Summary

Details

Page properties
Content
... ... @@ -10,13 +10,13 @@
10 10  
11 11  Zūm Wired is a distributed lighting control system manufactured and distributed by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, DMX, and DALI protocols to allow for automated control of a building's lighting.
12 12  
13 -A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same Ethernet wiring standards. The three networks in a Zūm Wired system that use Ethernet standard cabling are:
13 +A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same cables and connectors as Ethernet. The three networks in a Zūm Wired system that adhere to Ethernet standards are:
14 14  
15 15  * Ethernet
16 16  * Zūm Net
17 17  * Zūm Link
18 18  
19 -In addition to the three networks listed above, there are two additional wiring standards that may be encountered to connect non-Zūm devices to the Zūm Link network, which are covered below under the Zūm Link section
19 +Additionally, traditional 4-wire Cresnet can be thought of as a subset oZūm Link, and details on how to wire Cresnet into a Zūm Link network can be found below.
20 20  
21 21  == Ethernet ==
22 22  
... ... @@ -30,7 +30,7 @@
30 30  
31 31  == Zūm Link ==
32 32  
33 -Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. ZUMLINK-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMLINK-JBOX).WebHome]].
33 +Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. Links to articles covering specific Zūm Link devices can be found [[here>>doc:Wiring Guide.Zūm Wired System Overview.WebHome]].
34 34  
35 35  === Zūm Link to Cresnet ===
36 36  
... ... @@ -46,8 +46,8 @@
46 46  |(% style="width:87px" %)2|(% style="width:213px" %)24V|(% style="width:426px" %)Orange
47 47  |(% style="width:87px" %)3|(% style="width:213px" %)GND|(% colspan="1" rowspan="2" style="width:257px" %)Black|(% style="width:426px" %)White / Green
48 48  |(% style="width:87px" %)4|(% style="width:213px" %)GND|(% style="width:426px" %)Blue
49 -|(% style="width:87px" %)5|(% colspan="1" rowspan="2" style="width:213px" %)N/C|(% colspan="1" rowspan="2" style="width:257px" %)N/C|(% style="width:426px" %)White / Blue
50 -|(% style="width:87px" %)6|(% style="width:426px" %)Green
49 +|(% style="width:87px" %)5|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)White / Blue
50 +|(% style="width:87px" %)6|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)Green
51 51  |(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
52 52  |(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown