9 = Ethernet Wiring =
10
11 Ethernet is used for various devices within a Crestron Lighting Control system, including connecting a lighting control processor to the lighting network, connecting Zūm Net devices to the lighting network, connecting TSW touch-screen interfaces to the lighting network, and connecting the lighting network itself to a building network (building LAN).
12
13 == Cabling ==
14
15 All cable should be Category 5e or greater (including Category 6 and Category 6a).
16
17 The maximum length of any single ethernet run is 100 meters (328 feet). Runs longer than this will require a powered ethernet switch (such as a CEN-SW-POE-5) to be installed midway through the run to enable proper communication.
18
19 == Terminations ==
20
21 Cresnet Ethernet devices require the use of RJ-45 connectors.
22
23 While either T568A or T568B termination pin-out are acceptable as long as they are used consistently, it is **recommended to use the T568B pin-out for all terminations.** By keeping to one standard, it is easier to stay consistent and prevent errors where the two sides of a single cable are not terminated to the same standard.
24
25 See// Figure 1 //for the T568-B pin-out.
26
27 When making RJ-45 terminations, take care that the wires are in the correct order and pushed all the way to the end of the connector. A crimping tool with sharp blades that have not been dulled with use also helps in making good terminations.