1 -{{box title="**CONTENTS**"}}
2 -{{toc/}}
3 -{{/box}}
1 +(% class="row" %)
2 +(((
3 +(% class="col-xs-12 col-sm-8" %)
4 +(((
5 +(% class="box errormessage" %)
6 +(((
7 +All Category 5e/6a cabling must be terminated with standard, closed-end RJ-45 connectors. Cables terminated with "EZ" or passthrough connectors are known to cause networking and communications issues.
8 +)))
4 4  
5 5  (% class="row" %)
6 6  (((
7 7  (% class="col-xs-12 col-sm-8" %)
8 8  (((
9 -= Overview =
14 +Zūm Wired is a distributed lighting control system manufactured by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, and DALI protocols to allow for automated control of a building's lighting.
10 10  
11 -Zūm Wired is a distributed lighting control system manufactured by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, DMX, and DALI protocols to allow for automated control of a building's lighting.
16 +A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same cables and connectors as Ethernet. The three networks in a Zūm Wired system are:
12 12  
13 -A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same cables and connectors as Ethernet. The three networks in a Zūm Wired system that adhere to Ethernet standards are:
14 -
15 15  * Ethernet
16 16  * Zūm Net
17 17  * Zūm Link
18 18  
19 -Additionally, traditional 4-wire Cresnet can be wired directly into a Zūm Link network; [[wiring details below>>WebHome||anchor="HZ16BmLinktoCresnet"]].
22 +Additionally, traditional 4-wire Cresnet can be wired directly into a Zūm Link network; [[wiring details below>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HZ16BmLinktoCresnet"]].
20 20  
21 21  = Ethernet =
22 22  
... ... @@ -26,13 +26,13 @@
26 26  
27 27  Zūm Net wiring should adhere to Ethernet cabling standards and use standard RJ-45 connectors. Zūm Net connects networked room-level controllers throughout the building to each other and to the lighting network. Each Zūm Net run will typically originate at a Hub or Processor panel and then connect to a number of ZUMNET-JBOX devices.
28 28  
29 -Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable is shown in purple on //[[Figure 1>>WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices.
32 +Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable is shown in purple on //[[Figure 1>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices.
30 30  
31 31  ZUMNET-JBOX devices are covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
32 32  
33 33  = Zūm Link =
34 34  
35 -Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a room to the ZUMNET-JBOX for that room. Zūm Link cable is shown in orange on //[[Figure 1>>WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm Net devices. Additionally, **do not loop Zūm Link runs back to a Zūm Net device**; each Zūm Link run should originate at an orange Zūm Link port on a Zūm Net device and end at the last Zūm Link device on the run.
38 +Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a room to the ZUMNET-JBOX for that room. Zūm Link cable is shown in orange on //[[Figure 1>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm Net devices. Additionally, **do not loop Zūm Link runs back to a Zūm Net device**; each Zūm Link run should originate at an orange Zūm Link port on a Zūm Net device and end at the last Zūm Link device on the run.
36 36  
37 37  Links to articles covering specific Zūm Link devices can be found [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.WebHome]].
38 38  
... ... @@ -55,22 +55,28 @@
55 55  |(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
56 56  |(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown
57 57  
58 -//[[Figure 2>>WebHome||anchor="HFigure2"]]// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Cresnet.WebHome]].
61 +//[[Figure 2>>SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure2"]]// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Cresnet.WebHome]].
59 59  )))
60 60  
61 61  
62 62  (% class="col-xs-12 col-sm-4" %)
63 63  (((
67 +{{box title="**CONTENTS**"}}
68 +{{toc/}}
69 +{{/box}}
70 +
64 64  (% class="wikigeneratedid" id="HFigure1" %)
65 65  (((
66 66  [[[[image:wiki_zumwired trans.png]]>>attach:wiki_zumwired trans.png]]
67 -//Figure 1: Overview of a typical Zūm Wired system [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumwired%20trans.png?rev=1.2]]//
74 +//Figure 1: Overview of a typical Zūm Wired system [[(larger)>>attach:wiki_zumwired trans.png]]//
68 68  )))
69 69  
70 70  (% class="wikigeneratedid" id="HFigure2" %)
71 71  (((
72 72  [[[[image:wiki_zumlink to cresnet.png||alt="image2.jpg"]]>>attach:wiki_zumlink to cresnet.png]]
73 -//Figure 2: Zūm Link to Cresnet Wiring [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumlink%20to%20cresnet.png?rev=1.1]] - white/blue and green wire left bare for illustration purposes only; during actual installation they should be capped and insulated.//
80 +//Figure 2: Zūm Link to Cresnet Wiring [[(larger)>>attach:wiki_zumlink to cresnet.png]] - white/blue and green wire left bare for illustration purposes only; during actual installation they should be capped and insulated.//
74 74  )))
75 75  )))
76 76  )))
84 +)))
85 +)))