(((
82 ShowRunnerCLC™: ShowRunnerCLC™ and Crestron Licenses Needed
83 Floor Hub: Y
84 )))|Y|N/A
85 |BACNET Features|(((
86 Per Area Status:
87 Active Scene
88 Occupied
89 Occupancy Enabled
90 Individual Load Level
91 Photocell Level (per Photocell)
92 Plug Loads Enabled
93
94 System:
95 Demand Response Enabled
96 System Wide Override (Panic/Emergency)
97
98 ~* More Features added upon request
99 )))|See list for ShowRunnerCLC™ Total Control|(((
100 ShowRunnerCLC™: See list for ShowRunnerCLC™ Total Control
101 Floor Hub: See list for ZUM-FLOOR-HUB
102 )))|(((
103 Per Room Status:
104 Online
105 On
106 Occupied
107 Daylighting Active
108 Device Battery is Low
109 Plug Loads Enabled
110 Occupancy Sensor Enabled
111 Current Daylight Level
112 Active Scene
113 \\System:
114 Demand Response Enabled
115 )))|N/A
116 |BACNET Settings Scope
117 (What Points are Exposed)|Per Area|Per Area|(((
118 ShowRunnerCLC™: Per Area
119 Floor Hub: Global
120 )))|Global|N/A
121 |BACNET Points Supported|Depends on Crestron License and Hardware|Depends on Crestron License and Hardware|ShowRunnerCLC™: Depends on Crestron License and Hardware
122 Floor Hub: 1000|1000|N/A
123 |Crestron Fusion|Y|Y|(((
124 ShowRunnerCLC™: Y
125 Floor Hub: N
126 )))|N|N/A
127 |Export to Zūm Floor Hub|Y, Licensed|Y, Licensed|ShowRunnerCLC™: Y, Licensed|N/A|N/A
128 |GLPAC|Y|Y|ShowRunnerCLC™: Y
129 Floor Hub: Via ShowRunnerCLC™|N|N/A
130 |System to System Link|Y|Y|(((
131 ShowRunnerCLC™: Y
132 Floor Hub: N
133 )))|N|N/A
134 |Minimum NETBRIDGE Firmware|v1.13.0020 (PUF Zum MESHNET v1.07.16)|v1.010|N/A|See Crestron|See Crestron
135 |Minimum Gateway Firmware|v1.4469.00022|N/A|N/A|See Crestron|See Crestron
136 |Minimum ShowRunnerCLC™ Version|2.198|2.198|N/A|N/A|N/A
137
138 {{{* Zūm Setup App works as long as the NETBRIDGE is physically near the iOS/Android device running the Zūm Setup App.
139 ** Fade time is automatically applied if scene is set longer than 1 second. Must be triggered from ShowRunnerCLC™, cannot be triggered from Zūm keypad with current firmware (as of April 2020).
140 *** Zūm wireless does not support direct coupling of fade times and the behavior is different internally within the dimmer versus other Crestron products. Raise/Lower level accuracy is not guaranteed. For best performance when settings scenes, set the slider manually which will send exact levels to the dimmer.
141 **** Zūm wireless scenes cannot presently be read on command. Scenes should be created and saved from ShowRunnerCLC™ directly. Saved scenes are stored directly on the Zūm wireless dimmer and in ShowRunnerCLC™. ShowRunner will query the NETBRIDGE after scene recall and attempt to build scene information but operations are done one at a time.
142 ***** Zūm wireless real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunner.  Levels set by the daylight sensor with daylighting enabled will not be reported by v. Sometimes delays in sending load levels occur. Feature is primarily intended for remotely setting scenes.
143 ****** Zūm wireless does not support a true override but ShowRunnerCLC™ will disable keypads and occupancy sensors and recall scene 15. The occupancy sensor enabled state and current scene will be remembered and recalled when leaving occupancy mode.
144 }}}
145
146 {{id name="caveats"/}}
147
148 ==== Caveats ====
149
150 * Consult Chief Integrations to verify sequence of operations if there are any concerns.  Zum wireless is not a direct replacement for Crestron wired and infiNET EX wireless products.
151 * Zum Wireless has an internal rate limit that will shutdown communication if a number of commands are received in a short period of time.  This can be seen when repeatedly pressing buttons on a keypad as well as repeatedly triggering actions from ShowRunnerCLC™.
152 * Raise/Lower operations from ShowRunner cannot track directly with the load response, see ~*~** above.  ShowRunner will poll the NETBRIDGE for current levels ~~3 seconds after the raise/lower is stopped to obtain current load levels.
153 * Lower operations can turn the load off.  The load will not come on with a raise.  This is a firmware behavior in the Zum hardware.
154 * Wireless control presents some additional latency possibilities.  Commands required to provide full functionality (load control/raise/lower) with Zum wireless are more intensive than traditional Crestron hardware and may impact performance under heavy load.  Local operation of the Zum wireless room is not impacted.
155 * Real time load status is not available.  Any changes to loads performed using the raise/lower functions in room will not be propagated back to ShowRunnerCLC™.  Levels set by the daylight sensor with daylighting enabled will not be reported by ShowRunnerCLC™.
156 * Keypad behaviors cannot be modified in ShowRunnerCLC™.  Some modifications are permitted within the Zum app.  Custom keypads can be implemented using the AVBRIDGE connected to the system via a serial port, Zum requires an AV specific keypad for this purpose; or via export buttons ([[Details>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Advanced Tools.Zummesh Keypad Custom Programming.WebHome]]).
157 * Zum Partition Sensors do not report back to the system and cannot be used to handle room divide/combine logic externally to the linked Zum rooms.
158 * Off Scene cannot be saved and is always room Off
159 * Scenes 1 through 16 are supported and may be modified and saved.
160 * Scenes with fade times greater than 1 second will result in loads being commanded individual from ShowRunnerCLC™ and may not be in sync depending on load quantity, RF gateway load, and RF signal integrity.  Zum hardware does not support a fade time as part of the Scene setting.  Fade times must be commanded from ShowRunnerCLC™.  Scene fade times will be ignored when scenes are activated by Zum keypads or internal occupancy logic.
161 * Saving scenes from ShowRunnerCLC™ captures the levels set in ShowRunnerCLC™ at the time of the save.  ShowRunner will attempt to learn scenes as they are recalled.
162 * Override/Override Level features are not supported
163 * Load disable is not supported
164 * After hours logic is not supported
165 * Blink before timeout is not supported
166 * CCT control is presently not supported (ZUMMESH-JBOX-DALI support may be available in the future)
167 * RGB loads are not supported
168 * Minimum/Maximum Levels are not supported when loads are being recalled locally.  ShowRunnerCLC™ will honor them when control occurs from ShowRunnerCLC™ except for raise/lower which is performed on hardware.
169 * Dimming curves are not supported when loads are being recalled locally.  Use Zum app to adjust dimming curves if necessary.  Recommended to leave ShowRunnerCLC™ dimming curve set to "Unaffected".
170 * BACNET support requires a processor hardware license and ShowRunner BACNET license.  BACNET point availability can be configured per Area.
171 * Chief Integrations recommends one 4-series (preferred) or 3-series processor per building floor at a minimum.
172 * Zummesh and infiNET EX devices are not officially supported on the same gateway, discuss with Crestron if needing both.
173
174 (% id="HTopologies" %)
175 ==== Topologies ====
176
177 (% class="box" %)
178 (((
179 **ShowRunnerCLC™ Total Control**
180 [[image:ZumSr\@2x.png||alt="Zum SHOWRUNNER™ Total Control Topology"]]
181 )))
182
183 (% class="box" %)
184 (((
185 **ShowRunnerCLC™ + AVBRIDGE + Serial Port**
186 [[image:ZumAvbSr\@2x.png||alt="Zum AVBRIDGE + SHOWRUNNER™ Topology"]]
187 )))
188
189 (% class="box" %)
190 (((
191 **ShowRunnerCLC™ (External Room Export) + ZUM-FLOOR-HUB (Mirror Driver)**
192 [[image:ZumFhSr\@2x.png||alt="Zum Floor Hub + SHOWRUNNER™ Topology"]]
193 )))
194
195 (% class="box" %)
196 (((
197 **ZUM-FLOOR-HUB Only**
198 [[image:ZumFh\@2x.png||alt="Zum Floor Hub Topology"]]
199 )))
200
201 (% class="box" %)
202 (((
203 **Zūm iOS/Android Setup App**
204 [[image:ZumApp\@2x.png||alt="Zum App Topology"]]