11 11  Zūm Wired is a distributed lighting control system manufactured and distributed by Crestron that is set to replace the older Cresnet-based GLPP hardware. It uses industry standard 0-10V, phase dimming, DMX, and DALI protocols to allow for automated control of a building's lighting.
12 12  
13 -A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same Ethernet wiring standards. The three networks in a Zūm Wired system that use Ethernet standard cabling are:
13 +A Zūm Wired system consists of several devices that are joined on three distinct networks that each use the same cables and connectors as Ethernet. The three networks in a Zūm Wired system that adhere to Ethernet standards are:
14 14  
15 15  * Ethernet
16 16  * Zūm Net
17 17  * Zūm Link
18 18  
19 -In addition to the three networks listed above, there are two additional wiring standards that may be encountered to connect non-Zūm devices to the Zūm Link network, which are covered below under the Zūm Link section
19 +Additionally, traditional 4-wire Cresnet can be thought of as a subset oZūm Link, and details on how to wire Cresnet into a Zūm Link network can be found [[below>>xwiki:Wiring Guide.Wiring Overview.Zūm Net.WebHome||anchor="HZ16BmLinktoCresnet"]].
20 20  
21 21  == Ethernet ==
22 22  
... ... @@ -26,12 +26,16 @@
26 26  
27 27  Zūm Net wiring should adhere to Ethernet cabling standards and use standard RJ-45 connectors. Zūm Net connects networked room-level controllers throughout the building to each other and to the lighting network. Each Zūm Net run will typically originate at a Hub or Processor panel and then connect to a number of ZUMNET-JBOX devices.
28 28  
29 -Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable and devices are shown in purple on //Figure 1//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. ZUMNET-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
29 +Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable and devices are shown in purple on //Figure 1//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices.
30 30  
31 +ZUMNET-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
32 +
31 31  == Zūm Link ==
32 32  
33 -Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. ZUMLINK-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMLINK-JBOX).WebHome]].
35 +Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm Net devices. Additionally, **do not loop Zūm Link runs back to a Zūm Net device**; each Zūm Link run should originate at an orange Zūm Link port on a Zūm Net device and end at the last Zūm Link device on the run.
34 34  
37 +Links to articles covering specific Zūm Link devices can be found [[here>>doc:Wiring Guide.Zūm Wired System Overview.WebHome]].
38 +
35 35  === Zūm Link to Cresnet ===
36 36  
37 37  While most Zūm Link wiring will adhere to Ethernet cabling standards and utilize standard RJ-45 connectors, Zūm Link is not technically Ethernet. In some situations, it may be necessary to wire traditional Cresnet devices into a Zūm Link space.
... ... @@ -46,16 +46,12 @@
46 46  |(% style="width:87px" %)2|(% style="width:213px" %)24V|(% style="width:426px" %)Orange
47 47  |(% style="width:87px" %)3|(% style="width:213px" %)GND|(% colspan="1" rowspan="2" style="width:257px" %)Black|(% style="width:426px" %)White / Green
48 48  |(% style="width:87px" %)4|(% style="width:213px" %)GND|(% style="width:426px" %)Blue
49 -|(% style="width:87px" %)5|(% colspan="1" rowspan="2" style="width:213px" %)N/C|(% colspan="1" rowspan="2" style="width:257px" %)N/C|(% style="width:426px" %)White / Blue
50 -|(% style="width:87px" %)6|(% style="width:426px" %)Green
53 +|(% style="width:87px" %)5|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)White / Blue
54 +|(% style="width:87px" %)6|(% colspan="1" style="width:213px" %)(N/C)|(% colspan="1" style="width:257px" %)(N/C)|(% style="width:426px" %)Green
51 51  |(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
52 52  |(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown
53 53  
54 54  //Figure 2// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:Wiring Guide.Wiring Overview.Cresnet.WebHome]].
55 -
56 -=== Non-System Sensor Integration ===
57 -
58 -L
59 59  )))
60 60  
61 61  