6 (((
7 (% class="col-xs-12 col-sm-8" %)
8 (((
Alexander Mott 4.2 9 = Zūm Wired System Overview =
Alexander Mott 1.1 10
Alexander Mott 5.2 11 Zūm Wired is a distributed lighting control system manufactured and distributed by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, DMX, and DALI protocols to allow for automated control of a building's lighting.
Alexander Mott 1.1 12
Alexander Mott 11.2 13 A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same Ethernet wiring standards. The three networks in a Zūm Wired system that use Ethernet standard cabling are:
Alexander Mott 5.2 14
Alexander Mott 11.2 15 * Ethernet
Alexander Mott 5.2 16 * Zūm Net
Alexander Mott 13.1 17 * Zūm Link
Alexander Mott 5.2 18
Alexander Mott 11.2 19 In addition to the three networks listed above, there are two additional wiring standards that may be encountered to connect non-Zūm devices to the Zūm Link network, which are covered below under the Zūm Link section
20
21 == Ethernet ==
22
Alexander Mott 24.1 23 Ethernet provides the backbone of the lighting network. Ethernet joins the Hub panels to each other, the processor, and (if the design calls for it) the building LAN. All Ethernet cabling should adhere to the [[Ethernet standards>>doc:Wiring Guide.Wiring Overview.Ethernet.WebHome]] for Crestron systems.
Alexander Mott 11.2 24
Alexander Mott 5.1 25 == Zūm Net ==
Alexander Mott 1.1 26
Alexander Mott 13.1 27 Zūm Net wiring should adhere to Ethernet cabling standards and use standard RJ-45 connectors. Zūm Net connects networked room-level controllers throughout the building to each other and to the lighting network. Each Zūm Net run will typically originate at a Hub or Processor panel and then connect to a number of ZUMNET-JBOX devices.
Alexander Mott 1.1 28
Alexander Mott 13.1 29 Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable and devices are shown in purple on //Figure 1//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. ZUMNET-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
30
Alexander Mott 5.1 31 == Zūm Link ==
Alexander Mott 1.1 32
Alexander Mott 27.1 33 Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. Links to articles covering specific Zūm Link devices can be found [[here>>doc:Wiring Guide.Zūm Wired System Overview.WebHome]].
Alexander Mott 1.1 34
Alexander Mott 5.1 35 === Zūm Link to Cresnet ===
Alexander Mott 1.1 36
Alexander Mott 15.1 37 While most Zūm Link wiring will adhere to Ethernet cabling standards and utilize standard RJ-45 connectors, Zūm Link is not technically Ethernet. In some situations, it may be necessary to wire traditional Cresnet devices into a Zūm Link space.
Alexander Mott 1.1 38
Alexander Mott 22.2 39 In the future, Crestron will be producing a ZUMLINK-CNRJ45 adapter to allow for plug-and-play connections between Zūm Link RJ-45 connectors and 4-wire Cresnet devices. Until this product is available however, it is necessary to strip the Zūm Link wire and terminate it directly into a Cresnet phoenix connector or terminal block.
Alexander Mott 15.1 40
Alexander Mott 22.2 41 The pin-out to connect a Cresnet device to a Zūm Link network that has been terminated per the T568B standard is as follows:
42
Alexander Mott 23.1 43 (% border="1" style="margin-right:auto" %)
Alexander Mott 24.1 44 |=(% style="width: 87px;" %)RJ-45 Pin|=(% style="width: 213px;" %)Function|=(% style="width: 257px;" %)Cresnet Color|=(% style="width: 426px;" %)T568-B Color
45 |(% style="width:87px" %)1|(% style="width:213px" %)24V|(% colspan="1" rowspan="2" style="width:257px" %)Red|(% style="width:426px" %)White / Orange
46 |(% style="width:87px" %)2|(% style="width:213px" %)24V|(% style="width:426px" %)Orange
47 |(% style="width:87px" %)3|(% style="width:213px" %)GND|(% colspan="1" rowspan="2" style="width:257px" %)Black|(% style="width:426px" %)White / Green
48 |(% style="width:87px" %)4|(% style="width:213px" %)GND|(% style="width:426px" %)Blue
Alexander Mott 26.1 49 |(% style="width:87px" %)5|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)White / Blue
50 |(% style="width:87px" %)6|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)Green
Alexander Mott 24.1 51 |(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
52 |(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown
Alexander Mott 22.2 53
54 //Figure 2// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:Wiring Guide.Wiring Overview.Cresnet.WebHome]].
Alexander Mott 1.1 55 )))
56
57
58 (% class="col-xs-12 col-sm-4" %)
59 (((
Alexander Mott 18.1 60 [[[[image:wiki_zumwired trans.png]]>>attach:wiki_zumwired trans.png]]
Alexander Mott 11.2 61 //Figure 1: Overview of a typical Zūm Wired space [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumwired%20trans.png?rev=1.1]]//
Alexander Mott 1.1 62
Alexander Mott 18.1 63 [[[[image:wiki_zumlink to cresnet.png||alt="image2.jpg"]]>>attach:wiki_zumlink to cresnet.png]]
Alexander Mott 22.2 64 //Figure 2: Zūm Link to Cresnet Wiring [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumlink%20to%20cresnet.png?rev=1.1]] - white/blue and green wire left bare for illustration purposes only; during actual installation they should be capped and insulated.//