... ... @@ -6,18 +6,17 @@
6 6  
7 7  Each job with Cresnet devices will have at least one Cresnet bus network. Every Cresnet bus network has a single //host// or //primary// device and one or more //client// or //secondary// devices (older materials may refer to hosts as //masters// and clients as //slaves//). Every Cresnet device on a Cresnet bus must be assigned a unique, one-byte hexadecimal Cresnet address. The range of available addresses is determined by the bus host:
8 8  
9 -(% class="table-condensed" %)
10 -|=(% style="width: 171px;" %)Host|=(% style="width: 96px;" %)Available Addresses|=Start|=End|=Notes
11 -|(% style="width:171px" %)3-Series or
12 -4-Series processors|(% style="width:96px" %)252|03|FE|Chief Integrations has experienced significant communications slowdowns on systems with more than 100 devices, and recommends using DIN-CENCN-2(-POE) or additional processors to break up larger Cresnet bus networks
13 -|(% style="width:171px" %)(((
9 +|=(% style="width: 186px;" %)Host|=(% style="width: 62px;" %)Available Addresses|=Start|=End|=Notes
10 +|(% style="width:186px" %)3-Series or
11 +4-Series processors|(% style="width:62px" %)252|03|FE|Chief Integrations has experienced significant communications slowdowns on systems with more than 100 devices, and recommends using DIN-CENCN-2(-POE) or additional processors to break up larger Cresnet bus networks
12 +|(% style="width:186px" %)(((
14 14  DIN-CENCN-2 or
15 15  DIN-CENCN-2-POE
16 -)))|(% style="width:96px" %)(((
15 +)))|(% style="width:62px" %)(((
17 17  25 per Net (50 total)
18 18  )))|03|1B|
19 -|(% style="width:171px" %)ZUMNET-JBOX-16A-LV
20 -or ZUMNET-JBOX-DALI|(% style="width:96px" %)32|03|22|(((
18 +|(% style="width:186px" %)ZUMNET-JBOX-16A-LV or
19 +ZUMNET-JBOX-DALI|(% style="width:62px" %)32|03|22|(((
21 21  ZUMNET-JBOX local controller counts as a device; only 31 additional Zūm Link or Cresnet devices may be connected
22 22  
23 23  Zūm Link and Cresnet can be intermingled; more details are available [[here>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Troubleshooting.Zūm Wired Wiring Overview.WebHome]]
... ... @@ -36,8 +36,7 @@
36 36  |(% colspan="1" rowspan="2" style="width:307px" %)22 AWG shielded twisted pair|(% style="width:287px" %)White|(% style="width:380px" %)Data +
37 37  |(% style="width:287px" %)Blue|(% style="width:380px" %)Data -