... ... @@ -16,7 +16,7 @@
16 16  * Zūm Net
17 17  * Zūm Link
18 18  
19 -Additionally, traditional 4-wire Cresnet can be wired directly into a Zūm Link network; [[wiring details below>>xwiki:Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HZ16BmLinktoCresnet"]].
19 +Additionally, traditional 4-wire Cresnet can be wired directly into a Zūm Link network; [[wiring details below>>WebHome||anchor="HZ16BmLinktoCresnet"]].
20 20  
21 21  == Ethernet ==
22 22  
... ... @@ -26,13 +26,13 @@
26 26  
27 27  Zūm Net wiring should adhere to Ethernet cabling standards and use standard RJ-45 connectors. Zūm Net connects networked room-level controllers throughout the building to each other and to the lighting network. Each Zūm Net run will typically originate at a Hub or Processor panel and then connect to a number of ZUMNET-JBOX devices.
28 28  
29 -Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable is shown in purple on //[[Figure 1>>xwiki:Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices.
29 +Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable is shown in purple on //[[Figure 1>>WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices.
30 30  
31 -ZUMNET-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
31 +ZUMNET-JBOX devices are covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
32 32  
33 33  == Zūm Link ==
34 34  
35 -Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a room to the ZUMNET-JBOX for that room. Zūm Link cable is shown in orange on //[[Figure 1>>xwiki:Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm Net devices. Additionally, **do not loop Zūm Link runs back to a Zūm Net device**; each Zūm Link run should originate at an orange Zūm Link port on a Zūm Net device and end at the last Zūm Link device on the run.
35 +Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a room to the ZUMNET-JBOX for that room. Zūm Link cable is shown in orange on //[[Figure 1>>WebHome||anchor="HFigure1"]]//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm Net devices. Additionally, **do not loop Zūm Link runs back to a Zūm Net device**; each Zūm Link run should originate at an orange Zūm Link port on a Zūm Net device and end at the last Zūm Link device on the run.
36 36  
37 37  Links to articles covering specific Zūm Link devices can be found [[here>>doc:Wiring Guide.Zūm Wired System Overview.WebHome]].
38 38  
... ... @@ -55,7 +55,7 @@
55 55  |(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
56 56  |(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown
57 57  
58 -//[[Figure 2>>xwiki:Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HFigure2"]]// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Cresnet.WebHome]].
58 +//[[Figure 2>>WebHome||anchor="HFigure2"]]// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Cresnet.WebHome]].