5 Communications between Crestron Cresnet devices occurs on the Cresnet bus. Cresnet is Crestron's proprietary 4-wire communications network that provides both 24V DC power and low-voltage, bidirectional communication that adheres to to RS-485 standards.
6
7 Each job with Cresnet devices will have at least one Cresnet bus network. Every Cresnet bus network has a single //host// or //primary// device and one or more //client// or //secondary// devices (older materials may refer to hosts as //masters// and clients as //slaves//). Every Cresnet device on a Cresnet bus must be assigned a unique, one-byte hexadecimal Cresnet address. The range of available addresses is determined by the bus host:
8
9 (% class="table-condensed" %)
10 |=(% style="width: 171px;" %)Host|=(% style="width: 96px;" %)Available Addresses|=Start|=End|=Notes
11 |(% style="width:171px" %)3-Series or
12 4-Series processors|(% style="width:96px" %)252|03|FE|Chief Integrations has experienced significant communications slowdowns on systems with more than 100 devices, and recommends using DIN-CENCN-2(-POE) or additional processors to break up larger Cresnet bus networks
13 |(% style="width:171px" %)(((
14 DIN-CENCN-2 or
15 DIN-CENCN-2-POE
16 )))|(% style="width:96px" %)(((
17 25 per Net (50 total)
18 )))|03|1B|
19 |(% style="width:171px" %)ZUMNET-JBOX-16A-LV
20 or ZUMNET-JBOX-DALI|(% style="width:96px" %)32|03|22|(((
21 ZUMNET-JBOX local controller counts as a device; only 31 additional Zūm Link or Cresnet devices may be connected
22
23 Zūm Link and Cresnet can be intermingled; more details are available [[here>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Zūm Wired Wiring Overview.WebHome]]
24 )))
25
26 Power considerations also play a role in determining the number of Cresnet devices which can be supported on a Cresnet bus, however we will not cover them here due to the wide array of variables which impact power calculations and determining whether there is sufficient power for a given device.
27
28 = Cabling =
29
30 Cresnet cabling provides the physical infrastructure for communication between Crestron Cresnet devices and consists of a 4-wire, 2-pair cable available directly from Crestron with either plenum and non-plenum rated jackets.
31
32 (% class="table-condensed" %)
33 |=(% style="width: 307px;" %)Pair|=(% style="width: 287px;" %)Color|=(% style="width: 380px;" %)Purpose
34 |(% colspan="1" rowspan="2" style="width:307px" %)18 AWG pair|(% style="width:287px" %)Red|(% style="width:380px" %)24 V DC Power
35 |(% style="width:287px" %)Black|(% style="width:380px" %)Common
36 |(% colspan="1" rowspan="2" style="width:307px" %)22 AWG shielded twisted pair|(% style="width:287px" %)White|(% style="width:380px" %)Data +
37 |(% style="width:287px" %)Blue|(% style="width:380px" %)Data -
38
39 (% class="wikigeneratedid" %)
40 Terminations
41
42 Lorem ipsum dolor sit amet,
43
44 See //[[Figure 1>>WebHome||anchor="HFigure1"]]// for details.
45 See //[[Figure 2>>WebHome||anchor="HFigure2"]]// for details.
46
47 = Crestron Wiring Notes =
48
49 Crestron includes some general Cresnet wiring guidelines in their submittals. Many of these suggestions are covered above, but we have included them here for reference:
50
51 [[image:1704485841724-854.png]]
52 )))
53
54
55 (% class="col-xs-12 col-sm-4" %)
56 (((
57 {{box title="**Contents**"}}
58 {{toc/}}
59 {{/box}}
60
61 (% class="wikigeneratedid" id="HFigure1" %)
62 (((
63 [[image:Templates.Article.Template.WebHome@image1.jpg]]
64 //Figure 1: [[Sea>>https://commons.wikimedia.org/wiki/File:Isle_of_Icacos_II.jpg]]//
65 )))
66
67 (% class="wikigeneratedid" id="HFigure2" %)
68 (((
69 [[image:Templates.Article.Template.WebHome@image2.jpg]]
70 //Figure 2: [[Waves>>https://commons.wikimedia.org/wiki/File:Culebra_-_Playa_de_Flamenco.jpg]]//
71 )))
72 )))
73 )))