Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Zūm Wired
1 +Zūm Wired Wiring Overview
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.WebHome
1 +SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.WebHome
Content
... ... @@ -2,15 +2,24 @@
2 2  (((
3 3  (% class="col-xs-12 col-sm-8" %)
4 4  (((
5 -Zūm Wired is a distributed lighting control system manufactured by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, DMX, and DALI protocols to allow for automated control of a building's lighting.
5 +(% class="box errormessage" %)
6 +(((
7 +All Category 5e/6a cabling must be terminated with standard, closed-end RJ-45 connectors. Cables terminated with "EZ" or passthrough connectors are known to cause networking and communications issues.
8 +)))
6 6  
7 -A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same cables and connectors as Ethernet. The three networks in a Zūm Wired system that adhere to Ethernet standards are:
10 +(% class="row" %)
11 +(((
12 +(% class="col-xs-12 col-sm-8" %)
13 +(((
14 +Zūm Wired is a distributed lighting control system manufactured by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, and DALI protocols to allow for automated control of a building's lighting.
8 8  
16 +A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same cables and connectors as Ethernet. The three networks in a Zūm Wired system are:
17 +
9 9  * Ethernet
10 10  * Zūm Net
11 11  * Zūm Link
12 12  
13 -Additionally, traditional 4-wire Cresnet can be wired directly into a Zūm Link network; [[wiring details below>>WebHome||anchor="HZ16BmLinktoCresnet"]].
22 +Additionally, traditional 4-wire Cresnet can be wired directly into a Zūm Link network; [[wiring details below>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HZ16BmLinktoCresnet"]].
14 14  
15 15  = Ethernet =
16 16  
... ... @@ -20,13 +20,13 @@
20 20  
21 21  Zūm Net wiring should adhere to Ethernet cabling standards and use standard RJ-45 connectors. Zūm Net connects networked room-level controllers throughout the building to each other and to the lighting network. Each Zūm Net run will typically originate at a Hub or Processor panel and then connect to a number of ZUMNET-JBOX devices.
22 22  
23 -Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable is shown in purple on //[[Figure 1>>WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices.
32 +Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable is shown in purple on //[[Figure 1>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices.
24 24  
25 25  ZUMNET-JBOX devices are covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
26 26  
27 27  = Zūm Link =
28 28  
29 -Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a room to the ZUMNET-JBOX for that room. Zūm Link cable is shown in orange on //[[Figure 1>>WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm Net devices. Additionally, **do not loop Zūm Link runs back to a Zūm Net device**; each Zūm Link run should originate at an orange Zūm Link port on a Zūm Net device and end at the last Zūm Link device on the run.
38 +Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a room to the ZUMNET-JBOX for that room. Zūm Link cable is shown in orange on //[[Figure 1>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm Net devices. Additionally, **do not loop Zūm Link runs back to a Zūm Net device**; each Zūm Link run should originate at an orange Zūm Link port on a Zūm Net device and end at the last Zūm Link device on the run.
30 30  
31 31  Links to articles covering specific Zūm Link devices can be found [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.WebHome]].
32 32  
... ... @@ -49,7 +49,7 @@
49 49  |(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
50 50  |(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown
51 51  
52 -//[[Figure 2>>WebHome||anchor="HFigure2"]]// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Cresnet.WebHome]].
61 +//[[Figure 2>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure2"]]// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Cresnet.WebHome]].
53 53  )))
54 54  
55 55  
... ... @@ -62,13 +62,15 @@
62 62  (% class="wikigeneratedid" id="HFigure1" %)
63 63  (((
64 64  [[[[image:wiki_zumwired trans.png]]>>attach:wiki_zumwired trans.png]]
65 -//Figure 1: Overview of a typical Zūm Wired system [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumwired%20trans.png?rev=1.2]]//
74 +//Figure 1: Overview of a typical Zūm Wired system [[(larger)>>attach:wiki_zumwired trans.png]]//
66 66  )))
67 67  
68 68  (% class="wikigeneratedid" id="HFigure2" %)
69 69  (((
70 70  [[[[image:wiki_zumlink to cresnet.png||alt="image2.jpg"]]>>attach:wiki_zumlink to cresnet.png]]
71 -//Figure 2: Zūm Link to Cresnet Wiring [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumlink%20to%20cresnet.png?rev=1.1]] - white/blue and green wire left bare for illustration purposes only; during actual installation they should be capped and insulated.//
80 +//Figure 2: Zūm Link to Cresnet Wiring [[(larger)>>attach:wiki_zumlink to cresnet.png]] - white/blue and green wire left bare for illustration purposes only; during actual installation they should be capped and insulated.//
72 72  )))
73 73  )))
74 74  )))
84 +)))
85 +)))