... ... @@ -14,26 +14,45 @@
14 14  
15 15  * Ethernet
16 16  * Zūm Net
17 -* Zūm Link - each Zūm Link run originates at a ZUMNET-JBOX and connects various Zūm Link devices within a a room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green.
17 +* Zūm Link
18 18  
19 19  In addition to the three networks listed above, there are two additional wiring standards that may be encountered to connect non-Zūm devices to the Zūm Link network, which are covered below under the Zūm Link section
20 20  
21 21  == Ethernet ==
22 22  
23 -Ethernet provides the backbone of the lighting network. Ethernet joins the Hub panels to each other, the processor, and (if the design calls for it) the building LAN. All Ethernet cabling should adhere to the [[Ethernet standards>>doc:Wiring Guide.Wiring Overview.Ethernet.WebHome]] as covered elsewhere on this wiki.
23 +Ethernet provides the backbone of the lighting network. Ethernet joins the Hub panels to each other, the processor, and (if the design calls for it) the building LAN. All Ethernet cabling should adhere to the [[Ethernet standards>>doc:Wiring Guide.Wiring Overview.Ethernet.WebHome]] for Crestron systems.
24 24  
25 25  == Zūm Net ==
26 26  
27 -Zūm Net connects networked room-level controllers throughout the space to each other and to the lighting network. Each Zūm Net run will typically originate at a Hub or Processor panel and then connect to a number of ZUMNET-JBOX devices. There should be one ZUMNET-JBOX per room. Zūm Net cable and devices are shown in purple on //Figure 1//
27 +Zūm Net wiring should adhere to Ethernet cabling standards and use standard RJ-45 connectors. Zūm Net connects networked room-level controllers throughout the building to each other and to the lighting network. Each Zūm Net run will typically originate at a Hub or Processor panel and then connect to a number of ZUMNET-JBOX devices.
28 28  
29 +Typically, there is only one ZUMNET-JBOX per room. Zūm Net cable and devices are shown in purple on //Figure 1//. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. ZUMNET-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMNET-JBOX).WebHome]].
30 +
29 29  == Zūm Link ==
30 30  
31 -Lo
33 +Zūm Link runs originate at a ZUMNET-JBOX and connect various Zūm Link devices within a a room to the ZUMNET-JBOX for that room. Zūm Link cable and JBOX devices are shown in orange on //Figure 1//, while Zūm Link keypads are shown in green with orange outline. **It is very important to never connect a Zūm Link cable to a Zūm Net port** as this may damage the Zūm net devices. ZUMLINK-JBOX devices are covered in more detail [[here>>doc:Wiring Guide.Zūm Wired System Overview.Load Controllers (ZUMLINK-JBOX).WebHome]].
32 32  
33 33  === Zūm Link to Cresnet ===
34 34  
35 -L
37 +While most Zūm Link wiring will adhere to Ethernet cabling standards and utilize standard RJ-45 connectors, Zūm Link is not technically Ethernet. In some situations, it may be necessary to wire traditional Cresnet devices into a Zūm Link space.
36 36  
39 +In the future, Crestron will be producing a ZUMLINK-CNRJ45 adapter to allow for plug-and-play connections between Zūm Link RJ-45 connectors and 4-wire Cresnet devices. Until this product is available however, it is necessary to strip the Zūm Link wire and terminate it directly into a Cresnet phoenix connector or terminal block.
40 +
41 +The pin-out to connect a Cresnet device to a Zūm Link network that has been terminated per the T568B standard is as follows:
42 +
43 +(% border="1" style="margin-right:auto" %)
44 +|=(% style="width: 87px;" %)RJ-45 Pin|=(% style="width: 213px;" %)Function|=(% style="width: 257px;" %)Cresnet Color|=(% style="width: 426px;" %)T568-B Color
45 +|(% style="width:87px" %)1|(% style="width:213px" %)24V|(% colspan="1" rowspan="2" style="width:257px" %)Red|(% style="width:426px" %)White / Orange
46 +|(% style="width:87px" %)2|(% style="width:213px" %)24V|(% style="width:426px" %)Orange
47 +|(% style="width:87px" %)3|(% style="width:213px" %)GND|(% colspan="1" rowspan="2" style="width:257px" %)Black|(% style="width:426px" %)White / Green
48 +|(% style="width:87px" %)4|(% style="width:213px" %)GND|(% style="width:426px" %)Blue
49 +|(% style="width:87px" %)5|(% colspan="1" rowspan="2" style="width:213px" %)N/C|(% colspan="1" rowspan="2" style="width:257px" %)N/C|(% style="width:426px" %)White / Blue
50 +|(% style="width:87px" %)6|(% style="width:426px" %)Green
51 +|(% style="width:87px" %)7|(% style="width:213px" %)Cresnet Y (Data +)|(% style="width:257px" %)White|(% style="width:426px" %)White / Brown
52 +|(% style="width:87px" %)8|(% style="width:213px" %)Cresnet Z (Data -)|(% style="width:257px" %)Blue|(% style="width:426px" %)Brown
53 +
54 +//Figure 2// illustrates how a Zūm Link cable should be terminated at a Cresnet phoenix connector (recall that the standard left-to-right color code for Cresnet wiring is red-white-blue-black). Cresnet wiring is covered in more detail [[here>>doc:Wiring Guide.Wiring Overview.Cresnet.WebHome]].
55 +
37 37  === Non-System Sensor Integration ===
38 38  
39 39  L
... ... @@ -42,10 +42,10 @@
42 42  
43 43  (% class="col-xs-12 col-sm-4" %)
44 44  (((
45 -[[image:wiki_zumwired trans.png]]
64 +[[[[image:wiki_zumwired trans.png]]>>attach:wiki_zumwired trans.png]]
46 46  //Figure 1: Overview of a typical Zūm Wired space [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumwired%20trans.png?rev=1.1]]//
47 47  
48 -[[image:Templates.Article.Template.WebHome@image2.jpg]]
49 -//Figure 2: [[Waves>>https://commons.wikimedia.org/wiki/File:Culebra_-_Playa_de_Flamenco.jpg]]//
67 +[[[[image:wiki_zumlink to cresnet.png||alt="image2.jpg"]]>>attach:wiki_zumlink to cresnet.png]]
68 +//Figure 2: Zūm Link to Cresnet Wiring [[(larger)>>https://wiki.chiefintegrations.com/download/Wiring%20Guide/Wiring%20Overview/Z%C5%ABm%20Net/WebHome/wiki_zumlink%20to%20cresnet.png?rev=1.1]] - white/blue and green wire left bare for illustration purposes only; during actual installation they should be capped and insulated.//
50 50  )))
51 51  )))
image1.jpg
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.MarkKohlmann
Size
... ... @@ -1,1 +1,0 @@
1 -43.8 KB
Content
image2.jpg
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.MarkKohlmann
Size
... ... @@ -1,1 +1,0 @@
1 -40.0 KB
Content
wiki_zumlink to cresnet.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.alexander\.mott@chiefintegrations\.com
Size
... ... @@ -1,0 +1,1 @@
1 +759.1 KB
Content