Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Zūm Wired
1 +*Zūm Wired
Content
... ... @@ -10,17 +10,17 @@
10 10  
11 11  Zūm Wired is a distributed lighting control system manufactured and distributed by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, DMX, and DALI protocols to allow for automated control of a building's lighting.
12 12  
13 -A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same cables and connectors as Ethernet. The three networks in a Zūm Wired system that adhere to Ethernet standards are:
13 +A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same Ethernet wiring standards. The three networks in a Zūm Wired system that use Ethernet standard cabling are:
14 14  
15 15  * Ethernet
16 16  * Zūm Net
17 17  * Zūm Link
18 18  
19 -Additionally, traditional 4-wire Cresnet can be thought of as a subset oZūm Link, and details on how to wire Cresnet into a Zūm Link network can be found below.
19 +In addition to the three networks listed above, there are two additional wiring standards that may be encountered to connect non-Zūm devices to the Zūm Link network, which are covered below under the Zūm Link section
20 20  
21 21  == Ethernet ==
22 22  
23 -Ethernet provides the backbone of the lighting network. Ethernet joins the Hub panels to each other, the processor, and (if the design calls for it) the building LAN. All Ethernet cabling should adhere to the [[Ethernet standards>>doc:Wiring Guide.Wiring Overview.Ethernet.WebHome]] for Crestron systems.
23 +Ethernet provides the backbone of the lighting network. Ethernet joins the Hub panels to each other, the processor, and (if the design calls for it) the building LAN. All Ethernet cabling should adhere to the [[Ethernet standards>>doc:Wiring Guide.Wiring Overview.Ethernet.WebHome]] as covered elsewhere on this wiki.
24 24  
25 25  == Zūm Net ==
26 26  
... ... @@ -30,7 +30,7 @@
30 30  
31 31  == Zūm Link ==
32 32  
33 -Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. Links to articles covering specific Zūm Link devices can be found [[here>>doc:Wiring Guide.Zūm Wired System Overview.WebHome]].
33 +Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. ZUMLINK-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMLINK-JBOX).WebHome]].
34 34  
35 35  === Zūm Link to Cresnet ===
36 36  
... ... @@ -40,18 +40,21 @@
40 40  
41 41  The pin-out to connect a Cresnet device to a Zūm Link network that has been terminated per the T568B standard is as follows:
42 42  
43 -(% border="1" style="margin-right:auto" %)
44 -|=(% style="width: 87px;" %)RJ-45 Pin|=(% style="width: 213px;" %)Function|=(% style="width: 257px;" %)Cresnet Color|=(% style="width: 426px;" %)T568-B Color
45 -|(% style="width:87px" %)1|(% style="width:213px" %)24V|(% colspan="1" rowspan="2" style="width:257px" %)Red|(% style="width:426px" %)White / Orange
46 -|(% style="width:87px" %)2|(% style="width:213px" %)24V|(% style="width:426px" %)Orange
47 -|(% style="width:87px" %)3|(% style="width:213px" %)GND|(% colspan="1" rowspan="2" style="width:257px" %)Black|(% style="width:426px" %)White / Green
48 -|(% style="width:87px" %)4|(% style="width:213px" %)GND|(% style="width:426px" %)Blue
49 -|(% style="width:87px" %)5|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)White / Blue
50 -|(% style="width:87px" %)6|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)Green
51 -|(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
52 -|(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown
43 +|RJ-45 Pin|Function|Cresnet Color|T568-B Color
44 +| | | |
45 +| | | |
46 +| | | |
47 +| | | |
48 +| | | |
49 +| | | |
50 +| | | |
51 +| | | |
53 53  
54 54  //Figure 2// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:Wiring Guide.Wiring Overview.Cresnet.WebHome]].
54 +
55 +=== Non-System Sensor Integration ===
56 +
57 +L